Installation:
The product contains bracket for wall mounting and spacers for ceiling mounting.
Step 1:
Fasten the mounting part (with screws from within) to either wall bracket (supplied), ceiling (with or without supplied
spacers), pendulum, wire or flag bracket. If mounted close to a wall, make sure that the unlock button is facing
outwards.
Pass the mains cables through the cable gland. Connect
the mains cables to terminal blocks:
L
for live
wire,
N
for neutral and
PE
for
ground. Tighten the cable tie around the cables
.
Step 2:
To insert the pictograms, first unscrew the two screws holding the side profile (see picture). Remove the profile,
insert the pictograms and refit the side profile.
Step 3:
Slide the luminaire into the socket.
The lock/unlock button appears indicating that the luminaire is securely
installed. To dismantle the luminaire, push the lock/unlock button, slide the luminaire to the left and pull it down.
NOTE! The light source is non-replaceable.
1
2
Dimensional drawings:
MaxLED 26 MaxLED 47 MaxLED 65
Centralized
At the end of their useful life the
packaging and product should be
disposed of via a suitable
recycling centre. Do not dispose
of with your normal household
waste. Do not burn.
MaxLED26
MaxLED47
MaxLED65
Part no.:
290267
290266
290268
Lumen output:
280 lm
500 lm
850lm
Weight:
970g
1450g
2200g
Maximum power consumption:
2.6W/2.9VA
5.1W/5.4VA 8.2W/8.6VA
Operation voltage:
140-250V DC/AC 50-60Hz
Ambient temperature range:
-30 to +50°C
Relative humidity:
Up to 95%
Classification:
EN 60598-2-22
IP40