63-2740—02

6

OPERATION

The MS4104, MS4109, MS4604, MS4609, MS8104 and 

MS8109 DCA are designed for use in Smoke Control Systems. 

If power fails, the actuator spring returns to the 0° position. The 

actuator mounts flush with the damper box. The actuator drives 

from 0° to 95° and spring returns back to 0°.

The actuators are operated by an spst two-position controller. 

When using an spst two-position controller, the actuator drives 

to the damper fully open position when controller contact 

makes and spring returns to the damper fully closed position 

when controller contact breaks. The actuator drops to holding 

power level on detection of stall, independent of hub position.

Cycling

The actuator and the internal spring are designed so that no 

special cycling during long-term holding is required. Honeywell 

recommends following all local, state, and national codes for 

periodic testing of the entire smoke control system. Refer to 

National Fire Protection Association (NFPA) National Fire 

Codes

®

: NFPA90A, NFPA92A, and NFPA92B for your 

application.

NOTE: The actuator is designed to operate for 30 min-

utes during a one-time excursion to 350°F (176°C).

CHECKOUT

MS4104F, MS4109F (120 Vac model)

1.

Check damper position.

2.

Connect 120 Vac to the black and white leadwires to 

drive the damper to the open position. The actuator 

should drive the damper.

3.

If the actuator does not spring return, verify that the actu-

ator is properly installed. See Installation section.

4.

If the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

MS4604F, MS4609F (230 Vac model)

1.

Check damper position.

2.

Connect 230 Vac to the blue and brown leadwires to 

drive the damper to the open position. The actuator 

should drive the damper.

3.

If the actuator does not spring return, verify that the actu-

ator is properly installed. See Installation section.

4. I

f the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

MS8104F, MS8109F (24 Vac model)

1.

Check damper position.

2.

Connect 24 Vac to the red and black leadwires to drive 

the damper to the open position. The actuator should 

drive the damper.

3.

If the actuator does not spring return, verify that the actu-

ator is properly installed. See Installation section.

4.

If the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

National Fire Codes

®

 is a registered trademark of the National Fire Protection Association (NFPA).

Содержание MS4104F1010

Страница 1: ...either clockwise cw or counterclockwise ccw spring rotation Integral spring return ensures level of return torque Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power consumption Models available for 24 120 and 230 Vac Ninety five degree...

Страница 2: ...tuators because side loading of the output hub reduces actuator life Temperature Ratings Ambient 0 F to 130 F 18 C to 55 C Shipping and Storage 40 F to 140 F 40 C to 60 C IMPORTANT The actuator is designed to meet UL555S standards at 350 F 176 C The actuator must be tested with the damper to achieve this rating Humidity Ratings 5 to 95 RH noncondensing Noise Rating Maximum Driving Open 80 dBA at 1...

Страница 3: ...tion Association NFPA National Fire Codes NFPA90A NFPA92A and NFPA92B for your application NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper perfor mance Design Life at Rated Voltage 30 000 full stroke cycles Approvals See Table 3 Environmental Protection Ratings See Table 4 Accessories 205649 Mounting Bracket not supplied with actuator Table...

Страница 4: ... Location and Mounting The actuators are designed to open a damper by driving the damper shaft in either clockwise or counterclockwise direction The actuator housing has two slots on the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft CAUTION Equipment D...

Страница 5: ...ximum 130 lb in torque Use 1 4 in wrench see Specifications for details to tighten set screws Wiring See Fig 3 through 5 for typical wiring diagrams WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock individuals or short equ...

Страница 6: ...rsion to 350 F 176 C CHECKOUT MS4104F MS4109F 120 Vac model 1 Check damper position 2 Connect 120 Vac to the black and white leadwires to drive the damper to the open position The actuator should drive the damper 3 If the actuator does not spring return verify that the actu ator is properly installed See Installation section 4 If the actuator is correctly installed but neither runs nor spring retu...

Страница 7: ...7 63 2740 02 ...

Страница 8: ...d Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 63 2740 02 M S 05 13 Printed in Mexico ...

Отзывы: