These instructions cover how to install the replacement PSU
PCB assembly and cover (VCS-PSU-N) in to a Vigilon Compact
panel, either COMPACT-24 (non networkable) or
COMPACT-24-N (networkable) panel or Nano panel (NANO-24)
. The package contains:

1 - Replacement PSU PCB assembly

1 - Replacement Cover
Not used on Nano
panel

To replace the PSU in a Vigilon Compact panel

&

Isolate the mains power supply to the Vigilon Compact

panel.

Removal

a.

Open the outer and inner doors of the panel.

b.

Disconnect the mains cable from the mains terminals

j

at

PSU PCB assembly and unplug the battery circuit cable
from connector

k

.

c.

Remove the two nuts and washers from the panel

l

(keep

for later use)

and lift out the cover

m

or

q

.

d.

Disconnect the ribbon cable

n

.

e.

Remove the two screws and washers that secure the PSU
assembly

o

(keep for later use)

and lift out the PSU PCB

assembly

p

or

r

from the clinching standoffs.

Replacement

a.

Fit the

Replacement PSU PCB assembly

r

on to the two

self clinching standoffs.

&

Ensure that the Replacement PSU PCB assembly is

secured using screws and washers at the two fixing points

o

.

b.

Reconnect the ribbon cable

n

between Replacement PSU

PCB assembly and MCB assembly.

c.

Align the

Replacement cover

q

with the two fixings on the

panel side. Slide the cover down and secure it using the
nuts and washers

l

.

d.

Reconnect the mains cable to mains terminals

j

on the

Replacement PSU PCB assembly.

e.

Reconnect the battery circuit to connector

k

on

Replacement PSU PCB assembly .

f.

Close the inner and outer doors of the panel.

4188-905 issue 2_07/08_Replacement PSU

1

Installation

Replacement PSU PCB & Cover

(VCS-PSU-N)

by Honeywell

Inner door

REMOVAL OF COVER

EXPOSES HIGH VOLTAGE

WARNING

REMOVE ONLY

DURING COMMISSIONING

Back box

Vigilon Compact panel

Existing PSU

New PSU

MCB

assembly

MCB

assembly