4 Fault Isolation
4.3 Fault Isolation Concepts
R688
HPM High-Performance Process Manager Service
343
December 2020
Honeywell
Table 61 IOP Hard Failure Error Codes
Last Failure
Mnemonic
Description
Corrective Action
UNKNOWN
Unknown hardware failure.
If an IOP card fails and this code is present during restart,
the IOP was disabled, probably by the Watch Dog Timer
time-out circuit, ESD, or RFI. Check the situation.
Replace the IOP if the problem persists.
WRONGCPU
CPU is not the correct part - 80C31
or 80C32
Applicable to I/O Link Interface only (not presently an IOP
error).
IOP Box Soft failure error codes
The IOP Box Soft failure codes are defined in the following table. The corrective actions are identified in
the table.
Table 62 IOP Box Soft Failure Error Codes
Error
Code
Failure
Mnemonic
Description
Corrective Action
00
UNKNOWN
Null Soft failure. No failure
None.
01
STCOVRUN
Sample time clock overrun.
Investigate a possible I/O Link problem. Data
access to the IOP cards may not be operating
properly. Check the High-Performance I/O Link
card, the I/O Link cable, and the IOP cards.
02
REQOFLOW
IOP task request overflow.
Call TAC for assistance.
03
BADRESUM
IOP executive resumed a nonwaiting
task.
Call TAC for assistance.
04
DIAGTMOT
Diagnostics not run in at least 5
seconds indicates a processing
overload.
Investigate control point mix/strategy for an
excessive load. Otherwise, a possible I/O Link
problem exists. Check the High-Performance
I/O Link card, the I/O Link cable, and the IOP
cards.
05
DIAGOFLO
Entire diagnostic cycle overran the 2-
minute allocated time in which
diagnostics have to run to
completion.
Same as error code 04.
06
FTAMISSG
The FTA is missing.
Install the FTA. If an FTA is present, replace the
FTA or check the FTA cable. (Note: For the
LLMux or RHMUX, this code refers to the
Power Adapter assembly. RTD and TC FTAs
are diagnosed by error codes
50 and 51).
07
EECKSMER
EEPROM (used to hold calibration
information in Analog Output IOPs)
checksum failure. It usually means an
Analog Output IOP is not calibrated
properly.
Calibrate the Analog Output IOP card (refer to
the “IOP Calibration Procedures” section for the
procedure). If the error persists, replace the
HLAI, or the AO IOP card, or the FTA.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...