MI-DCZME

M200E-SMB

Honeywell Morley-IAS

Pittway Tecnologica S.r.l

Via Caboto 19/3 

34147 Trieste, Italy

Lift

Sollevare

Levantar

Anheben

Push down

Premere

Precionar 

hacia abajo

Runterdrücken

Rotate  /  Ruotare

Girar  /

  

Drehen

Rotate

Ruotare

Girar

Drehen

Clip / Agganciare

Acoplar /

 

Einrasten

Plug

Inserire

Conectar

Einhaken

2

3

1

1

3

2

1:2 DIN

1:1 M200E-SMB

Fig./Abb.  1

DOP-IOD102

EN 54-17: 2005, EN 54-18: 2005 

0905  22

0905  22

This manual is intended as a quick reference installation guide.  Please refer to the 

control panel manufacturers installation manual for detailed system information.
The Morley series of modules are a family of microprocessor controlled interface 

devices permitting the monitoring and/or control of auxiliary devices.The MI-DCZME 

provides an interface between a zone of System Sensor manufactured conventional 

type fire detection devices and an intelligent signalling loop.

A single tri-colour LED indicates the status of the module. In normal conditions, the 

LED can be set by command from the control panel to blink green when the module 

is polled. In the case of a fire alarm on the conventional zone, the LED is switched 

on constant red by panel command. If a fault is detected on the conventional zone or 

the zone supply voltage drops below 18V, or a fault with the external power supply is 

signalled, the LED will blink yellow if enabled on the control panel. When a short circuit 

is detected on the loop to either side of the module, the LED is switched to show a 

constant yellow light.
This module does not require maintenance. 

SPECIFICATIONS

Intelligent Loop

 

Operating Voltage Range: see S00-7100

LED Cutoff Voltage: 16.5VDC

Max. Standby Current (µA @24 V and 25

o

C) External Supply Conventional Zone:  

No Communication: 

120

Max. Standby Current (mA @24 V and 25

o

C) Conventional Zone connected to 

Capacitive EOL only, Loop Powered Conventional Zone: 

 

No Communication: 

1.3

LED Current (Red): 

1.3mA

LED Current (Yellow): 

4.5mA

Isolator Features:  see S00-7100

Conventional Zone

Supply Voltage:  

18 to 32 VDC (either from loop or external supply)

Maximum Standby Load Current:   3mA for detectors

Maximum Zone Load:  

17.5mA (Limited internally)

Maximum Conventional Line Resistance: 50 Ohm (both legs)

End of Line Capacitor:  

47μF non-polarised. M200E-EOL-C supplied

General

Humidity: 

5% to 95% relative humidity (non-condensing)

Ingress protection: 

IP44 (Mounted in M200E-SMB)

Maximum Wire Gauge: 

2.5mm²

INSTALLATION

Note:

 These modules must only be connected to control panels using compatible 

proprietary analogue addressable communication protocols for monitoring and control.
Morley series modules can be mounted in several ways (See 

Figure 1

):

1:1

  An  M200E-SMB  custom  low  profile  surface-mounting  box. The  SMB  Base  is 

affixed to mounting surface, and then the module and cover are screwed onto 

the base using the two screws supplied. Box dimensions: 132mm(H) x 137mm(W) 

x 40mm(D)

1:2

  The DIN bracket on top allows mounting onto standard 35mm x 7.5mm "Top Hat" 

DIN rail inside a control panel or other suitable enclosure. Install and remove as 

shown in Figure 1:2

Wiring to all series Morley modules is via plug in type terminals capable of supporting 

conductors up to 2.5mm²

CAUTION

Disconnect loop power before installing modules or sensors. 

The module address is selected by means of rotary decade address switches (see 

Figure 3

).  A screwdriver should be used to rotate the wheels to select the desired 

address, either from the front or the top of the module. 

Note:

 The number of addresses available will be dependent on panel capability, 

check the panel documentation for information on this.  

Short Circuit Isolators 

All Morley series modules are provided with short circuit monitoring and isolators on 

the intelligent loop.  If required the isolators may be wired out of the loop to facilitate 

the use of the modules on high current loaded loops, for example if sounders are 

used.  To achieve this, the loop out positive should be wired to terminal 5 rather than 

terminal 2. See 

Figure 2

 for details.

CAUTION

Electrostatic Sensitive Device

Observe precautions when handling and making connections

MI-DCZME

INSTALLATION INSTRUCTIONS - MI-DCZME 

CONVENTIONAL ZONE INTERFACE MODULE

EN

MI-DCZME

Fig./Abb. 3

Содержание MI-DCZME

Страница 1: ... Current Yellow 4 5mA Isolator Features see S00 7100 Conventional Zone Supply Voltage 18 to 32 VDC either from loop or external supply Maximum Standby Load Current 3mA for detectors Maximum Zone Load 17 5mA Limited internally Maximum Conventional Line Resistance 50 Ohm both legs End of Line Capacitor 47μF non polarised M200E EOL C supplied General Humidity 5 to 95 relative humidity non condensing ...

Страница 2: ...nea 47 μF non polarizzato Alimentato tramite M200E EOL C General Umidità Umidità relativa compresa tra il 5 e il 95 in assenza di condensa Protezione ingressi IP44 montato su M200E SMB Massimo calibro del filo 2 5mm INSTALLAZIONE Nota Questi moduli possono essere collegati esclusivamente a pannelli di controllo dotati di opportuno protocollo di comunicazione proprietario indirizzabile ed analogico...

Страница 3: ... mediante terminales extraíbles con capacidad para cables con sección de hasta 2 5 mm PRECAUCIÓN Desconecte la alimentación del lazo antes de instalar módulos o sensores La dirección de ambos módulos se selecciona por medio de selectores de dirección giratorios y decádicos Figura 3 a los que se accede desde la parte delantera o superior del módulo Hay que utilizar un destornillador para girar llos...

Страница 4: ...nitt von max 2 5mm ACHTUNG Vor der Installation von Meldern oder Modulen ist die Ringleitung spannungsfrei zu schalten Die Moduladresse wird mit einem geeigneten Schraubendreher an dem Drehschalter eingestellt siehe Abbildung 3 Dieser kann von der vorne oder der rechten Seite des Moduls erreicht werden Anmerkung Einige Brandmelderzentralen können nur 99 Adressen benutzten Isolator Alle Module der ...

Отзывы: