Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
127
10.12 Automatic reset
(Control panel: Menu PAR
P13)
Activate the Automatic reset after fault with this parameter.
NOTE:
Automatic reset is allowed for certain faults only.
Fault:
1.
Under voltage
2.
Over voltage
3.
Over current
4.
Motor over temperature
5.
Under load
Trial time
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first auto reset. If the number of faults oc-
curring during the trial time exceeds trail number (the value of P13.4), the
fault state becomes active. Otherwise the fault is cleared after the trial time
has elapsed and the next fault starts the trial time count again. See figure in
the right side.
If a single fault remains during the trial time, a fault state is true.
Fault trigger
Motor stop signal
Motor start signal
Supervision
Fault active
RESET / Fault reset
Trial time
Par. 13.3
Restart 1
Restart 2
Wait time
Par. 13.2
Wait time
Par. 13.2
Wait time
Par. 13.2
Autoreset function: (Trials = 2)
Fig. 65. Example of Automatic restarts with two restarts
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...