Honeywell K594.RF Скачать руководство пользователя страница 1

K595.RF Product Guide

 

 

Rev 2.0 3/3/2017 

 

 
 

K594.RF Product Guide 

 
 
 

Table of Contents    

 

Table of Contents .............................................. Page 1 

Overview and General Concept ......................... Page 2 

Application ......................................................... Page 2 

Features ............................................................ Page 3 

Installation ......................................................... Page 3 

Commissioning .................................................. Page 4 

Using the E527/E527.4G ............................... Page 5 

Using the E529 .............................................. Page 5 

Binding the K594 ............................................... Page 6 

Using the E527/E527.4G ............................... Page 6 

Using the E529 .............................................. Page 7 

Testing ............................................................... Page 8 

PIR Specifications .............................................. Page 9 

RF Specifications ............................................... Page 9 

Technical Specifications .................................... Page 9 

PIR Coverage .................................................... Page 11 

Document Revision History................................ Page 11 

 

 

 

Содержание K594.RF

Страница 1: ...ation Page 2 Features Page 3 Installation Page 3 Commissioning Page 4 Using the E527 E527 4G Page 5 Using the E529 Page 5 Binding the K594 Page 6 Using the E527 E527 4G Page 6 Using the E529 Page 7 Testing Page 8 PIR Specifications Page 9 RF Specifications Page 9 Technical Specifications Page 9 PIR Coverage Page 11 Document Revision History Page 11 ...

Страница 2: ...losed of other devices within the guestroom see Application below Application The K594 RF s microprocessor controlled PIR detects motion in a guestroom and reports it to the room controller Combined with information from other inputs such as a lanai or window switch or a minibar guestroom occupancy can be determined and used for energy control or lighting decisions Occupancy information may also b...

Страница 3: ...0 angle 0 pitch It should be positioned to view both the entry door and the bed areas of the guestroom the swivel mounting allows adjustment for optimal occupancy sensing The K594 RF should be mounted within operational range of the e4 thermostat and any other devices it may communicate with Avoid possible sources of radio interference such as metallic boxes WiFi access points microwave ovens wate...

Страница 4: ...t Commissioning To function as part of the in room network the K594 RF must be commissioned by accepting instruction as to room identification RF channel P5 address P5 channel and IOMap setting for the specific room see IOMap Summary table below An E528 4G E527 4G or E529 can be used to configure and bind the K594 RF Prepare the thermostat to bind the K594 by setting the Room ID PAN ID and RF Chan...

Страница 5: ...ns and press DISPLAY button to store Room ID The thermostat will beep and scroll new Room ID on display 3 Set the PAN ID a In Service Mode go to Pan PAN ID and press DISPLAY button to view value b Use UP Down arrow buttons to change to desired PAN ID c Press DISPLAY to store The thermostat will beep 4 Set the RF Channel a In Service Mode go to rF RF Channel and press DISPLAY button to view value b...

Страница 6: ...Set into the Thermostat Bind the K594 If Using the E528 E527 4G 1 In Service Parameter mode go to the Io I O Map parameter 2 Press DISPLAY button to view value 3 Change the value to the desired I O Map If only using the K594 as a remote Motion Sensor and NOT using its external input to monitor a door switch or other contact use I O Map 0 Otherwise select the appropriate I O Map from the IOMap Summ...

Страница 7: ...ssage Upon seeing the Bind Offer from the E529 the K595 will bind itself to the advertised Room ID and RF Settings If binding is successful the K594 will Flash its Status LED 3 times Send the thermostat a message to sound its buzzer Reset itself Send a device startup message that includes the K595 software version and its battery status IO Map Name VIF Control VIF Reinforcement Frame 0 Input Disab...

Страница 8: ...mode for 60 seconds IO Map Name VIF 0x1E Control VIF Reinforcement Frame 14 Window Segment 1 0x1E 0x1E 15 Window Segment 1 Inverted 0x1E 0x1E 16 Window Segment 2 0x1E 0x1E 17 Window Segment 2 Inverted 0x1E 0x1E 18 Window Segment 3 0x1E 0x1E 19 Window Segment 3 Inverted 0x1E 0x1E 20 Window Segment 4 0x1E 0x1E 21 Window Segment 4 Inverted 0x1E 0x1E 22 Window Segment 5 0x1E 0x1E 23 Window Segment 5 I...

Страница 9: ...egrees Sensitivity 0 5m 12m 1 64 40ft Parameter K594 RF RF Data Rate 250kbps Antenna Type SMT Indoor Range 70ft Transmit Power 1mW 0dBm Receive Sensitivity 94 6dBm Frequency Band 2 4 Ghz Encryption AES 128 Protocol 802 15 4 Frequency Channels 11 26 Parameter K594 RF Input Voltage 4 x AA Batteries Battery Life 2 2 Years Operating Temperature 0 C to 60 C 32 F to 140 F Storage Temperature 20 C to 60 ...

Страница 10: ...ving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment IC ID 1...

Страница 11: ...product it describes are subject to change without notice Honeywell makes no representations or warranties with respect to this document In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document No part of this document may be reproduced in...

Отзывы: