Hardware Installation
151153
3-8
2. Configure the circuit for Class A in programming (see Section 7.5 of the
IFP-1000 Instal-
lation Manual PN 151139 or IFP-1000ECS Installation manual PN 151460
).
Figure 3-9 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-9 uses both I/O circuit 5 and 6, so in programming it
would be referred to as point 5.
3.5.3
Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for
Class A (Style D) or Class B (Style B) configurations.
3.5.3.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull
stations, directly to the I/O circuits of the RPS-1000 panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 3-10.