INSTALLATION INSTRUCTIONS

62-0330-01

H7625B, H7626B, H7635B,C 

H7636B, H7655B, H7656B

DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/

TEMPERATURE SENSORS

APPLICATION

The H76XXB Duct-Mount and H76XXC Outdoor-Mount 

Humidity/Temperature Sensors are universal Relative 

Humidity transmitters that can be powered with either a 

+18 to 40 Vdc or 24 Vac supply . The devices are half 

wave rectified. The transmitter also includes either a 20K 

ohm NTC thermistor or a 1K platinum PTC (compatible 

with the T775) for optional temperature use.

The humidity sensors are designed with a field selectable 

4 to 20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output signal 
equivalent to 0 to 100% RH. All units are shipped from 
the factory with a default setting to accept AC power with 
three-wire, 0 to 10 Vdc output.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 

hazardous condition.

2.

Check ratings given in instructions and on the 
product to ensure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage 
Hazard.

Can shock individuals or short equipment 
circuitry.

Disconnect power supply before installation.

CAUTION

Equipment Damage Hazard.
Improper wiring can damage the sensor 
beyond repair.

Follow the wiring instructions carefully.

Mounting

The method of mounting depends on the particular 

sensor application. The following procedures include 

outdoor and duct applications. Also refer to the 

instructions for the electronic control.

Duct mounting Configuration

The H7625B, H7626B, H7635B, H7636B, H7655B and 

H7656B can be mounted in a duct to sense humidity and 

temperature.

IMPORTANT

Select a location to expose sensor to average 
duct humidity and temperature. Avoid locations 
where stratification can cause sensing errors.

NOTES:
• Knockouts allow 1/2 in. conduit connection. To avoid 

damaging board during installation, the cover can be 
detached completely:

• Carefully remove wire plug from board.
• Set the cover aside.

1.

Drill a 3/4” diameter hole in the duct where the 
transmitter is to be mounted. 

2.

Insert the stainless steel probe into the hole until 
the foam is in direct contact with the duct.

3.

Attach the transmitter to the duct using the sup-
plied #8 X 3/4” self-tapping screws.

4.

Remove the cover and install your conduit connec-
tor or watertight fitting. The outer ring is used when 
using a 1/2” NPT conduit fitting.

5.

After wiring the unit, place the cover back on and 
gently turn it until it is tight.

Outdoor Mounting Configuration

The H7635C senses outdoor air humidity and 
temperature. Mount this control where it can sense 
average outdoor air humidity and temperature. Normally, 
the north side of a building provides a suitable location.

NOTES:
• H7635C is weatherproof for outdoor use. Knockouts 

allow 1/2 in. conduit connection. 

• To avoid damaging board during installation, the cover 

can be detached completely:

• Carefully remove wire plug from board.
• Set the cover aside.

Содержание H7625B

Страница 1: ...structions carefully Mounting The method of mounting depends on the particular sensor application The following procedures include outdoor and duct applications Also refer to the instructions for the electronic control Duct mounting Configuration The H7625B H7626B H7635B H7636B H7655B and H7656B can be mounted in a duct to sense humidity and temperature IMPORTANT Select a location to expose sensor...

Страница 2: ...s The humidity output signal can be adjusted for 0 5Vdc 0 10 Vdc or 4 20 mA using the switch block Switches 6 7 and 8 are used to set the output NOTE Refer Fig 2 for switch settings Table 1 Controller Compatibility and Output Settings Fig 2 DIP switch and Wire Connection locations M31319 INCORRECT CORRECT Controller Required Sensor Output Setting LONSPEC Setting W7750 W7760 W7761 4 20 mA C7600C W7...

Страница 3: ...ed pair may be used for 2 wire current output transmitters the connections to the temperature sensor should be made with wire nuts or crimp style connectors Refer to Figure 3 for wiring diagrams CAUTION Never connect or disconnect wiring with power applied Fig 3 Wiring Diagrams CAUTION It is recommended that you use an isolated UL listed class 2 transformer when powering the unit with 24 VAC Failu...

Страница 4: ... MOTION SENSOR HUMIDITY SENSOR M OS OS AS AS M HC HP HS COM VIN Vac VOUT 0 10 Vdc 1 4 L1 HOT L2 COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2 HEAT RELAY 1 FAN RELAY ECONOMIZER HEAT RELAY 2 COMPRESSOR CONTACTOR 3 COMPRESSOR CONTACTOR 4 12 2 3 4 5 6 7 TR23 Remote Sensor 8 9 10 11 1 E GND OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 DI 1 DI 2 DI 3 DI 4 GND GND 24 VAC COM 24 VAC COM 24 VAC 24 VAC 2...

Страница 5: ... signal 7 50 0 10 75 RH Table 2 Troubleshooting M31268 1 24 VAC 24 VAC COM EGND SHLD SBUS1 SBUS2 NET 1 NET 2 24 VAC COM 24 VAC 2 3 4 5 6 7 8 9 DO 1 DO 2 COM DO 3 DO 4 COM DO 5 DO 6 0 1 2 3 4 5 6 COM DO 7 DO 8 COM 7 8 9 0 1 1 1 1 1 1 1 1 1 1 2 1 AO 1 COM AO 2 AO 3 COM D1 1 D1 2 COM 2 3 4 5 6 7 8 D1 3 D1 4 20VDC U1 1 9 0 1 2 2 2 2 2 2 2 2 2 2 3 3 3 COM 3 3 U1 2 4 3 U1 3 5 3 COM 6 3 U1 4 7 3 U1 5 8 3...

Страница 6: ... Table 3 Test and Calibration Settings 8 Switch Block Switch setting does not affect output This switch needs to be activated first Indicates OFF Setting 1 2 3 4 5 6 7 8 4 20mA Output 0 5 VDC Output On On 0 10 VDC Output On On 0 RH Output On 50 RH Output On 100 RH Output On Increment RH Output On On Decrement RH Output On On Reset to Original Calibration On On On Reverse or Direct Acting On On On ...

Страница 7: ...l show the 50 output again When the unit is out of setup mode the output will go back to RH output Increment RH Output This will shift the RH output linearly up in 0 5 steps Switch 4 must be set to ON first After switch 4 is on each time switch 5 is set ON the RH output will increase by 0 5 The increase goes into effect each time switch 5 is set to ON Decrement RH Output This will shift the RH out...

Страница 8: ...al Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 62 0330 01 E K Rev 03 10 Printed in U S A LonSpec is a trademark of Echelon Corporation ...