T8411R ELECTRONIC HEAT PUMP THERMOSTAT

7

68-0185—2

To set the °F/°C indication and heat cycle rate:

1.

If the room temperature is displayed 
in °F, set the temperature setpoint to 

52°F. If the room temperature is dis-

played in °C, set the temperature 
setpoint to 11°C. 

2.

Press the 

 

 keys simultaneously 

for more than two seconds to light all 
segments on the display and to 

enter installer setup mode. When 

the keys are released, a two-digit 
software code is displayed.

OPTIONAL SYSTEM CHECKOUT 

When the heat or cool outputs are turned on, the five-minute 

off-timer safety feature is bypassed.

When in steps 2. and 3. only, the 

 key can be used to turn 

heat or cool outputs on and off. Change the SYSTEM switch 

setting to test heat or cool outputs. No action takes place If the 
system switch is in the Off position.

The following examples of system settings show a two digit 
software code on the display. The code shown is only an 

example; codes can vary.

System setting at Heat:

To turn heat on, press the 

 key.

To turn auxiliary heat on, press the 

 key.

To turn auxiliary heat off, press the 

 key a third 

time.

To turn heat off, press the 

 key a fourth time.

System setting at Cool:

To turn cool on, press the 

 key.

To turn cool off, press the 

 key.

3.

Press the 

 key. Factory information is displayed. Infor-

mation displayed varies by model. This information is 

only for factory use.

4.

Press the 

 key again to display °C or °F.

5.

Press the 

 key to change the °C or °F indi-

cation.

NOTE: Stage one heat and cool cycle rates are 

fixed at 3 cph. Only stage two heat cycle 

rates are selectable.

6.

Press the 

 key to display the heat cycle rate 

of 3, 6, or 9. If the desired cycle is displayed, 
press the 

 key to exit the installer setup 

mode. To change the heat cycle rate, press the 

 key to 

scroll between 3, 6, and 9. Stop scrolling when the 
desired rate is displayed. 

7.

Press the 

 key to display cool-

ing algorithm configuration 
default.

8.

Press the 

 key again to change 

cooling algorithm to C1 or C3.

C1 = Standard cooling algorithm.

C3 = Aggressive cooling algorithm (can cause 

overshooting).

9.

Press the 

 key again. Current configuration 

(CC) is displayed. A typical example is 

shown, but CC varies by model. This informa-
tion is for factory use only. 

10.

Press 

 to save all changes, exit installer 

setup mode and return to normal operation.

NOTE: After exiting installer setup mode, change the set-

point to the desired room temperature.

OPERATION

The T8411R Thermostat provides two-stage heat and one-
stage cool temperature control with proportional plus integral 

control to eliminate droop.

Comfort Period

In mild weather, the heat pump cycles continuously to maintain the 
sensed temperature within 1°F of the setpoint. In moderate weather,

 

the heat pump cycles longer, minimizing the need for auxiliary 

heat. The heat pump runs the majority of the time in severe 
weather and only shuts off for brief periods using auxiliary 

heat to maintain temperature within 1°F of setpoint. 

Thermal Performance

During severe weather, the T8411R actually controls closer to 
the setpoint than a conventional control. This is because the 

heat anticipator is replaced by two electronic control 

strategies— cycling by heat anticipation and proportional plus 
integral (P+I) control.

Electronic cycling by heat anticipation acts like a traditional heat 
anticipator except that it never needs adjusting for various con-trol 

circuit load currents. It cycles off the heating system slightly before the 

room temperature reaches the setpoint to keep heat that remains in the 
ductwork from overheating the room.

In severe weather, a conventional control with a heat 
anticipator tends to turn off the system too soon so the 

effective setpoint is somewhat below the setpoint. In very cold 

weather, the difference between setpoint and effective control 
point can be 5°F or 6°F (2°C or 3°C) with a conventional 

control. This phenomenon is called droop.

Proportional plus integral action eliminates droop by adjusting 

the on time of the stage until the control point matches the 

setpoint. The T8411R maintains the space temperature within 
1°F of the setpoint. 

This zero droop performance provides improved occupant 
comfort and energy savings. Occupants do not need to 

continually adjust thermostat settings to maintain desired 

temperature, even during severe weather.

M14683

M18426

M18431

M18432

Aux Ht

M18433

M18434

M18435

M18434

M14688

M14689

M14690

M18421

or

M18420

Содержание HEAT PUMP THERMOSTAT T8411R

Страница 1: ...in a variety of locations Keys are located by the display for easy access Fan and system switches are located on the lower edge to eliminate accidental setting changes Easy installation setup and self test saves installer time and increases their productivity Manual changeover from heat to cool eliminates unexpected system operation F or C temperature display for added model flexibility Selectable...

Страница 2: ...1R TRADELINE model includes a thermostat wallplate for wiring and mounting thermostat and owner s guide Power T8411R 24 Vac nominal 18 to 30 Vac 50 60 Hz Electrical Ratings First Stage Heating 0 02 to 1 5A run 7 5A inrush Second Stage Heating 0 02 to 1 5A run 3 5A inrush Cooling 0 02 to 1 5A run 7 5A inrush Fan 0 02 to 0 5A run 2 5A inrush Emergency Heat Output E 0 02 to 1 5A run 3 5A inrush Heati...

Страница 3: ...on Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average room temperature See Fig 2 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the therm...

Страница 4: ...ate and con nect the system wires See Fig 4 2 Securely tighten each terminal screw 3 Push the excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat Mounting Thermostat to Wallplate 1 Engage the tabs at the top of the thermostat and wall plate 2 Swing down the thermostat and press the lower edge of the thermostat onto the wallpla...

Страница 5: ... TERMINALS SYSTEM SWITCH HEAT OFF COOL R W2 L B O Y EM HT W1 E AUXILARY HEAT RELAY CHANGEOVER VALVE HEAT CHANGEOVER VALVE COOL COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR HEAT FAN RELAY RELAY EMERGENCY HEAT RELAY G C THERMOSTAT LOGIC THERMISTOR SENSOR POWER SUPPLY ON AUTO STAGE 2 RELAY STAGE 1 RELAY FAN SWITCH M11333A 3 3 M18577 SYSTEM Cool Off Heat Em Ht Auto On FAN DASHED LINES INDICATE TABS ON BA...

Страница 6: ...heating load Set Temperature Setpoint NOTE Temperature setpoint range is 40 to 99 F 4 to 39 C The temperature setpoint and the room temperature are shown separately on the display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right ...

Страница 7: ... displayed A typical example is shown but CC varies by model This informa tion is for factory use only 10 Press to save all changes exit installer setup mode and return to normal operation NOTE After exiting installer setup mode change the set point to the desired room temperature OPERATION The T8411R Thermostat provides two stage heat and one stage cool temperature control with proportional plus ...

Страница 8: ...ting and cooling Table 1 Sequence of Operations a The O terminal is powered continuously in cooling the B terminal is powered continuously in heating and the L terminal is powered continuously in emergency heat as a function of the system switch position even without a call for heat or cool CHECKOUT Heating 1 Slide the SYSTEM switch to Heat and the FAN switch to Auto 2 Press and hold the s key to ...

Страница 9: ... THERMOSTAT PARTIAL DISPLAY INOPERATIVE THERMOSTAT SEE THE SETTINGS AND ADJUSTMENTS SECTION FOR INSTRUCTIONS ON INSTALLER SETUP MODE STILL IN INSTALLER SETUP MODE RECONFIGURE THE DISPLAY SEE SETTINGS AND ADJUSTMENTS SECTION TEMPERATURE DISPLAY IS INCORRECT THERMOSTAT IS CONFIGURED FOR F OR C DISPLAY CHECK THAT C TERMINAL IS CONNECTED TO THE SYSTEM TRANSFORMER CHECK POWER TO HEATING AND COOLING EQU...

Страница 10: ...68 0185 2 10 ...

Страница 11: ...11 68 0185 2 ...

Страница 12: ...ilding Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: