48
Notifier SLC Wiring Manual —
P/N 51253:U5 12/20/2017
Section 10: Intelligent Detectors, Intelligent Detector Bases, and Wireless
Gateway
10.1 Description
10.1.1 Intelligent Detector Bases
Detector bases provide a connection between the SLC and a variety of intelligent detectors:
•
B501, B501-BL, B501-IV: 4-inch flangeless plug-in detector base. (FlashScan/CLIP; Figure 10.1)
•
B300-6: 6-inch plug-in detector base. White. For ivory, order B300-6-IV. Replacement model for B210LP. (FlashScan/CLIP;
•
B210LP: 6-inch flanged plug-in detector base. (FlashScan/CLIP; Figure 10.1)
•
B710HD Detector Base - used with all HARSH™ detectors. See Sections 10.2 – 10.5.
•
B224BI, B224BI-IV Isolator base (Figure 10.3)
•
B224RB, B224RB-IV (FlashScan/CLIP, plug-in relay detector base; Figure 10.4)
•
B200S, B200S-IV: Intelligent sounder base (See Figure 10.5)
•
B200S-LF, B200S-LF-IV: Intelligent low-frequency sounder base (See Figure 10.5)
•
B200SR, B200SR-IV: Intelligent programmable sounder base (See Figure 10.6)
•
B200SR-LF, B200SR-LF-IV: Intelligent programmable low-frequency sounder base (See Figure 10.6)
•
B501BH Standard sounder base.
•
B501BH-2 UL 864 9th edition compliant standard sounder base.
•
B501BHT-2 UL 864 9th edition compliant temporal sounder base, replaces B501BHT.
For more information refer to the
Installation Instructions
documents provided with these devices.
10.1.2 Intelligent Aspiration Detectors
The FSA-5000 Intelligent FAAST XS, FSA-8000 Intelligent FAAST XM, FSA-20000 Intelligent FAAST XT, and FSA-20000P Intelli-
gent FAAST XT PRO aspiration smoke detectors may be used to provide early warning fire protection using aspiration sensing technol-
ogy.
•
FSA-5000 covers 5,000 square feet through one pipe.
•
FSA-8000 covers 8000 square feet through one pipe.
•
FSA-20000 covers 28,800 square feet through one to four pipes
•
FSA-20000P covers 28,800 square feet through one to four addressable pipes
These detectors are listed with UL for use with the NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030. They support FlashScan mode
only (an early version of FSA-8000 supported CLIP only). See Section 10.6.
10.1.3 Wireless Gateway
The FWSG Wireless Gateway acts as a bridge between a group of wireless fire devices, and a FlashScan SLC loop on NFS-320, NFS-
320SYS, NFS2-640, and NFS2-3030 (version 22 and above). The gateway can be powered by the SLC loop or by an external 24 VDC,
UL-listed power supply. See Section 10.7.
For details about the wireless network itself, see the
SWIFT™ Smart Wireless Integrated Technology Instruction Manual.
NOTE:
Standard base color is White, “-BL” suffix indicates Black color model. “-IV” suffix indicates Ivory color model.
NOTE:
When a wireless relay is in use, modules device count must be limited to 109 modules per loop. This includes wired and wireless
modules that are on the same loop. The module address range must be within 1-109.