L482A

 Low Limit Controller 

INSTALLATION INSTRUCTIONS 

BEFORE INSTALLATION 

No special tools are required to install the L482A Low Limit 

Controller. Refer to the job drawings for specific wiring and 

installation information. 

INSTALLATION 

When Installing this Product... 

1.

  

Read these instructions carefully. Failure to follow them

 

could damage the product or cause a hazardous 

condition.

 

2.

  

Check ratings given in instructions and on the product to 

ensure the product is suitable for your application.

 

3.

  

Installer must be a trained, experienced service 

technician.

 

4.

  

After installation is complete, check out product 

operation as provided in these instructions.

 

Mounting 

IMPORTANT

 

1.

  

The controller operates from the lowest temperature 

along the entire 20 feet of the sensing element.

 

2.

  

Locate controller case and bellows where ambient 

temperature is always warmer than the set point.

 

3.

  

For settings above the scale range midpoint it can be 

necessary to locate the controller case close to a 

steam pipe or other warm surface and make sure the

 

element does not extend across a cold surface.

 

Controller 

Surface mount the controller (Fig. 1) vertically on any 

Fig. 1. L482A Low Limit Controller dimensions in in. (mm). 

convenient location (including the duct itself). Orient the case 

with the bellows positioned on the bottom. 

SETPOINT 
ADJUSTMENT 
SCREW 

4 (101) 

2-3/32 

(53) 

7/8 (22) HOLE 
FOR 1/2 CONDUIT 
WITH 1-3/32  (28) 
KNOCKOUT  RING 
FOR  3/4 CONDUIT 

1-7/8 

(48) 

5/16 

(8) 

3/16 (5) 
DIAMETER 
MOUNTING 
HOLE 

3-1/4 (83)

5/16 (8) 

1 (25) 

1-1/8 (29) 

3/8 X 3/16 
(10 X 5) 
DIAMETER 
ELONGATED 
MOUNTING 
HOLE 

C606A 

SETPOINT 
SCALE 

4-11/16 

(119) 

MOUNTING 
HOLES  (2) 
10-32  UNF-2B 
THREAD 

PUSH 
TO 
RESET 

20 FT BY 1/8 INCH 
SENSING ELEMENT 

® U.S. Registered Trademark 
Copyright © 2004 Honeywell International Inc. 

95-7432-1 

All Rights Reserved 

996-496 Rev. A 

Содержание L482A

Страница 1: ...oller case and bellows where ambient temperature is always warmer than the set point 3 For settings above the scale range midpoint it can be necessary to locate the controller case close to a steam pipe or other warm surface and make sure the element does not extend across a cold surface Controller Surface mount the controller Fig 1 vertically on any Fig 1 L482A Low Limit Controller dimensions in ...

Страница 2: ...al straps Fig 3 Fig 2 Element mounted to duct with CCT2600 Clips Fig 3 Element mounted in duct with perforated metal straps C789 GROMMET ELEMENT CLIP DETAIL USE NO 10 SHEET METAL SCREWS BEND HERE IF NECESSARY C790 WIRE FASTENINGS ELEMENT PERFORATED METAL STRAPS OPERATION On a temperature drop to setpoint LINE 1 to M1 contacts close and LINE 2 to M2 contacts open Reset to the normal state is manual...

Страница 3: ...m above sea level CHECKOUT Because of the L482A limited setpoint range operational checkout can be difficult Use one of the following methods to verify proper controller operation 1 If the ambient temperature is below 50 F 10 C a Turn the setpoint adjustment through the ambient temperature and note the switch action b When the setpoint is increased to equal the ambient temperature 1 LINE 1 to M1 c...

Страница 4: ...eywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 996 496 Rev A Printed in U S A on recycled 95 7432 1 B B Rev 4 04 paper containing at least 10 www honeywell com post consumer paper fibers ...

Отзывы: