4 Fault Isolation
4.3 Fault Isolation Concepts
R688
HPM High-Performance Process Manager Service
315
December 2020
Honeywell
I/O Link overruns corrective actions
Depending upon the application, one or more of the following actions may be appropriate.
Avoid using IOP resident parameters other than:
Analog Input scan parameters PV and PVSTS.
all alarm flags such as BADPVFL, PVHHFL, PVHIFL, PVLOFL, PVLLFL, PVROCPTP and
PVROCNTP.
Digital Input scan parameters PVFL and BADPVFL.
Digital Output scan parameters SO and INITREQ.
Change the point mix or scan rate to redistribute or slow down points that read multiple non-scan
I/O Link parameters.
Use Logic points for non-scan I/O input connections that are used by more than one point.
Delete inactive or non-essential points and non-scan input connections that are used by more than
one point.
Contact the Honeywell Technical Assistance Center for additional help if the above recovery actions are
not useful.
Comm/Control Hard failure codes
The following the following table defines the Hard failure codes for both the HPMM Communications
and the Control processors. This table spans numerous pages. Some codes are used for both the
Communications and Control processors where others are unique to an individual processor. The CPU
column in the table indicates Both, Comm, or Control to make the distinction.
Corrective actions are identified by number. The corrective actions are listed in Table 57 HPMM
Corrective Actions.
Table 58 Communications and Control Processor Hard Failure Codes
Error
Code
CPU
Failure Mnemonic
Description
Corrective Action
(See Table 57)
0000
Both
NULL
Unknown Error
2
0001
Both
PWRDWN
Power Down Detected
2
0002
Both
LR_PAR
Local RAM parity error
2, 6
0003
Both
LR_LRAM
Unused on HPM Platform
1
0004
Both
LR_CK
Unused on HPM Platform
1
0005
Both
LR_EXC
Unused on HPM Platform
1
0006
Both
LR_HREV
0007
Both
MM_HREV
0008
Both
LR_TMR
0009
Both
LR_PTRN
Local RAM pattern test failure
6
000A
Both
LR_BYTE
Unused on HPM Platform
1
000B
Both
LR_ADCD
000C
Both
LR_ADDL
000D
Both
LR_CLRR
Local RAM initialization test failure
6
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...