INSTALLATION INSTRUCTIONS

M896

Damper Actuator

APPLICATION

The

 M896 Damper Actuator is a 24 Vac motor with an

external shaft for coupling. Powered rotation is counter-
clockwise (ccw), with a maximum rotation of 110

°

. The

actuator is designed as a replacement actuator for the
D892 and D896 Automatic Vent Dampers or as the
original actuator on similar OEM dampers. Maximum OEM
damper operating torque cannot exceed ten in.-oz.

OPERATION

On a call for heat, the actuator automatically opens the
damper and the furnace or boiler begins its ignition cycle.
When the heating cycle ends, the burner turns off and the
actuator automatically closes the damper. Heating system
efficiency is increased because the closed damper
reduces the loss of residual appliance heat and heated
room air through the draft diverter.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could cause a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained experienced service

technician.

4. Install the M896 Damper Actuator as a replacement

only on AGA/CGA-approved damper systems.

5. After installation is complete, check out actuator

operation as provided in the Checkout section.

WARNING

Severe illness or death possible.
Prevent dangerous buildup of
carbon monoxide.
Be sure damper used with M896 has a return
spring that opens the damper if the coupler fails.

CAUTION

Electrical shock or equipment
damage possible.
1.

Disconnect power supply.

2.

Do not negate the action of any existing safety
or operational control.

3.

Make sure that the damper return spring is
operational prior to installing the actuator.

4.

Label all wires prior to disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.

To Install the M896 Damper Actuator:

1. Remove the existing actuator.
2. Make sure the damper return spring is operational.

(The damper return spring must open the damper
when the actuator coupling is removed to prevent a
dangerous buildup of carbon monoxide.)

3. Locate the arrow coupler and keeper clip

 (see Fig. 1).

M3949

A

B

KEEPER 
CLIP

ARROW
COUPLER

DAMPER
SHAFT

Fig. 1. Installing arrow coupler on damper

shaft using keeper clip.

4. Slip keeper clip over arrow coupler as shown in Fig.

1. This compresses the arrow coupler.

5. Install the arrow coupler in the slot on the damper

shaft with the arrow pointing up.

6. Align the slot on the actuator shaft with the arrow

coupler and attach the actuator to the damper.
See Fig. 2. (If the actuator output shaft is not
properly aligned with the arrow coupler, manually
turn the motor knob with a screwdriver to align the
actuator shaft.)

7. Attach the actuator to the damper bracket using the

screws removed in step 1.

8. Remove the keeper clip from the arrow coupler.
9. Connect the Molex plug to the M896 Harness Cable

Connector.

69-1089B-1

Содержание M896

Страница 1: ...ess or death possible Prevent dangerous buildup of carbon monoxide Be sure damper used with M896 has a return spring that opens the damper if the coupler fails CAUTION Electrical shock or equipment damage possible 1 Disconnect power supply 2 Do not negate the action of any existing safety or operational control 3 Make sure that the damper return spring is operational prior to installing the actuat...

Страница 2: ...CREWDRIVER TO MANUALLY OPEN AND CLOSE VENT DAMPER PLACE SCREWDRIVER IN SLOTTED KNOB AND ROTATE COUNTERCLOCKWISE UNTIL BOTH LEDS TURN ON 1 1 M896 M11367 Fig 4 Wiring diagram for M896 D896 connection to L8148E1166 using wiring harness with two Molex plugs MV MV PV PV GND BURNER 24V GND 24V SPARK S8600F H M S8610F H POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE PLUG...

Страница 3: ...2 B1 L2 5 4 5 5 3 4 S4 LED 2 LED 1 Fig 5 Wiring diagram for M896 D896 connection to S8600 S8610 using wiring harness with two Molex plugs SETTINGS The service switch has both a normal NORM and a service SERV mode NORM M896 opens on a call for heat and closes at the end of the heating cycle SERV M896 electrically opens after the thermostat has a call for heat and remains open CHECKOUT Heating 1 Tur...

Страница 4: ...hnician calls TROUBLESHOOTING WARNING Fire or explosion hazard Can cause property damage severe injury or death Explosion or carbon monoxide poisoning possible Never apply a jumper across or short gas control terminals or wires This can force the damper to remain closed and cause an explosion NOTE If there is a power failure the damper remains exactly where it is at the moment of failure open clos...

Страница 5: ...pertinente 4 Installer l actionneur de registre M896 comme pièce de rechange uniquement dans les systèmes à registre approuvés par l AGA CGA 5 Une fois l installation terminée vérifier le fonctionnement du produit comme l indique la section Vérification AVERTISSEMENT Peut causer des maladies graves et entraîner la mort Empêcher l accumulation dangereuse au monoxyde de carbone S assurer que le regi...

Страница 6: ...E LE MODULE NE FONCTIONNERA QUE SI LE REGISTRE D AÉRATION EST BRANCHÉ 1 1 MF11369 SENSE TH W VENT DAMPER PLUG FAISCEAU DE FILS REGISTRE D AÉRATION M896 D896 2 2 4 Faire glisser la goupille par dessus l accouplement en flèche comme l illustre la Fig 1 Cela a pour effet de comprimer l accouplement en flèche 5 Installer l accouplement en flèche dans la fente de l arbre du registre en faisant pointer ...

Страница 7: ...50 OHMS N F N O N F N O C C S1 S2 K1 N F N O C S3 T W TV Z C1 C2 L1 B2 B1 L2 5 4 5 5 3 4 S4 VOYANT 2 VOYANT 1 RÉGLAGES L interrupteur d entretien comporte la position normale NORM et la position service SERV NORM Le M896 s ouvre lors d une demande de chaleur et se referme à la fin du cycle de chauffage SERV Le M896 s ouvre électriquement après un appel de chaleur du thermostat et reste ouvert VÉRI...

Страница 8: ...é et provoquer des blessures ou même entraîner la mort Risque d explosion ou d empoisonnement au monoxyde de carbone Ne jamais placer de cavalier entre les bornes ou les fils du régulateur à gaz et ne jamais court circuiter le régulateur à gaz Cela pourrait forcer le registre à rester en position de fermeture et provoquer une explosion REMARQUE En cas de panne de courant le registre restera exacte...

Отзывы: