4 Fault Isolation
4.11 I/O Card Indicators
380
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
4.11 I/O Card Indicators
Loss of Power
CAUTION
Loss of power detected by an Analog Output IOP card causes all of the channels of an
Analog Output IOP to drop to a nonpowered state and all channels of a Digital Output
IOP to set its outputs to off. Refer to “Removal and Replacement” section regarding use
of a Standby Manual device to maintain process point output values.
A Journal output status of
NORESP
may indicate this detected loss of power. Check the outputs and the
mode of the related control points should this occur.
Overview
When power is first applied to any IOP or I/O Link Extender card, check the
Power
and
Status
indicators. The
Power
indicator is illuminated whenever dc power is applied. After a few seconds, the
Status
indicator should be illuminated in a steady state.
Indicator functionality
The following table describes the function of the
Power
and
Status
indicators on IOP and I/O Link
Extender cards. The functionality of the
Status
indicator on IOPs with model numbers that have a “Y”
in the model number, such as MU-PAOY22, have additional functionality which is described in Table 79
HPMM Diagnostic Test List. The function of the Power indicator is the same for all IOPs.
Table 80 IOP Card Indicators
Card Type
Indicator
Functionality
IOP
Power
Status
Power is applied to the card. If the indicator is
extinguished, check the Power System, the power
cable to the card file, and the fuse on the backpanel.
If the LED blinks once a second, a Soft failure has
occurred. If the LED remains off, a Hard failure has
occurred.
I/O Link
Extender
Power
Status
Power is applied to the card. If the indicator is
extinguished, check the Power System, the power
cable to the card file, and the fuse on the backpanel.
Flickers when data is being transmitted. If the LED
blinks at a one second rate, an Optic Coupler module is
disconnected.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...