background image

LeakFilm MC

Master Controller with RS-485 MODBUS

Technical Manual

Содержание HLFCMSRD

Страница 1: ...LeakFilm MC Master Controller with RS 485 MODBUS Technical Manual ...

Страница 2: ...ever attempt to open a plastic enclosure or connector or replace refit the wire of the sensor while power is still applied to the controller LeakFilm controllers must be earthed grounded for electrical safety and to limit the effects of radio frequency interference Earth ground points are provided F G or SHIELD terminal of the controllers Ensure that all screens instrument earth clean earth wiring...

Страница 3: ...ld result in minor injury to personnel or product or property damage Note Identifies useful additional information Every effort has been made to ensure the accuracy of this document however Honeywell Analytics can assume no responsibility for any errors or omissions in this document or their consequences Honeywell Analytics would greatly appreciate being informed of any errors or omissions that ma...

Страница 4: ...tion 8 5 1 Mounting and Location 9 5 2 Standalone installation of LeakFilm MC 9 5 3 LeakFilm MC with Host System 11 6 Electrical connections and power on 13 6 1 Terminal connections 13 6 2 Power on Commissioning 16 7 Configuration 17 7 1 Menu Mode 17 7 2 Alarm Mode 18 8 Characteristic and specification 20 9 Ordering Information 21 10 MODBUS Register Map 22 11 Warranty statement 24 12 Installation ...

Страница 5: ...us indication and configuration The master controller also provides 3 relays fault leak and communication error for controlling external equipment such as alarms sirens valves or switches LeakFilm MC has been designed to be mounted through 4 mounting holes so that the user can easily install the controller on a wall or in the interior of an electrical control panel Caution LeakFilm Mini cannot be ...

Страница 6: ...M should run automatically when put into a computer CD ROM player If the CD ROM does not start click on My Computer locate the CD ROM and double click the file start exe Diagram 2 Package Box Contents WARNINGS When unpacking the product handle with care to avoid any damage to the product Do not throw away the box which may be required for product storage or transport and keep it together with the ...

Страница 7: ... Product Name Description HLFC1DRD LeakFilm Pro 1 Channel Conductive_D Chemical Controller with Leak Location Detection HLFC5CRN LeakFilm 5 5 Channel Conductive Controller with Broken Sensor Detection HLFC1HRN LeakFilm HC 1 Channel Hydrocarbon Controller with Broken Sensor Detection Diagram 3 Applicable LeakFilm controllers Table 1 Applicable LeakFilm controllers ...

Страница 8: ...hed grounded for electrical safety and to limit the effects of radio frequency interference Earth ground points are provided F G or SHIELD terminal of the controllers Ensure that all screens instrument earth clean earth wiring is earthed grounded at a single point either at the controller or master controller BUT NOT BOTH to prevent false readings or alarms that may occur due to potential earth gr...

Страница 9: ...e noted when locating the controllers When locating the controllers consider the possible damage caused by natural events e g rain or flooding LeakFilm MC provides only IP43 limited water proof feature Consider ease of access to the controller for repair and maintenance Avoid any location mentioned in the above warnings See the installation drawing at the end of this manual for mechanical dimensio...

Страница 10: ...xMD The acceptable range is 1 to 200 and the default value is 200 See 6 1 Electrical connections for instructions on how to set MaxMD When you use LeakFilm 5 together with LeakFilm Pro HC set the ID of LeakFilm 5 between 1 and 15 first and then set the IDs for LeakFilm Pro and HC later to the rest of the numbers because LeakFilm 5 ID can be set only from 1 to 15 while LeakFilm Pro HC can be set fr...

Страница 11: ...il A communication ID is required for LeakFilm MC to communicate with the host system The acceptable range of the ID is from 1 to 32 and the default value is 1 The ID of each master controller should be unique otherwise it cannot communicate with the host system properly due to ID conflict See 6 1 Terminal connections for instructions on how to set the communication ID ID 1 ID 2 ID 32 Max 32 units...

Страница 12: ...ny software tool to log the data from LeakFilm MC The user should create a tool based on the MODBUS register map or should purchase a commercial tool suitable for the purpose Caution Each master controller connected to the host system should have a unique communication ID otherwise incorrect data can be transmitted to the host system ...

Страница 13: ... are provided F G or SHIELD terminal of the controllers Diagram 5 Wiring Diagram V from SMPS V from SMPS Power S W Spare Terminal Not used MODBUS RS485 to host system MODBUS RS485 to host system Rx to slave controllers Tx to slave controllers Sensor Broken Relay Output NO Leak Relay Output NO Comm Error Relay Output NO Sensor Broken Relay Output NC Leak Relay Output NC Comm Error Relay Output NC S...

Страница 14: ... relay NO and COM closed when leak signal detected NC Normal close of the relay NC and COM open when leak signal detected COM Common of the relay NO Communication Error Relay J4 Normal open of the relay NO and COM closed when communication error detected NC Normal close of the relay NC and COM open when communication error detected COM Common of the relay NO Spare Relay J5 Not used NC Not used COM...

Страница 15: ...of communication ID setting of LeakFilm MC User can set MaxMD using the SW4 dip switch as shown in the below table If MaxMD is 7 LeakFilm MC scans from 1 to 7 only In this case any controller with an ID of more than 7 will not be scanned so it will not be monitored by the LeakFilm MC To avoid missing any controllers that are connected to the LeakFilm MC leave MaxMD set to the default value of 200 ...

Страница 16: ...t turns on 6 LeakFilm MC enters normal monitoring mode LCD LED Display Description Version 1 0 ID 001 MaxMD 200 Software version display ID 001 shows the communication ID of LeakFilm MC set by SW3 dip switch MaxMD 007 shows MaxMD set by SW4 dip switch 2 seconds delay LeakFilm Master Controller 2010 01 08 06 12 16 Leak System Normal Normal monitoring mode Display date time at normal no alarm status...

Страница 17: ...in normal and how many slave control lers are in alarm status 2 Status History 2 Status History 392 Module 002 Leak Clear 2010 01 08 16 12 16 User can view the event log using the UP and DOWN buttons A maximum of 999 events can be logged in LeakFilm MC 3 Re Scan Module 3 Re Scan Module Re Scan start This function rescans all the controllers connected to LeakFilm MC Once a new controller is connect...

Страница 18: ...Modbus Set Baud Rate 9600 Set the communication speed between the master controller and the host system Normal monitoring mode Display date and time at normal no alarm status Table 6 Menu Mode of LeakFilm MC 7 2 Alarm Mode Once the alarm occurs in one of slave controllers connected to LeakFilm MC it displays as below LCD LED Display Description Comm Error LeakFilm Master Controller 2014 03 10 21 2...

Страница 19: ...4 10 Module 001 0 0m FAULT LEAK COMM ERR POWER When a leak occurs LeakFilm MC displays the module number and location of the leak and the LEAK LED turns on The buzzer sounds as set by the Silent Control menu Table 7 Alarm Mode of LeakFilm MC Caution If LeakFilm MC detects multiple alarms from the slave controllers it displays all alarms by controller module ID sequentially ...

Страница 20: ...Relay NC NO Communication RS485 MODBUS Communication Function Status transmission Leak Detection Leak Location Leak Clearance Broken Detection Broken Clearance Communication error and clearance Data Recording 999 events Detector ID Leak and Leak location or Broken or Communication error year month day hour min sec Storage Temperature 10 to 65 C Operating Temperature 10 to 55 C Operating humidity 5...

Страница 21: ...onductive Sensor with Leak Position Detection HLFSSCND 001 Custom Length Conductive Sensor with Leak Position Detection HLFSSAND 100 LeakFilm Chemical 100 meter Chemical Sensor with Leak Position Detection HLFSSAND 050 50 meter Chemical Sensor with Leak Position Detection HLFSSAND 001 Custom Length Chemical Sensor with Leak Position Detection HLFSSHNN 100 LeakFilm Hydrocarbon 100 meter Hydrocarbon...

Страница 22: ...roken Bit 6 0 CH2 Normal 1 CH2 Sensor Broken Bit 7 0 CH3 Normal 1 CH3 Sensor Broken Bit 8 0 CH4 Normal 1 CH4 Sensor Broken Bit 9 0 CH5 Normal 1 CH5 Sensor Broken 30119 30132 Reserved N A 14 Reserved for future expansion 30133 Status of slave controller ID 002 R 1 Same as register 30117 See above note 30134 Leak location for LeakFilm Pro ID 002 Status for LeakFilm 5 ID 002 Not used for LeakFilm HC ...

Страница 23: ...HC ID 016 R 1 Same as register 30118 See above note 30359 30372 Reserved N A 14 Reserved for future expansion 33301 Status of slave controller ID 200 R 1 Same as register 30117 See above note 33302 Leak location for LeakFilm Pro ID 200 Not used for LeakFilm HC ID 200 R 1 Same as register 30118 See above note 10 MODBUS Register Map ...

Страница 24: ...attendance where any fault is not found with the equipment Honeywell Analytics shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or operation of the Contract Goods by the Buyer or any Party This warranty covers instrument and parts sold to the Buyer only by authorized distributors dealers and representatives as appoint...

Страница 25: ...25 LeakFilm MC Technical Manual 3013M5005 Issue 3 MAN0966 04 15 12 Installation Drawing ...

Страница 26: ...26 LeakFilm MC Technical Manual 3013M5005 Issue 3 MAN0966 04 15 12 Installation Drawing ...

Страница 27: ...41 0 44 943 4300 Fax 41 0 44 943 4398 gasdetection honeywell com Customer Service Tel 800 333 222 44 Freephone number Tel 41 44 943 4380 Alternative number Fax 800 333 222 55 Middle East Tel 971 4 450 5800 Fixed Gas Detection Middle East Tel 971 4 450 5852 Portable Gas Detection India Tel 91 124 4752700 Americas Honeywell Analytics Inc 405 Barclay Blvd Lincolnshire IL 60069 USA Tel 1 847 955 8200 ...

Отзывы: