Honeywell MiniZone EMM-3 Скачать руководство пользователя страница 1

PRODUCT DATA

68-3041-2

® U.S. Registered Trademark
Copyright © 2002 Honeywell •  All Rights Reserved 

EMM-3

Electronic MiniZone™ Panel

APPLICATION

The EMM-3 Electronic MiniZone™ Panel controls single-

stage heat/cool equipment and is used on two-and three-zone 

applications.

FEATURES

• Uses any Honeywell four-wire thermostat.
• Optional C7735 Discharge Air Temperature Sensor 

Sensor for capacity control.

• SYSTEM and ZONE damper status LEDs indicate 

system status.

• Automatic zone changeover with 20-minute 

changeover timer.

• Individual zone fan control.
• Thermal circuit breaker protects panel and transformer 

from damage if miswired.

• Purge timer protects equipment between calls for 

heating and cooling.

• Uses spring-open/power-closed, spring-closed/power-

open, and power-open/power-closed dampers.

• Interfaces with single or dual transformer equipment.

For Internet access:

www.honeywell.com/yourhome/zoning/zoning_home.htm

For technical support:

 

call 1-800-828-8367.

To download Zoning literature:

http://hbctechlit.honeywell.com

Contents

Application.........................................................................1

Features ............................................................................1

Specifications ....................................................................2

Ordering Information .........................................................2

Installation .........................................................................4

Startup and Checkout........................................................7

Service ..............................................................................9

Troubleshooting.................................................................9

Содержание MiniZone EMM-3

Страница 1: ...over with 20 minute changeover timer Individual zone fan control Thermal circuit breaker protects panel and transformer from damage if miswired Purge timer protects equipment between calls for heating and cooling Uses spring open power closed spring closed power open and power open power closed dampers Interfaces with single or dual transformer equipment For Internet access www honeywell com yourh...

Страница 2: ... 24000 to 1600 ohms Output Ratings Equipment Relays and Zone Relays 1 5A run 3 5A inrush 200 000 cycles 30 Vac 1 5A run 7 5A inrush 100 000 cycles 30 Vac Humidity Ratings 5 to 90 RH non condensing Temperature Ratings Shipping 20 to 120 F Operating 40 to 150 F LED SYSTEM LED Used to communicate equipment status Red Heat mode Green Cool mode Orange Purge mode Flashing Red System exceeds high DATS in...

Страница 3: ...A1007 and W8900A1004 Trol A Temp T8601D2027 Table 2 Recommended Dampers Honeywell Damper Type Round Rectangular Power open power closed MARD D643 using ML6161 Motor Actuator Spring open power closed ARD ZD Table 3 Required Accessories Accessory Description 40 VA transformer AT140D1046 Capacity protector DATS C7735A1000 Round static pressure regulator damper 7 SPRD 8 SPRD 9 SPRD 10 SPRD 12 SPRD 14 ...

Страница 4: ...to call for heat 1 Zone 1 damper is open Zone 1 LED on EMM 3 is green 2 Zones 2 and 3 dampers are closed Zones 2 and 3 LED on EMM 3 are off 3 Heating equipment is activated SYSTEM LED is red 4 Continue wiring the system CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before continuing installation 7 Connect Zone 2 thermostat to EMM 3 8 Reconnect power to EMM ...

Страница 5: ...re continuing installation 15 Reconnect power to EMM 3 16 Check out fan operation a Set Zone 1 thermostat fan switch to On and Zones 2 and 3 thermostats to Auto b Zone 1 damper is open Zone 1 LED on EMM 3 is green c Zones 2 and 3 dampers are closed Zones 2 and 3 LED on EMM 3 are off d Fan equipment is activated SYSTEM LED is off e Repeat procedure for zones 2 and 3 Continue wir ing the system CAUT...

Страница 6: ...wered power stealing or some electromechanical thermostats EQUIPMENT Discharge Air Temperature Sensor See C7735 Installation Instructions for further information ZONEMAX R C ZMS ZMS Heating Transformer Cooling Transformer Cool Relay Heat Relay Fan Relay This diagram shows the typical single stage equipment thermostat and damper motor connections For specific wiring for other thermostats damper mot...

Страница 7: ...pers close Panel calls for heat Heat is delivered only in zone 1 When another zone calls for heat while zone 1 is calling that zone damper opens For electric heat applications use thermostat that calls for fan with all calls for heat Damper Zone1 M4 Zones 2 and 3 M6 Panel W heat ZONE 1 ENDS CALL FOR HEAT SYSTEM orange Thermostat None System enters Purge mode Damper s from zone 1 remains open all o...

Страница 8: ...1 2 minutes and more than 10 F 12 C temperature rise the panel returns to Cool mode if call still exists delivering cooling to zone 1 and any other zone calling for cool Damper Zone 1 M4 Zones 2 and 3 M6 Panel G fan AFTER BOOT BUTTON IS PRESSED SYSTEM orange Panel G fan System enters Purge mode for 2 1 2 minutes Dampers to all zones open See Purge mode Dampers M4 PURGE OVERRIDE BUTTON IS PRESSED N...

Страница 9: ...THE THERMOSTAT CALLING FOR COOL IS THERE CONTINUITY AT RC Y ON THE EQUIPMENT CONTACTS OF THE EMM PANEL NO NO NO THE THERMAL FUSE HAS TRIPPED REMOVE THE R OR C TRANSFORMER POWER WIRE FROM THE PANEL FOR 15 SECONDS AND ALLOW THE FUSE TO RESET TAKE THE THERMOSTAT AND DAMPER WIRES OFF FROM EACH ZONE BEFORE YOU RE ATTACH THE R OR C WIRE IS THERE VOLTAGE AT R M1 OR R C ON ALL OF THE ZONES IS THERE 24 VAC...

Страница 10: ...AND ALLOW THE FUSE TO RESET TAKE THE THERMOSTAT AND DAMPER WIRES OFF FROM EACH ZONE BEFORE YOU RE ATTACH THE R OR C WIRE IS THERE VOLTAGE AT R M1 OR R CON ALL OF THE ZONES IS THERE 24 VAC AT W C ON THE THERMOSTAT DO YOU HAVE A DATS HOOKED TO THE PANEL NO YES YES YES YES JUMPER THE R WIRE TO THE W WIRE ON THE THERMOSTAT IF THE HEAT LIGHT COMES ON YOU HAVE A BAD THERMOSTAT REPLACE THERMOSTAT IF YOU ...

Страница 11: ...EMM 3 ELECTRONIC MINIZONE PANEL 11 68 3041 2 ...

Страница 12: ...w honeywell com yourhome Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 EMM 3 ELECTRONIC MINIZONE PANEL ...

Отзывы: