![Honeywell IFP-2100 Скачать руководство пользователя страница 152](http://html.mh-extra.com/html/honeywell/ifp-2100/ifp-2100_installation-and-operation-manual_148864152.webp)
Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-9
9.4.2
View Group Points
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 2 to view group points.
5.
Enter the group number, then press ENTER.
9.4.3
Edit OPG Template
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 3 to edit OPG Template.
5.
Enter the Template number, then press ENTER
6.
Press ENTER on the template name to edit the name.
You can use words to display a descriptive name for a group.
Note: See Appendix B for editing names.
7.
Right arrow to the OPG and select YES or NO to select which output groups to include in the template.
9.5
Point
You may need to change characteristics of individual input points (detectors and switches) even after using
JumpStart AutoProgramming. This section explains how to change options for: type of input point; latching/non-
latching status (switches); and name and zone/group assignment of a point.
9.5.1
Point Programming For 5815XL Module
To program for points on an 5815XL module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for
available choices. Then press ENTER.
5.
Enter the number of the point you wish to edit, then press ENTER.
Auto Unsilence
If this option is selected, the output group can be silenced for a programmed time-frame. If the condition that
caused the output to activate has not cleared during the time-frame, the output reactivates. If you select this
option, select the time-frame in the delay field. Range is 0-60 minutes.
Startup Delay
When a alarm is generated, the Output group will not activate until the timer expires assuming the event is
still active. Range is 0-120 Seconds
Table 9-3: Silencing Options
Optional
Timers
Description
Содержание IFP-2100
Страница 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...
Страница 256: ...Cut Along the Dotted Line ...
Страница 258: ...Cut Along the Dotted Line ...
Страница 260: ...Cut Along the Dotted Line ...
Страница 262: ...Cut Along the Dotted Line ...
Страница 263: ......