4. Set Up and Calibration Procedures - Calibration
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
61
7/07
Calibrate Motor
Use the procedure in Table 24 to calibrate the actuator motor for 0 % and 100 % input signal
ATTENTION
For a motor calibration to be saved, you must complete the procedure. The calibration will not
be saved if you exit without completing the steps of the procedure.
Table 24 Motor Calibration Procedure
Step
Operation
Press
Result
1
Enter Calibration
Mode
SETUP
until you see
Upper Display
=
CAL
Lower Display
=
MOTOR
FUNCTION
Upper Display
=
DIS
Lower Display
=
CALMTR
or
key
Upper Display
=
BEGN
Lower Display
=
CALMTR
2
Calibrate Zero (0%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
MTR LO
•
Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its low position.
•
Wait 5 seconds, then go to step 3.
3
Calibrate Span
(100%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
MTR HI
•
Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its high position.
•
Wait 5 seconds, then go to step 4.
4
FUNCTION
Calibration for zero and span motor positions are now saved.
Motor calibration is complete.
NOTE: See Table 25. You may also exit calibration mode by
pressing the DISPLAY or SETUP keys.
NOTE: If you are calibrating the motor to a short stroke range, the procedure is the same.
ATTENTION
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit
switches. See
Setting End-of-Travel Limit Switches
.