Summary
The following are steps necessary to install the Telguard device properly.
NOTE: IF YOU DO NOT PROCEED IN THE ORDER AND MANNER PRESCRIBED, YOU MAY NOT
COMPLETE THE INSTALLATION IN THE TIME DESIRED.
These steps are summarized below and explained in detail in the remainder of this manual.
1.
Register for Telguard service
2.
Physically install the TG-7 Series device
•
Mount the TG-7 Series device in desired location
•
If using the optional TG-PEM accessory, install it according to its directions
•
Complete all power-related wiring connections
3.
Determine antenna placement for best performance
•
Connect antenna
•
Measure Received Signal Strength (RSSI)
•
Consider other antenna options
4.
Transmit an alarm over the Telco connection
5.
Activate and transmit alarm panel alarm messages over cellular connection
6.
Connect supervisory trip outputs
7.
Connect trip input (optional)
8.
Connect Tamper Switch (optional)
Note: Step 4 not necessary for Sole Path installations.
This installation approach provides the alarm installer with the easiest and fastest method of properly
installing a TG-7 Series device. Please follow the instructions carefully and if you should need assistance or
have any questions, please call Telguard Technical Support at 1-800-229-2326 extension 9.
Note: Dealer Account Establishment and Telguard Registration must be complete prior to Installation.
Step 1: Register the Telguard Unit
Installation Tip: Register for Telguard service prior to leaving for the job site to avoid a second trip.
The registration form may be completed online through our 24/7 dealer portal
The desired features and programmable options for any installation are selected during the registration
process. This includes STC strategy, Trip-Input enabling, and added value services like HomeControl Flex
and Standard Line Security.
UL/ULC Commercial Fire Sole Path Features
•
Link Supervision: When registering a TG-7FS or TG-KIT device for commercial fire applications,
several link supervision options are available per UL (5-minute supervision and 60-minute
supervision) and ULC (180-second supervision) requirements. These must be enabled during
registration in accordance to code.
•
End-to-End Acknowledgment feature: When enabled an RFC condition will occur when the
captured signal is not delivered to the Central Station as expected.
Decide on a STC Trip Output Strategy
The Telguard device provides the host alarm panel with two supervisory trip outputs for reporting a Telguard
system trouble code to the central station. The supervisory trip outputs are programmable to suit various