7 IOP Calibration Procedures
7.4 LLAI IOP Calibration Procedure
R688
HPM High-Performance Process Manager Service
441
December 2020
Honeywell
Figure 211 Full Scale Calibration Circuit
– TC and All Linear Full Scale Circuits
NC
A
B
C
A
B
C
+
+
User Input Devic e
Input Voltage:
Current Input:
0-100 mV dc
0-5 v olt
4-20 mA
10-50 mA
100 mV
5 V
20 mA (5 V)
50 mA (5 V)
N/A
N/A
N/A
N/A
Themoc ouple: A NSI J
ANSI K
A NSI E
A NSI T
A NSI B
A NSI S
A NSI R
Japanes e Ty pe R
40 mV
40 mV
40 mV
40 mV
20 mV
20 mV
20 mV
20 mV
100 mV
40 mV
100 mV
40 mV
20 mV
20 mV
20 mV
20 mV
Full-Scale Calibration Values
Normal Range Ex tended Range
Channels 2-8
Channel 1
-
-
TB1
TB2
17
1
2
3
4
Shield
Ref erenc e
Cu
Cu
Cu
Cu
Model MU/MC-TAIL01 and MU/MC-TAIL02 FTAs
NC
A
B
C
+
-
Cu
Cu
Model MU/MC-TAIL03 FTA
Channels 1-8
1
3
Install the jumper betw een pins 2 and 3.
2
P1
Use c opper (Cu) w ire f rom v oltage s ourc e.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...