Position new actuator.

 11 

Follow the reverse procedure when reassembling.

 12 

Fit the M20 cable gland or plug and socket.

 13 

Connect the VAN to the electrical power supply, 

see  page 2 (4 Wiring). 

7 MAIntenAnCe

 CAUtIon

In order to ensure smooth operation, check the 
tightness and function of the unit:

 

– Once per year, twice per year in the case of 

biogas; check for internal and external 
tightness, see page 4 (5 Tightness test). 

 

– Check electrical installations once a year in line 

with local regulations; pay particular attention to 
the PE wire, see page 2 (4 Wiring). 

 

If the flow rate has dropped, clean the strainer.

 

We recommend replacing the seals, see accesso-
ries, page 6 (8.2 Seal set VA 1–2). 

 1 

Disconnect the system from the electrical power 

supply.

 2 

Shut off the gas supply.

 3 

Undo connection parts.

 4 

 

 5 

 

 6 

 

 7 

 

 8 

 9 

Once the seals have been replaced, follow the 

reverse procedure to reassemble the unit. Note 
the recommended tightening torques for the con-
nection parts.

Connection parts

tightening 

torque 

[ncm]

VAx 1: M5

500 ± 50

VAx 2: M6

800 ± 50

VAx 3: M8

1400 ± 100

 10 

Then check the unit for internal and external tight-

ness, see  page 4 (5 Tightness test). 

8 ACCessoRIes

8.1 Pressure switch for gas DG..VC

The pressure switch for gas monitors the inlet pres-

sure p

u

 and the outlet pressure p

d

 

Monitoring the inlet pressure p

u

: the pressure 

switch for gas is mounted on the inlet side.  
Monitoring the outlet pressure p

d

: the pressure 

switch for gas is mounted on the outlet side. 

p

u

p

d

Scope of delivery:  

1 x pressure switch for gas,  

2 x self-tapping retaining screws,  
2 x sealing rings. 

Also available with gold-plated contacts for voltages 

of 5 to 250 V.

 

When retrofitting the pressure switch for gas, see 
enclosed operating instructions “Pressure switch-
es for gas DG..C”, section entitled “Mounting the 
DG..C.. on valVario gas solenoid valves”.

 

The switching point is adjustable via hand wheel.

 1 

 

 2 

 

 3 

type

Adjusting range 

(adjusting 

tolerance = 

± 15% of the 

scale value)

Mean switching 

differential at 

min. and max. 

setting

[mbar]

["WC]

[mbar]

["WC]

DG 17VC

2–17

0.8–6.8 0.7–1.7 0.3–0.8

DG 40VC

5–40

2–16

1–2

0.4–1

DG 110VC 30–110

12–44

3–8

0.8–3.2

DG 300VC

100–

300

40–120

6–15

2.4–8

 

Deviation from the switching point during testing 
pursuant to EN  1854 Gas pressure switches: 

± 15%.

Содержание Krom Schroeder VAN Series

Страница 1: ...in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as fo...

Страница 2: ...Elster GmbH Osnabrück Germany XXXX VAN 3 INSTALLATION CAUTION Incorrect installation Please observe the following to ensure that the magnetic relief valve is not damaged during instal lation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve housing A filter must be installed upstream of every system Dropping the device can cause permanent damage ...

Страница 3: ...ed white VAN open CAUTION Please observe the following to ensure smooth operation Route valve and closed position indicator cables separately through M20 cable glands or use two separate plugs Otherwise there is a risk of interference between valve voltage and closed position indicator voltage To make wiring easier the connection terminal for the closed position indicator can be removed 1 3 2 LV1 ...

Страница 4: ... coating No additional grease is required 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply Remove the M20 cable gland or other type of connection 3 4 5 6 7 8 9 Dependingontheconstructionstageoftheunit there are two different methods for replacing the actuator If the unit concerned has no O ring in this place arrow replace the actuator as described here Otherwise g...

Страница 5: ...M5 500 50 VAx 2 M6 800 50 VAx 3 M8 1400 100 10 Then check the unit for internal and external tight ness see page 4 5 Tightness test 8 ACCESSORIES 8 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pressure pu the pressure switch for gas is mounted on the inlet side Monitoring the outlet pressure pd the press...

Страница 6: ...g with a high pressure cleaner and or cleaning products 9 2 Mechanical data Gas types natural gas LPG gaseous biogas max 0 1 by vol H2S or clean air other types of gas on request The gas must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient temperature Max inlet pressure pu 500 mbar 7 25 psig Leakage rate 500 cm3 h 0 132 gal h Closing time q...

Страница 7: ... For ther moprocessing equipment observe local regulations 11 CERTIFICATION 11 1 Declaration of conformity We the manufacturer hereby declare that the products VAN with product ID No CE 0063BU1564 comply with the requirements of the listed Directives and Standards Directives 2014 35 EU LVD 2014 30 EU EMC 2011 65 EU RoHS II 2015 863 EU RoHS III Regulation EU 2016 426 GAR Standards EN 161 2011 A3 20...

Страница 8: ...ve At the end of the product life number of op erating cycles reached dispose of the pack aging and product in a corresponding recycling centre Do not dispose of the unit with the usu al domestic refuse Do not burn the product On request old units may be returned carriage paid to the manufacturer in accordance with the relevant waste legislation requirements 2022 Elster GmbH We reserve the right t...

Отзывы: