5 FAULT TRACING
When a fatal fault is detected by the frequency converter control electron-
ics, the drive will stop and the symbol FT and the fault code blinked on the
display are in the following format, e.g.:
FT 2
Fault code (02 = overvoltage)
The active fault can be reset by pressing BACK/RESET button when the
API is in active fault menu level (FT XX), or pressing BACK/RESET button
with long time (> 2 s) when the API is in active fault submenu level (F5.x), or
via the I/O terminal or field bus. Reset fault history (long push > 5 s), when
the API is in fault history submenu level (F6.x). The faults with subcode and
time labels are stored in the Fault history submenu which can be browsed.
The different fault codes, their causes and correcting actions are presented
in the table below.
Table 11. Fault codes
Fault code Fault name
Possible cause
Correcting actions
1
Overcurrent
Frequency converter has detected too high a current
(>4*IN) in the motor cable:
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
Check loading.
Check cables.
Check motor size.
2
Overvoltage
The DC-link voltage has exceeded the internal safety
limit:
• deceleration time is too short
• high overvoltage peaks in mains
Increase the deceleration time
(„Deceleration time 1“ on page 33 or „Table 25. Ramps
and brakes setup.“ on page 33).
3
Earth fault
Current measurement has detected extra leakage
current at start:
• insulation failure in cables or motor
Check motor cables and motor
8
System fault
• component failure
• faulty operation
Reset the fault and restart.
If the fault re-occurs, contact the distributor near to
you.
NOTE!
If fault F8 occurs, find out the subcode of the
fault from the Fault History menu under Id xxx
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...