3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
7
31-00141M—03
Fig. 14. Wiring for modulating (0/2-10 VDC)
proportioning control, MS75 (shown) and MS71.
Fig. 15. Wiring for 4-20 mA proportioning controllers,
MS75 (shown) and MS71.
Fig. 16. Wiring for modulating (0/2-10 VDC)
proportioning control operating multiple actuators,
MS75 (shown) and MS71.
Fig. 17. Wiring for SYLK BUS control, MS3103.
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING IF AVAILABLE.
V
–
+
FEEDBACK
4
3
1
2
M37320
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
FLOATING
, FWD
FLOATING
, REV
3
0°-90°/MODULATING
90°-0°/FEEDBACK
RED
BLACK
BROWN
WHITE
CLASS 2
ACTUATOR
4 TO 20 mA
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
490 TO 510
OHMS,
1/2 W
MINIMUM
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING IF AVAILABLE.
V
–
+
FEEDBACK
4
3
1
2
M37321
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
FLOATING, FWD
FLOATING, REV
3
0°-90°/MODULATING
90°-0°/FEEDBACK
RED
BLACK
BROWN
WHITE
CLASS 2
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION
AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING
IF AVAILABLE.
V
–
+
FEEDBACK
4
3
1
2
M37322
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
FLOATING
, FWD
FLOATING
, REV
3
ACTUATOR
V
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
FLOATING
, FWD
FLOATING
, REV
3
0°-90°/MODULATING
90°-0°/FEEDBACK
RED
BLACK
BROWN
WHITE
0°-90°/MODULATING
90°-0°/FEEDBACK
RED
BLACK
BROWN
WHITE
CLASS 2
1
2
3
HOT
COM
CONTROLLER
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS
AND OVERLOAD
PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
ADDRESS SELECTOR
S-BUS
S-BUS
24 VAC
CLASS 2
S-BUS
S-BUS
RED
BLACK
BROWN
BROWN
ACTUATOR
ADDRESS 11
ADDRESS 12
ADDRESS 13
ADDRESS 14
ADDRESS 15
TEST