Honeywell Modutrol IV M9164A 1013 Скачать руководство пользователя страница 13

SERIES 90 MODUTROL IV

 MOTORS

13

63-2631—07

CHECKOUT

After the installation and linkage adjustment, check the entire 

motor and control hookup. Proper checkout ensures that:

• The motor operates the load (damper or valve) properly.

• The motor responds properly to the controller as the input 

varies (See Table 12).

• The auxiliary switch, if used, operates at the desired point of 

motor rotation.

1.

Inspect motor, linkage, and valve or damper to ensure all 

mechanical connections are correct and secure.

NOTE: In damper installations, the pushrod should not 

extend more than a few inches past the ball 

joints.

2.

Ensure that there is adequate clearance for the linkage 

throughout the entire motor stroke without binding or 

striking other objects.

3.

Ensure the motor transformer is properly sized.

NOTE: If a common transformer is used to power multi-

ple motors, ensure the power input is in phase 

with all motors.

4.

Drive the motor fully open and fully closed 

(See Table 12).

NOTE: Refer to controller or system instructions for 

additional checkout procedures.

5.

For spring return motors, ensure that the valve or 

damper returns to normal position upon power interrup-

tion.

6.

Return the controller to the desired setting before leaving 

the job.

REPLACEMENT

Damper Application

1.

Turn off power and remove wiring from the old motor.

2.

Remove the crank arm from shaft of old motor and 

remove the old motor.

3.

Determine necessity of the mounting bracket. If the link-

age can reach the new motor shaft position and the 

crank arm has clearance for the necessary rotation, the 

bracket is not required. Use the 220738A Adapter 

Bracket or the 221455A Crank Arm if the crank arm must 

rotate through the bottom plane of the motor.

a. If no bracket is required, mount the new motor 

directly to the equipment and refer to the Installation, 

Settings and Adjustments, and the Operation and 

Checkout sections of these instructions.

b. If the bracket is required, refer to the Adapter Bracket 

section and Fig. 3 in addition to the Installation, Set-

tings and Adjustments, and the Operation and 

Checkout sections of these instructions.

4.

Use No. 12 or 1/4 inch machine screws or bolts to mount 

the new motor.

5.

Mount damper crank arm and linkage to the new motor 

shaft.

6.

Use the Checkout procedures to test the crank arm and 

linkage adjustment.

Valve Application

When replacing a motor in a valve application, the linkage 

determines the necessity of the 220738A Adapter Bracket. 

With Q100, Q601 or Q618 Linkages, it is necessary to use the 

220738A to raise the motor shaft to the appropriate height. 

Valve applications with a Q5001 Linkage do not require the 

220738A Adapter Bracket. To operate Honeywell V5011 

two-way or V5013 three-way valves through full stroke, use a 

160° stroke motor or make sure the stroke is adjusted to 160 

degrees.

Содержание Modutrol IV M9164A 1013

Страница 1: ...eight of older motors is available Motors have field adjustable stroke 90 to 160 Die cast aluminum housing Integral auxiliary switches are available factory mounted or can be field added Nominal timing standard of 30 seconds 90 stroke and 60 seconds 160 stroke Other timings available Spring return motors can operate valve linkages form power end or auxiliary end shafts for normally closed or norma...

Страница 2: ...Number Guide See Table 1 Table 1 Modutrol IV Series 2 and 3 Model Number Guide NOTE Torque designation corresponds to torque rating at standard timing nominally 60 sec for 160 and 30 sec for 90 except for 300 lb in motors which have timings of 2 or 4 min Dimensions Refer to Fig 2 Electrical Ratings Refer to Table 2 Control Inputs Proportional Series 90 NOTE Motor Series 90 control can be either El...

Страница 3: ...ROKE 160 DEGREE STROKE NON SPRING RETURN MOTORS 160 10 90 45 SPRING RETURN MOTORS AND NON SPRING RETURN MOTORS ASYMMETRICAL MOTORS SYMMETRICAL MOTORS M18998D 4 7 8 124 5 1 2 140 13 16 20 4 1 16 103 1 4 7 1 1 2 37 5 1 2 140 JUNCTION BOX MOTOR AUXILIARY END POWER END ADAPTER BRACKET 2 9 16 66 5 3 8 137 6 7 16 164 9 16 15 3 4 19 TOP VIEW OF BRACKET TOP VIEW 4 5 8 116 4 1 4 107 2 5 16 58 11 16 17 4 7 ...

Страница 4: ...stor Board plugs onto Series 90 Motor quick connect wire terminals Provides same functionality as 4074BYK 4074EAU 4074EDC or 4074EED Resistor Kits 4074BYK Series 90 Resistor Kit provides for unison control of up to six Series 90 Motors 4074EAU W973 Resister Kit provides for control of two or three Series 90 Motors from a W973 Single zone Logic Panel or W7100 Discharge Air Controller 4074EDC 4 20 m...

Страница 5: ...ns and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors wi...

Страница 6: ... except the Q5001 To mount the motor with the bracket See Fig 3 1 Mount the bracket to the equipment with existing or stan dard bolts 2 Using the provided bolts mount the motor to the bracket threaded holes For valve linkage applications other than the Q5001 1 Mount the bracket to the linkage 2 Position the motor on the bracket to align the motor shaft with the linkage 3 Attach the motor to the br...

Страница 7: ...pply VA rating is large enough to provide power to all motors used without overloading 3 Fig 11 shows that the motor terminals are quick connects located on top of the printed circuit board 4 To access the wiring compartment a Remove the four screws from the junction box top b Lift off the cover 5 Refer to Fig 5 for typical wiring and Fig 7 for internal auxiliary switch connections NOTE Reverse mo...

Страница 8: ...PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M770A SERIES 90 CONTROLLER MOTOR L1 HOT L2 1 1 2 R W B R W B T1 T2 TRANSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M13708 135 OHM POTENTIOMETER MOTOR BLUE LEAD YELLOW LEAD RED LEAD USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY MEETS CLASS 2 REQUIREMENTS TAPE UNU...

Страница 9: ...6284D4004 S M6285A1005 S M6285A1054 S M6285A4009 S 600 Ohms No Yes No 187 Ohm M6274F1009 F M6284F1070 F M6284F1078 F M6285F1001 F M6294F1009 F M6294F1017 F M6284D1032 F 10 K Ohms No No Yes Not Available M6284A1071 S M6284A1089 S M6284C1028 S 196 346 Ohms Yes Yes No 274 Ohm M6284A1030 S M6284A1055 S M6284A1097 S M6284B1004 S M6284C1010 S M6284C1044 S M6284F1013 S M6284F1039 S M6285A1039 S M6285A104...

Страница 10: ... Motors Adjustable timing for M9182D1023 The timing potentiometer the second from the right Refer to Fig 10 sets the timing to 1minute if turned fully CCW 2 minutes if turned to its middle point and 4 minutes if turned fully CW CAUTION Careless Installation Hazard Use of excessive force while adjusting cams damages the motor To avoid damaging motor end switches set cams by moving only the top of t...

Страница 11: ...oth directions 9 Disconnect the potentiometer reconnect the controller and replace the motor top cover NOTE Changing the differential from 1 to 10 reverses the switching action For example with a 10 dif ferential switch contacts R B make and R W break on a counterclockwise closed rotation With a 1 differential switch contacts R W make and R B break on a counterclockwise closed rotation OPERATION U...

Страница 12: ...IFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM BLUE LEFT OUTER AUXILIARY SWITCH FAST RISEPORTION APPROX 1 DIFF 1 8 INCH STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED FAST RISE PORTION APPROX 1 DIFF FAST RISE PORTION APPROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM RED LEF...

Страница 13: ...the old motor 2 Remove the crank arm from shaft of old motor and remove the old motor 3 Determine necessity of the mounting bracket If the link age can reach the new motor shaft position and the crank arm has clearance for the necessary rotation the bracket is not required Use the 220738A Adapter Bracket or the 221455A Crank Arm if the crank arm must rotate through the bottom plane of the motor a ...

Страница 14: ...SERIES 90 MODUTROL IV MOTORS 63 2631 07 14 honeyvell energy ...

Страница 15: ...SERIES 90 MODUTROL IV MOTORS 15 63 2631 07 ...

Страница 16: ... 2631 07 M S Rev 11 12 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification t...

Отзывы: