MOUNTING IN A DAMPER APPLICATION

Remove the Ranco Actuator and mount the M7164 re-

placement as shown in Fig. 10.

MOUNTING IN A VALVE APPLICATION

Remove the Ranco Actuator and linkage and install the

appropriate linkage and Modutrol IV motor according to
the instructions in the Installation section supplied with
the linkage.

WIRING CONVERSION

Disconnect power supply before beginning installation

to prevent electrical shock or equipment damage. All wiring
must comply with local electrical codes, ordinances, and
regulations.

To wire the M7161, M7164, proceed as follows. See

Table 2. Disconnect power, then remove wiring from Ranco
Actuator and connect to the motor according to Table 2
and Fig. 11.

M7161, M7164, M7184
OPERATION AND REPLACEMENT

Fig. 10—Replacing Ranco Linear Actuator with
M7164 in a damper application. Use linkage
(Q605 recommended) and pushrod to change
from a linear to a circular force.

CRANK ARM

(221455A)

PUSH ROD NO. 27520

C THRU L

90 DEGREE MOTOR

BALL JOINT

NO. 27518

M 493A

HONEYWELL

RANCO

TABLE 2—LA2-1000/2000 TO M7164 TERMINAL INTERCHANGES.

From Ranco LA2-1000/2000

To Honeywell M7161G, M7164A,G

Terminal

Function

Terminal

       Function

  1—COMD (+)

+ command signal

C

+ signal

  6—REF (—)

signal common

R

- common

  9—24 Vac

power supply

L1

a

 or T1

power supply

10 —24 Vac

power supply

L2

a

 or T2

F

b

a

Terminals L1 and L2 are used for 120 Vac motors. New power supply wiring must be run for 120 Vac motors.

b

This terminal is not used when replacing Ranco Actuators.

10

Содержание M7161

Страница 1: ...lectrically normally open all other motors are electrically normally closed Oil immersed motor and gear train for reliable performance and long life Wiring box provides NEMA 3 weather protection Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter a...

Страница 2: ...SASSOCIATIONCERTIFIED General Listing File No LR1620 Guide 400 E ELECTRICAL RATINGS Voltage Vac Current Power Con 50 60 Hz Draw A sumption W M7161 24 0 62 14 M7164 120 0 20 19 M7184 24 0 80 18 AUXILIARY SWITCH RATINGS Amperes One Contact Ratinga 120V 240V Full Load 7 2 3 6 Locked Rotor 43 2 21 6 a 40 VA pilot duty 120 240 Vac on opposite contact ACCESSORIES ES650117 Explosion proof Housing Enclose...

Страница 3: ...d Linkage Assembly Connects Modutrol Motor to water or steam valve Q5001 Valve Linkage Connects Modutrol Motor to water or steam valve Q100 Linkage Connects Modutrol Motor to butterfly valve 221455A Motor Crank Arm Infinitely adjustable crank arm Approximately 0 75 inch shorter than the 4074ELY Crank Arm can rotate through downward position and clear base of motor without requiring use of adapter ...

Страница 4: ...4A B and M7184A Motors are ship ped from the factory in the closed position at the limit of counterclockwise rotation as viewed from the power end of the motor M7161G and M7164G are shipped in the open position atthelimitofclockwiserotationasviewedfromthe power end of the motor See Fig 2 ADAPTER BRACKET The 220738A Adapter Bracket positioned between the motor and the equipment raises the shaft hei...

Страница 5: ...red distance while the motor moves through its full stroke 2 With modulating control maximum damper opening should be no more than 60 Little additional airflow is provided beyond this point 3 The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve The motor will be damaged if it is not permitted to complete its full stroke 4 Do not exce...

Страница 6: ... the motor correspond to the characteristics of the power supply See Figs 6 7 for typical system wiring Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply The motor terminals are quick connects located on top of theprintedcircuitboardshowninFig 5 Accesstothewiring compartment is gained by removing the four screws on the top ...

Страница 7: ...ig 9 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off power before adjusting switch cams 2 Do not turn motor shaft by hand or with wrench as damage to the motor can result NOTE The following instructions are for normally closed motors motor shaft rotates clockwise as viewed from the power end of the motor on an increase in signal 1 Remove cover o...

Страница 8: ...PROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM BLUE SWITCH FOLLOWER C F R MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM 1 8 IN STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED SWITCH FOLLOWER FAST RISE PORTION APPROX 1 DIFF L2 L1 HOT 1 2 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANS...

Страница 9: ... in 4 0 N m pushrod M7164G1030a e electrically normally openc M7164A1017a 90 deg 30 sec 24 Vac Q605 14W 35 lb in 4 0 N m pushrod electrically normally closedc 4 0 to 7 0 M7161G1017b e 90 deg 30 sec 120 Vac Q100 M7164G1014b e 19W 35 lb in 4 0 N m electrically normally openc M7161G1025d e 160 deg 60 sec 24 Vac Q601 Q618 M7164G1022d e 14W 35 lb in 4 0 N m or Q5001 electrically normally openc M7164A10...

Страница 10: ...uator and connect to the motor according to Table 2 and Fig 11 M7161 M7164 M7184 OPERATION AND REPLACEMENT Fig 10 Replacing Ranco Linear Actuator with M7164 in a damper application Use linkage Q605 recommended and pushrod to change from a linear to a circular force CRANK ARM 221455A PUSH ROD NO 27520 C THRU L 90 DEGREE MOTOR BALL JOINT NO 27518 M 493A HONEYWELL RANCO TABLE 2 LA2 1000 2000 TO M7164...

Страница 11: ... JumperterminalsCandF motorshoulddrivetothefully open clockwise positionasviewedfromthepower end Remove jumper Remove the lead from terminal C or R motor should drive to the closed fully counterclock wise position M7161G and M7164G JumperterminalsCandF motorshoulddrivefullclosed fullycounterclockwise positionasviewedfromthe power end Remove jumper Remove the lead from termi nal C or R motor should...

Страница 12: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: