background image

ML7999C UNIVERSAL PARALLEL-POSITIONING ACTUATOR

5

32-00079EF—01

Fig. 5. Opening ML7999C low-voltage wiring 

compartment.

Fig. 6. Typical ML7999C wiring.

OPERATION

ML7999C Universal Parallel-Positioning Actuator is 
designed to operate combustion air dampers, butterfly gas 
valves, oil modulation valves, and flue gas recirculation 
systems requiring up to 100 lb-in. torque. An R7999C 
controller operates the ML7999C.

The actuator has a position indicator that shows shaft 
position. As the indicator moves with the shaft, it provides 
an angular representation of the shaft position.

IMPORTANT

When the cover is removed and replaced, the 
position indicator will not operate until manually 
rotated clockwise to engage it. An audible click 
indicates the position indicator is engaged.

NOTE:

While installing the actuator, the hub can be 
manually driven using the push buttons located 
under the cover. The buttons are labeled CW and 
CCW. To use them, the only required wiring 
connections are L1, L2, and GND. However, after 
the device is installed and wired to the R7999, do 
not use these buttons for anything but 
troubleshooting.

Password Protection (ID Signal)

Before using the actuator, the ID signal must be set. See 
the software interface instructions for details. After this 
signal is set, the R7999C sends the signal to operate the 
actuator. Until the appropriate ID signal is sent, the 
actuator is offline and responds only to its own ID signal. 
(See Table 1.)

.

M16470

LINE VOLTAGE

WIRING

LOW 

VOLTAGE

WIRING

GND

L2 L1

DR1

DR2
CW

S

CCW

L2
L1

ML7999

R7999

M16469A

1/2 IN. MAXIMUM

TERMINATE WIRE SHIELD AT THE CONTROLLER (R7999).

SEE FIGURE 5 FOR ACTUATOR WIRING.

RUN LOW/LINE VOLTAGE IN SEPARATE CONDUIT.

1

2

1

2

G

3

3

Table 1. On-Board LED Indications

LED

Online

Configured

Meaning

Notes

Fast Blink

No

Yes

Awaiting ID signal.

Responds only to ID signal.

Slow Blink

Yes

Yes

ID signal recognized.

Monitors signals for operation or offline 
commands.

Steady On

No

No

Actuator has failed.

Return actuator to factory.

Содержание ML7999C

Страница 1: ...1 2 in 13 mm shaft with no additional parts required Couples directly to 5 16 in 8 mm and 3 8 in 9 mm shafts using available self centering shaft reduction accessories Shaft coupler assembly available for shafts larger than 1 2 in Bracket Accessory Kit available for mounting to Honeywell V51 Butterfly Gas Valves Visual indication of actuator position NEMA 3 rating with optional weatherproof kit UL...

Страница 2: ... 100 lb in 11 3 Nm Breakaway Minimum 100 lb in 11 3 Nm Stall Minimum 100 lb in 11 3 Nm Stall Maximum 150 lb in 17 Nm Actuator Design Life at 100 lb in Full Stroke Cycles 100 000 minimum Repositions 2 000 000 minimum Feedback Potentiometer Total Resistance 5000 ohms 10 Actuator Timing 90 Travel Standard 24 to 30 seconds Derated Cold Start Timing from 40 F to 20 F 40 C to 29 C 150 seconds maximum No...

Страница 3: ...amage actuator Do not locate actuator where ambient temperatures will exceed the limits listed in the Specifications section CAUTION Equipment Damage Hazard Excessive vibration will damage actuator Do not locate actuator where vibration will exceed the limits listed in the Specifications section Mounting ML7999C Actuator The actuator mounts on a 1 2 in round or square shaft For shafts smaller than...

Страница 4: ...in separate conduit to avoid signal interference Earth Ground Earth ground is required for proper operation of the ControLinks system Earth ground provides a connection between the subbase and the control panel of the equipment The earth ground must be capable of conducting enough current to blow the fuse or breaker in the event of an internal short 1 Use wide straps or brackets to provide minimum...

Страница 5: ... buttons are labeled CW and CCW To use them the only required wiring connections are L1 L2 and GND However after the device is installed and wired to the R7999 do not use these buttons for anything but troubleshooting Password Protection ID Signal Before using the actuator the ID signal must be set See the software interface instructions for details After this signal is set the R7999C sends the si...

Страница 6: ...ve actuator closed position five degrees off mechanical closed fixed stop 4 Verify that the gas fuel fgr linkage dampers are at their closed positions 5 Tighten the set screws on the actuator OPEN ACTUATORS 2 5 DEGREES LOCK ACTUATOR CLOSED POSITION ACTUATOR MECHANICAL CLOSED FIXED STOP Mechanical open closed fixed stops of actuator ML7999C Move actuator 5 degrees of mechanical closed fixed stop Ve...

Страница 7: ...10 Move actuator linkage damper 2 5 degrees off mechanical closed fixed stop 7 Auto seek open to actuator mechanical open fixed stop See Fig 11 Fig 11 Auto seek open to actuator mechanical open fixed stop 8 Move the actuator five 5 degrees off the mechanical open stop See Fig 12 Fig 12 Move actuator five degrees off the mechanical open stop 9 Lock actuator open position See Fig 13 Fig 13 Lock actu...

Страница 8: ...ld drive the device clockwise c Press the button labeled CCW The actuator should drive the device counterclockwise 4 If the actuator operates properly check the control ler for proper output signals 5 If the actuator does not drive remove power discon nect the actuator hub and try to turn the shaft clockwise and counterclockwise If the shaft turns freely throughout the 90 degree stroke and the act...

Страница 9: ...intégrée Compartiment de câblage séparé pour le câblage de la tension de secteur et pour le câblage de la commande à basse tension Montage de l axe à accouplement direct Se couple directement à un axe de 1 2 po 13 mm sans pièce supplémentaire Se couple directement à des axes de 5 16 po 8 mm et de 3 8 po 9 mm à l aide d accessoires de réduction d axe auto centreurs Ensembles coupleur d axe disponib...

Страница 10: ...se de l actionneur 95 nominal 3 limité mécaniquement Précision de la position du moyeu de sortie 0 1 Couples nominaux aux tensions nominales Couple de levage et de maintien minimal 11 3 N m 100 lb po Couple de manœuvre minimal 11 3 N m 100 lb po Couple de maintien minimal 11 3 N m 100 lb po Couple de maintien maximal 17 N m 150 lb po Durée de vie de l actionneur à 100 lb po Courses complètes 100 0...

Страница 11: ...ager les pièces métalliques de l actionneur Installez l actionneur à un endroit non exposé aux vapeurs d acides ou à d autres vapeurs destructrices MISE EN GARDE Risque d endommagement de l équipement Les températures extrêmes endommagent l actionneur Ne pas installer l actionneur à un endroit où les températures ambiantes dépassent les limites prescrites dans la section Spécifications MISE EN GAR...

Страница 12: ... support de montage à l aide des vis fournies 4 Câblez l actionneur ML7999C conformément aux instructions de la section Câblage 5 Rétablissez l alimentation du système Fig 3 Montage de l actionneur ML7999C Fig 4 Montage de l actionneur ML7999C avec le support de montage CÂBLAGE AVERTISSEMENT Danger de décharge électrique Peut causer des blessures graves ou le décès Débranchez l alimentation avant ...

Страница 13: ...vannes de modulation à l huile et de systèmes de recirculation des gaz de combustion qui nécessitent un couple maximum de 100 lb po Un contrôleur R7999C commande l actionneur ML7999C L actionneur est muni d un indicateur de position qui indique la position de l axe L indicateur se déplace avec l axe pour fournir une représentation angulaire de la position de ce dernier IMPORTANT Une fois que le co...

Страница 14: ...ille les signaux de commande ou de mise hors ligne Allumée fixe Non Non Panne de l actionneur Réinitialiser l actionneur aux valeurs d usine OUVREZ LES ACTIONNEURS DE 2 À 5 DEGRÉS VERROUILLEZ LA POSITION FERMÉE DE L ACTIONNEUR BUTÉE FIXE DE FERMETURE MÉCANIQUE DE L ACTIONNEUR Butées fixes d ouverture de fermeture mécanique de l actionneur ML7999C Déplacez l actionneur de 5 degrés par rapport à la ...

Страница 15: ...mbustion sont en position fermée 5 Serrez les vis de réglage sur l actionneur 6 Déplacez la tringlerie et le registre de l actionneur de 2 à 5 degrés par rapport à la butée de fermeture mécanique de la tringlerie et du registre Verrouillez la position fermée de l actionneur Voir la Fig 10 Fig 10 Déplacez la tringlerie et le registre de l actionneur de 2 à 5 degrés par rapport à la butée de fermetu...

Страница 16: ... correspond à la course du registre ou du régulateur a Retirez le couvercle b Appuyez sur le bouton étiqueté CW L actionneur devrait entraîner l appareil dans le sens horaire c Appuyez sur le bouton étiqueté CCW L actionneur devrait entraîner l appareil dans le sens antihoraire 4 Si l actionneur fonctionne correctement vérifiez que les signaux de sortie du contrôleur sont adéquats 5 Si l actionneu...

Отзывы: