background image

R7426D UNIVERSAL INPUT CONTROLLER

EN1B-0204GE51 R0403

6

Off Delay for On/Off Output (C.26)

The On/Off output is controlled by the Plant / System On/Off

input and provides an Off switching output with adjustable

delay time e.g. to operate the fan still for a certain time after

humidification.

On/Off

Input

Controller Function

On/Off Output: Delay

On

Normal control

Off 

 On: 0 min

Off

Output Y1 = 0%

On 

 Off: 0...60 min

The off time delay can be adjusted by the parameter

OffDelay

.

PARAMETER SETTINGS AND

ADJUSTMENT

Main Setpoint W1 (P.01)

The main setpoint is either set by the parameter 

W1

(

CPATYP

 = 0 or 1) or by the external setpoint potentiometer

(

CPATYP

 = 2).

High/Low Limit Setpoint W

lim

 (P.02)

For high or low limit control, the control parameter 

W

lim

 is

used as setpoint.

During limit control, the throttling range 

Xp2

 and reset time

tr2

 are active.

Limit control will be active only, if the X2 signal (

X2ext

 = 0) is

available or alternatively the sensor X1 (

X2ext

 = 1) is used

also for limit control.

For cascade control the limit setpoint 

W

lim

 

determines the

control point at which the submaster setpoint

 

(

W

cas

)

maintains the limit value and is not shifted anymore by the

master control loop.

High or low limit control is in accordance with the parameter

LimTyp

 (C.13).

Submaster Setpoint W

cas

 

(P.06)

The R7426D controller provides cascade control which uses

two control loops, master and submaster to maintain the

master setpoint CTRP1. Cascade control will be active, if

sensor X2 is connected and the control parameter 

W

cas

 is set

to any value other than Off.

This adjustment sets the control point of the submaster

control loop, cascade input (X2), at zero deviation of the

master control loop. If the controlled input X1 deviates from

the master setpoint CTRP1, the submaster setpoint 

W

cas

 is

automatically altered (CTRP2

)

.

Cascade control is disabled, if the submaster setpoint 

W

cas

 is

set to Off.

Low limit of CTRP2 is performed if control parameter

LimTyp

 = 0 and high limit of CTRP2 is performed if control

parameter 

LimTyp

 = 1.

Reset Span Adjustment R

cas

 

(P.07)

The reset span adjustment 

R

cas

 determines the reset effect in

%, the submaster setpoint 

W

cas

 is altered, if the main input

(X1) deviates by 50% of the throttling range 

Xp1

.

Throttling Range Xp1 / Xp2 (P.08 / P09)

Throttling range X

p

 adjustment determines the controller

variable change, required at the main sensor (X1) and limit or

cascade sensor (X2) to operate the output device from full

open (100%) to full closed (0%) or vice versa.

Xp1

 is the throttling range for the main control loop, 

Xp2

 is

the throttling range for limitation or cascade control

(submaster control loop).

Application

Sens. Xp1 Xp2 tr1 tr2 vd/td

R7426D Controller

Main Control

X1

x

x

x

High or Low Limit Control

X2

x

x

x

Cascade Control

Master

X1

x

x

Submaster

X2

x

x

x

Table 6. Throttling Range, Reset and Derivative

Time Reference

 

Setting Guidelines for Proportional Band of
P, P+I and P+I+D Control

 

To estimate the proportional band (throttling range X

p

) for

stable control under all different load conditions the control or

correcting range X

h

 of the controlled variable by the final

controlling element has to be known. This is the maximum

difference in the controlled variable between the fully closed

and fully open position of the final controlling element (e.g.

valve).

 

The proportional band X

p

 for discharge air control can be

calculated by using the following rule-of thumb formula:

 

X

p

=

X

h

5

 

For room control the following rule-of-thumb formula can be

used:

 

X

p

=

X

h

10

 

In P+I or P+I+D control the same proportional band can be

used as for P control.

 

The following rule-of-thumb formula are used for P+I control:

  Discharge air control

X

p

=

X

h

4 5

...

 Room 

control

X

p

=

X

h

8 10

...

Содержание MicroniK 200 R7426D

Страница 1: ...y separated from the main power supply relays or other equipment which can possibly generate electromagnetic inter ference Verify that the ambient temperature and the humidity at the controller will be within the limits of 0 50 C 32 122 F and 5 to 95 rh Use shielded wiring in areas with high EMI All wiring should be separated from power lines by at least 150mm 6 Do not install controllers near fre...

Страница 2: ...ac and controller 24Vac 2 Connect line power conductors to transformer primary Line power must be supplied from a breaker panel with dedicated controller circuit Do not turn the line power on until all wiring has been checked against job drawings 3 Connect transformers 24Vac secondary to the controller terminals 18 and 19 Connect one conductor to terminal marked 24V and the other to terminal marke...

Страница 3: ...n type determines whether the limit function is low or high 1 0 1 Low limit High limit C 14 Senstyp Sensor type determines automatic detection or manual selection of NTC sensor type 0 0 1 Auto detection T3 NTC sensor type T3 C 15 Y1CTRF Control function 1 0 1 Direct control behaviour Reverse control behaviour C 22 Adr 1 Sets the serial communication address used for service or maintenance 254 0 25...

Страница 4: ...2 Throttling range cascade or limit control loop for X2 1 50 10 0 5 P 12 tr1 1 Reset time main control loop Off 20sec 20min Off 10 0 5 sec min P 13 tr2 1 Reset time cascade control loop Off 20sec 20min Off 10 0 5 sec min P 15 Ystart Start point for mid range shift of output Y1 50 50 0 0 5 P 17 X1Cal Calibration of input X1 20 20 0 0 1 P 18 X2Cal Calibration of input X2 20 20 0 0 1 P 19 T3Cal Calib...

Страница 5: ...utomatic identification of sensor type Temperature range Characteristics Pt 1000 30 130 C 1000Ω at 0 C BALCO 500 30 130 C 500Ω at 23 3 C NTC 20kΩ 30 85 C 30 130 C 1 20kΩ at 25 C 1 NTC sensor is detected automatically if during power up the sensor temperature is within 30 85 C and Senstyp 0 NTC sensor is selected manually if Senstyp is set to 1 Table 5 Sensor Types Automatic identification of senso...

Страница 6: ...nt CTRP1 the submaster setpoint Wcas is automatically altered CTRP2 Cascade control is disabled if the submaster setpoint Wcas is set to Off Low limit of CTRP2 is performed if control parameter LimTyp 0 and high limit of CTRP2 is performed if control parameter LimTyp 1 Reset Span Adjustment Rcas P 07 The reset span adjustment Rcas determines the reset effect in the submaster setpoint Wcas is alter...

Страница 7: ...ime Tu in discharge air control is normally in the range of 0 1 to 0 6min which allows adjustments of the reset time tr in a range of 0 2 to 2min In room control the response time Tu is in the range of 0 5 to 5min which results in a setting of 1 to 15min Derivative Decay Time td and Amplification vd P 27 P 28 The Proportional Integral Derivative P I D control adds the derivative function to P I co...

Страница 8: ...defines the start point of summer or winter compensation Above the compensation changeover point Wcomp summer compensation and below Wcomp winter compensation is performed Summer Winter Compensation Authority Su Wi P 04 P 05 These authority settings determine the reset effect TComp of the compensation sensor T3 on the main setpoint W1 in percentages To calculate winter and summer authority for e g...

Страница 9: ...e selected parameter or configuration no and enters the adjustment mode Fig 8 which is used to adjust configuration parameter values After adjustment the controller returns to selection mode by pushing the SET or SEL button Pushing the SEL button leads back to standard display mode Pushing the SET and SEL button simultaneously for approximately 1 sec the controller leaves the standard display mode...

Страница 10: ...six actual values can be selected and displayed Fig 6 by pushing the SEL button The icons of the permanently displayed controller mode are described in the following table Controller Mode Status Display Off Off icon On Sun icon A A Main Input X1 Main Setpoint CTRP1 Limitation Cascade Input X2 Submaster Limit Setpoint CTRP2 Compensation Temperature T3 Output Y1 SEL SEL SEL SEL SEL SEL Fig 6 Standar...

Страница 11: ...r decrements the value of the selected parameter Parameter ranges are shown in Table 3 and Table 4 An adjustment example is shown in Fig 12 Pushing the SEL button retains the old parameter value Pushing the SET button accepts the parameter value and returns to parameter configuration selection mode Resetting Parameter Values to Default Values Pushing simultaneously the or button during the power u...

Страница 12: ...he nominal control range as shown in Fig 6 To return to output selection mode three options are available Pushing the SET button after adjustment activates the manual override fixing of output value Pushing the SEL button causes that the output value is still determined by the control loop no fixing To release the manual override fixed of the output enter output adjustment mode and push the and bu...

Страница 13: ... or 1 CPA value 0 for CPATYP 2 SPA value control parameter W1 Standard Display and and and Main Sensor X1 is defective Limitation or Cascade Sensor X2 is defective Compensation Temperature Sensor T3 is defective T3 is displayed in X1 and X2 is displayed in Display if during power up no sensor is connected Display after error identification during operation Standard Display SEL SEL SEL SEL Fig 11 E...

Страница 14: ...ntrol Solutions Honeywell AG Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to 7157 585 EN1B 0204GE51 R0403 ...

Отзывы: