LS10143-001SK-E
Programming Overview
8-2
Internal Power Supply Circuit 9 (Relay 1):
Assigned to Group 998.
Internal Power Supply Circuit 10 (Relay 2):
Assigned to Group 999.
Addressable output points (Relay modules):
All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to
Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
8.1.3
Running JumpStart
®
AutoProgramming
Run JumpStart AutoProgramming immediately after you have addressed and connected all input devices
(detectors, pull stations, and so on) and output devices (notification appliances, relays, and so on).
Note: If you need to install a few devices after you have run JumpStart, you can install them manually or run
JumpStart again at a later time. JumpStart
®
will keep user options, such as names, for devices already in
-
stalled. Follow instructions in Section 8 for configuration.
To run JumpStart AutoProgramming, follow these steps.
1.
Select 7 for Panel Programming. Enter Access Code.
2.
Select 6 for JumpStart AutoProgramming.
3.
The message “The system will be shut down during JumpStart.” Press ENTER to accept.
4.
When the message, “SLC FAMILY” message appears, select IDP, SK or SD; depending on the type of SLC
devices the panel is using, and press
ENTER
to accept.
5.
A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This
can take several minutes, depending on the number of devices attached.
6.
If a Temp Programming Display is being used to initially setup an RFP-2100, a message will appear for
selecting to install the display or not. If the display is to stay in the system for normal annunciation, select
“Yes”. Otherwise select “No” and the display will be removed.” See Section 4.5.3.
7.
When the message “Configuring System Done” displays, press any key to continue.
Содержание IFP-2100
Страница 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...
Страница 256: ...Cut Along the Dotted Line ...
Страница 258: ...Cut Along the Dotted Line ...
Страница 260: ...Cut Along the Dotted Line ...
Страница 262: ...Cut Along the Dotted Line ...
Страница 263: ......