Page 28
Document No. 996-175-000-1, Revision 01
Commissioning Manual
•
Pressing any key then restores the display to the normal commissioning menu.
•
The Auto Learn sequence can be used as many times as required and does not affect the text
description used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the ‘Devices’ option to
obtain detailed information on the device type and to see the address of each device
found on the loop.
5.3.2 Calibrate
•
The calibrate function is identical to the routines described in Signalling Loops Section. Refer to
Section 5.2.2.
5.3.3 Zones
•
The Zone function is identical to the routines described in Signalling Loops Section. Refer to Section 5.2.3.
5.3.4 Devices
•
The ‘Devices’ option presents detailed information for the various types of peripheral device fitted on
the bus.
[ Panel in Commissioning mode ]
---------------------------------------------
P:012 Z003 "BOILER ROOM
"
Input unit S= 16 D8..D1= 00000001
The signal from the peripheral device is fixed at 16. It will drop to 0 if communications or
power to it is lost.
5.3.4.1
Changing Device Information
•
Changes are made by first pressing the ‘Change’ key. The display will present a menu of options that
can be changed, as follows:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Sensor Text 2)Zone 3)Event
6)Action 7)Group 9)Mode
•
Select the required option by pressing the appropriate number. Press the ‘No’ key to return to the
normal, device information display.
If only the device text can be changed, the display will jump straight to the location text.
Address Zone
Location
Text
Device Type
Analogue Signal
Digital inputs status
1=Logic High 0=Logic Low