2 Equipment Description
2.23 I/O Link Interface Cabling
126
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
Card File Type
I/O Link A Connector
I/O Link B Connector
7-Slot
J23
J24
15-Slot
J42
J43
IOP Only
J32
J31
Cable length
I/O Link Interface cables are to be no longer than 10 m (33 feet) in total length and are not to leave the
cabinet or cabinet complex.
Redundant cables
Two cables are required because the I/O Link Interface is redundant for reliability. One cable is
designated Link A and the other Link B.
No cable termination
The I/O Link Interface cabling does not involve external terminators and therefore an empty I/O Link
Interface connector on the backpanel is an acceptable situation.
CAUTION
The High-Performance Process Manager accommodates four types of card files. Use caution
when connecting the I/O Link Interface cables because of the differences between the card
files. All card files have two I/O Link Interface receptacles marked
LINKA
and
LINKB
.
Содержание HPM
Страница 8: ...Symbol Definitions viii HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 178: ......
Страница 300: ......
Страница 390: ......
Страница 396: ...5 UCN Exerciser 5 5 Test Operation 396 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 400: ...5 UCN Exerciser 5 6 Analyzing Results 400 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 496: ...9 Spare Parts 9 3 UCN EUCN Parts 496 HPM High Performance Process Manager Service R688 Honeywell December 2020 ...
Страница 497: ......
Страница 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...