ML7999A UNIVERSAL PARALLEL-POSITIONING ACTUATOR

65-0239—2

4

Mounting the ML7999 Actuator on V5197A 

Firing Rate Gas Valve. (Fig. 2)

WARNING

Explosion Hazard and Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

1. Turn off gas supply before starting installation.

2. Disconnect power supply for valve actuator before 

beginning installation and wiring. More than one 

disconnection can be involved.

1.

Attach the mounting bracket for the ML7999 Actuator 

(supplied with the V5197 Valve) in the position that best 

suits the valve location, access space and wiring 

requirements. 

2.

Place the short end of the V5197 valve drive stem in the 

top of the V5197 Valve drive so that the rectangular 

portion of the drive stem is inside the valve drive.

3.

Mount the ML7999 Actuator on the V5197 Valve and 

secure the actuator to the mounting bracket with the 

supplied screws.

4.

Wire the ML7999 Actuator per the instructions in the 

Wiring section.

5.

Restore power to the system.

Fig. 3.  Mounting ML7999.

Fig. 4. Mounting ML7999 with mounting 

bracket accessory.

WIRING

WARNING

Electrical Shock Hazard.

Can cause severe injury or death.

Disconnect power supply before installation.

All wiring must comply with local electrical codes, ordinances 

and regulations. The ML7999 is designed for used with a 

Class 2 power supply for low voltage. Voltage and frequency 

of the transformer must correspond with the characteristics of 

both the actuator and the power supply.

Earth Ground

Earth ground is required for proper operation of the 

ControLinks™ system. Earth ground provides a connection 

between the subbase and the control panel of the equipment. 

The earth ground must be capable of conducting enough 

current to blow the fuse or breaker in the event of an internal 

short. 

1.

Use wide straps or brackets to provide minimum length, 

maximum surface area ground conductors. If a leadwire 

must be used, use 14 AWG copper wire.

2.

Make sure that mechanically tightened joints along the 

ground path are free of nonconductive coatings and 

protected against corrosion on mating surfaces.

Shield Ground

Connect the shield ground of the ML7999 Actuator(s), 

Remote Reset, Manual Potentiometer, Controller 4-to-20 mA 

and Auxiliary 4-to-20 mA inputs to the earth ground strip 

provided in the Q7999 Universal Subbase. Connect the shield 

at the controller end only. See Fig. 6.

Preparation

Use OEM-supplied 1/2 in. conduit connectors in the low- and 

line- voltage base openings; the motor has separate line- and 

low-voltage wiring compartments.  Use Belden 9535, 

5-conductor, 100% shield coverage, 300V, 80°C (UL2464, 

CSA PCC FT4), or equivalent for low voltage wiring.

Wiring Procedures

IMPORTANT

Device must be hardwired.

1.

Remove the cover from the actuator.

2.

Pull back the snap-locks while opening the low-voltage 

compartment. See Fig. 5.

3.

Wire the low-voltage circuit to the R7999. See Fig. 6 for 

typical wiring connections.

4.

Close the low-voltage compartment.

5.

Wire the line-voltage circuit. See Fig. 6 for typical wiring 

connections.

6.

Replace the cover on the actuator.

M16467A

LOCK WASHER OR 
CAPTIVE NUT 
(NOT PROVIDED)

M16468A

LOCK WASHER OR 
CAPTIVE NUT 
(NOT PROVIDED)

Содержание ML7999A

Страница 1: ...FEATURES Universal power supply input Password protected with an eight digit hexadecimal identification signal 100 lb in 11 3 Nm torque Includes integral position feedback potentiometer Separate wiring compartment between line voltage power wiring and low voltage control Direct coupling shaft interface mounting Couples directly to a 1 2 in 13 mm shaft with no additional parts required Couples dire...

Страница 2: ...differential between DR1 DR2 Drive Counterclockwise Maximum 4 25 Vdc differential between DR1 DR2 NOTE Actuator does not respond until the 8 digit ID signal from the R7999 is passed via DR1 DR2 Actuator Stroke 95 nominal 3 mechanically limited Output Hub Position Accuracy 0 1 Torque Ratings at Rated Voltages Lift and Hold Minimum 100 lb in 11 3 Nm Breakaway Minimum 100 lb in 11 3 Nm Stall Minimum ...

Страница 3: ... and acid fumes can damage the actuator metal parts Install actuator in areas free of acid fumes and other deteriorating vapors Mounting ML7999 Actuator The actuator mounts on a 1 2 in round or square shaft For shafts smaller than 1 2 in self centering adapters are available for 5 16 in and 3 8 in shafts For shafts larger than 1 2 in adapters are available for 5 8 in 3 4 in and 9 16 in CAUTION Equ...

Страница 4: ... Ground Earth ground is required for proper operation of the ControLinks system Earth ground provides a connection between the subbase and the control panel of the equipment The earth ground must be capable of conducting enough current to blow the fuse or breaker in the event of an internal short 1 Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a le...

Страница 5: ...r is low check the power supply 3 Ensure actuator stroke matches stroke of damper or valve a Remove the cover b Press the button labeled CW The actuator should drive the device clockwise c Press the button labeled CCW The actuator should drive the device counterclockwise 4 If the actuator operates properly check the controller for proper output signals 5 If the actuator does not drive remove power...

Страница 6: ... does not drive replace the actuator 9 If the actuator and device shaft turn freely remount the actuator to the device according to instructions in the Installation section Make sure the actuator does not bind and that the actuator and device are both at the same clockwise or counterclockwise end stop when assembled Hook up the wires and repeat the Checkout procedures Troubleshoot if necessary ...

Страница 7: ...7 65 0239 2 ...

Страница 8: ...well Europe S A Honeywell Latin American Honeywell International Inc Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Отзывы: