Notifier SLC Wiring Manual —
P/N 51253:U5 12/20/2017
11
SLC Overview
Introduction
1.4 SLC Overview
Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line
Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For
detailed information refer to Appendix B, “SLC Surge Suppression”, on page 62.
1.5 Polling Protocols
1.5.1 Available Protocols
FlashScan
FlashScan® is a patented system (US Patent Number 5,539,389) that greatly enhances the speed of communication between analog
intelligent devices. Communication is in a grouped fashion. If one of the devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. Not all panels are FlashScan® capable; see “Protocol Use” below.
FSI-751 Ion Detector Installation Document
I56-1249
FSI-851 Ion Detector Installation Document
FSI-851A Canadian
I56-1924
FSL-751 Laser Detector Installation Document
FSL-751A Canadian
I56-057
FSP-751 & FSP-751T Photo Installation Document
I56-1230
FSP-851, FSP-851T, and FAPT-851 Photoelectric Detectors Installation Document
FSP-851A, FSP-851TA, and FAPT-851A
I56-3524, I56-1925
I56-2296
FSP-851R Photoelectric Smoke Sensor with Remote Test Capability in Duct Applications Installation
FSP-851RA Canadian
I56-3549
I56-2231
FST-751 Thermal Detector Installation Document
I56-1234
FSP-951, FSP-951-IV Intelligent Photo Smoke Detector
FSP-951A, FSP-951A-IV Canadian
I56-6519
I56-2230
FSP-951R and FSP-951R-IV Intelligent Photo Smoke w/Remote Test Capability
FSP-951RA and FSP-951RA-IV Canadian
I56-6520
I56-2231
FSP-951T and FSP-951T-IV Intelligent Photo/Temperature Detector
FSP-951TA and FSP-951TA-IV Canadian
I56-6521
I56-2232
FST-951/-IV, FST-951R/-IV, FST-951H/-IV Intelligent Heat Detector
FST-951A/-IV, FST-951RA/-IV, FST-951HA/-IV Canadian
I56-6522
I56-2233
FST-751R Rate of Rise Sensor Installation Document
I56-1242
FST-851, FST-851R, and FST-851H Thermal Detectors Installation Document
FST-851A, FST-851RA, and FST-851HA Thermal Detectors Installation Document
I56-3518, I56-1926
I56-2301
FTM-1 Firephone Control Module, FTM-1A Firephone Control Module
FTM-1A Canadian
I56-3533, I56-2067
FZM-1 Zone Interface Module Installation Document
FZM-1A Canadian
I56-3504
I56-3207
HPX-751 HARSH™ Installation Document
I56-1250
ISO-X Isolator Module Installation Document
ISO-XA Canadian
I56-1380, I56-1070
I56-3624
ISO-6 Six Fault Isolator Module
ISO-6A Canadian
I56-4096
I56-4160
LPX-751 Laser Detector Installation Document
I56-748
LPX-751L Laser Detector Installation Document
I56-1793
NBG-12LX Pull Station Installation Document
51093
NBG-12LXSP Spanish-/English-Labeled Addressable Manual Pull Station
I56-2769 (English)
I56-2797 (Spanish)
NBG-12LXP Portuguese-Labeled Addressable Manual Pull Station
I56-2272
SLC-IM Listing Document
LS10026-051NF
FSA-5000(A) Intelligent FAAST
®
XS Installation and Maintenance Instructions
I56-6008
FSA-8000(A) Intelligent FAAST
®
XM Installation and Maintenance Instructions
I56-3903
FSA-20000(A) Intelligent FAAST
®
XT Installation and Maintenance Instructions
I56-4217
FSA-20000P Intelligent FAAST
®
XT PRO Installation and Maintenance Instructions
I56-6507
Note: Refer to the Device Compatibility Document for compatible conventional devices.
15378
Document Number
Table 1.1 Reference Documentation (3 of 3)