Programming
Master Programming Level
The
Piezo Enable
option allows the programmer to select whether the piezo sounder on any installed GFANN-80 module will ever
sound. Pressing
1
while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Piezo Enable Yes
and
Piezo
Enable No
.
The
Lock Enable
option allows the programmer to select whether or not the GFANN-80 annunciator must be unlocked by its key before
any annunciator key presses will function. Pressing
2
while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes
(annunciator must be unlocked for keys to function) and
Lock Enable No
(lock position is ignored).
The Acknowledge Button Enable (
ACK BTN ENABLE
) option allows the programmer to select whether the Ack/Step button on any
installed GFANN-80 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-80 Options Screen #1
causes the display to toggle between
Ack Btn Enable Yes
(Ack/Step button functions normally) and
Ack Btn Enable No
(Ack/Step button
never functions).
The Silence Button Enable (
SIL BTN ENABLE
) option allows the programmer to select whether the Silence button on any installed
GFANN-80 annunciator will function normally or always be ignored. Pressing
1
while viewing the ANN-80 Options Screen #2 causes
the display to toggle between
Sil Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence button never func-
tions).
The Reset Button Enable (
RST BTN ENABLE
) option allows the programmer to select whether the Reset button on any installed
GFANN-80 annunciator will function normally or always be ignored. Pressing
2
while viewing the ANN-80 Options Screen #2 causes
the display to toggle between
Rst Btn Enable Yes
(Reset button functions normally) and
Rst Btn Enable No
(Reset button never func-
tions).
The Drill Button Enable (
DRL BTN ENABLE
) option allows the programmer to select whether the Drill button on any installed GFANN-
80 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-80 Options Screen #2 causes the display
to toggle between
Drl Btn Enable Yes
(Drill button functions normally) and
Drl Btn Enable No
(Drill button never functions).
ANN-RLY Options Screen
Pressing
3
for
ANN-RLY Options
while viewing ANN-BUS Screen #2 will cause the following screen to be
displayed:
The GFANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays
Relays 1 through 3. Pressing the down arrow key will display the remaining relays for this module.
To program any of the GFANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key correspond-
ing to the relay to be programmed. Following is a list of the available programming options for each relay:
•
General Alarm
•
General Trouble
•
General Supervisory
•
AC Loss
•
Waterflow Delay
•
Input Zone 1
•
Input Zone 2
•
Input Zone 3
•
Input Zone 4
•
Input Zone 5
•
Input Zone 6
•
Input Zone 7
•
Input Zone 8
•
Input Zone 9
•
Input Zone 10
•
Silenceable Alarm
•
Not Assigned
ANN-SEC Enable
The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card at J13. To enable the Secondary
ANN-BUS, press
2
while viewing ANN-BUS Screen #3 so that the display reads
ANN-SEC ENABLE YES
. Each press of the
2
key will
cause the display to toggle between
ANN-SEC ENABLE YES
and
ANN-SEC ENABLE NO
. The factory default setting is
ANN-SEC
ENABLE NO
.
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen