HPF602ULADA Distributed Power Module Installation Manual
4-13
3.
Connect the red wire to the positive (+) side of Battery #2.
Figure 4-6 Battery Connection
4.8
DIP Switch Settings
A 7-position DIP switch on the HPF602ULADA board allows you to select the following:
•
How long the HPF602ULADA will wait before indicating a loss of AC.
•
Which input (Input 1 or Input 2) will control the NACs.
•
Which NACs to wire as Class A and Class B.
•
Auxiliary power state.
•
Which NACs to operate as steady, ANSI temporal, or sync. outputs
Refer to Figure 4-2 for the location of the DIP switch on the HPF602ULADA board.
4.8.1
Selecting the Standard Input/Output Configurations
Figure 4-7 and Figure 4-8 show the position of each switch for the non-synchronized input and output
configurations. The position of Switches 4 and 5 does not affect the relationship of inputs to outputs.
Note:
The HPF602ULADA checks switches 1, 2, 3, and 6 only when powering up the HPF602ULADA. If you change these
switch settings, you must remove both the AC power and the battery to make the HPF602ULADA recognize the new
Model 6712
(Supervised)
Jumper
(P/N140694)