MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

63-2740—02

4

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

IMPORTANT

All wiring must agree with applicable codes, 

ordinances and regulations.

WARNING

Electrical Power Hazard.

Line voltage can cause death or serious injury 

and short equipment circuitry.

Disconnect power supply before installation.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Low voltage can shock individuals or short 

equipment circuitry.

Disconnect power supply before installation.

Location and Mounting

The actuators are designed to open a damper by driving the 

damper shaft in either clockwise 

 or counterclockwise 

 direction. The actuator housing has two slots on the 

bottom that, with a 205649 Mounting Bracket, secure it flush to 

a damper box (see Fig. 2). When mounted correctly, these 

slots allow the actuator to 

float

 without rotating relative to the 

damper shaft.

CAUTION

Equipment Damage Hazard.

Tightly securing actuator to damper housing can 

damage actuator.

Mount actuator to allow it to float along its vertical axis.

Fig. 2. Mounting actuator to damper housing.

Preparation

Before mounting the actuator onto the damper shaft, 

determine the:

— Damper/valve opening direction for correct spring 

return rotation. The actuator can be mounted to provide 

clockwise or counterclockwise spring return.

— Damper shaft size (see Specifications section).

M34623

ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR 

ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG 

INDICATED AXIS.  WHEN TOO TIGHT, THE RESULTING  BINDING 

CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.

ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH 

THE ACTUATOR.

1

1

2

90

°

2

Содержание MS4104F1010

Страница 1: ...either clockwise cw or counterclockwise ccw spring rotation Integral spring return ensures level of return torque Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power consumption Models available for 24 120 and 230 Vac Ninety five degree...

Страница 2: ...tuators because side loading of the output hub reduces actuator life Temperature Ratings Ambient 0 F to 130 F 18 C to 55 C Shipping and Storage 40 F to 140 F 40 C to 60 C IMPORTANT The actuator is designed to meet UL555S standards at 350 F 176 C The actuator must be tested with the damper to achieve this rating Humidity Ratings 5 to 95 RH noncondensing Noise Rating Maximum Driving Open 80 dBA at 1...

Страница 3: ...tion Association NFPA National Fire Codes NFPA90A NFPA92A and NFPA92B for your application NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper perfor mance Design Life at Rated Voltage 30 000 full stroke cycles Approvals See Table 3 Environmental Protection Ratings See Table 4 Accessories 205649 Mounting Bracket not supplied with actuator Table...

Страница 4: ... Location and Mounting The actuators are designed to open a damper by driving the damper shaft in either clockwise or counterclockwise direction The actuator housing has two slots on the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft CAUTION Equipment D...

Страница 5: ...ximum 130 lb in torque Use 1 4 in wrench see Specifications for details to tighten set screws Wiring See Fig 3 through 5 for typical wiring diagrams WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock individuals or short equ...

Страница 6: ...rsion to 350 F 176 C CHECKOUT MS4104F MS4109F 120 Vac model 1 Check damper position 2 Connect 120 Vac to the black and white leadwires to drive the damper to the open position The actuator should drive the damper 3 If the actuator does not spring return verify that the actu ator is properly installed See Installation section 4 If the actuator is correctly installed but neither runs nor spring retu...

Страница 7: ...7 63 2740 02 ...

Страница 8: ...d Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 63 2740 02 M S 05 13 Printed in Mexico ...

Отзывы: