These instructions cover how to install the replacement PSU
PCB assembly and cover (VCS-PSU-N) in to a Vigilon Compact
panel, either COMPACT-24 (non networkable) or
COMPACT-24-N (networkable) panel or Nano panel (NANO-24)
. The package contains:
1 - Replacement PSU PCB assembly
1 - Replacement Cover
Not used on Nano
panel
To replace the PSU in a Vigilon Compact panel
&
Isolate the mains power supply to the Vigilon Compact
panel.
Removal
a.
Open the outer and inner doors of the panel.
b.
Disconnect the mains cable from the mains terminals
j
at
PSU PCB assembly and unplug the battery circuit cable
from connector
k
.
c.
Remove the two nuts and washers from the panel
l
(keep
for later use)
and lift out the cover
m
or
q
.
d.
Disconnect the ribbon cable
n
.
e.
Remove the two screws and washers that secure the PSU
assembly
o
(keep for later use)
and lift out the PSU PCB
assembly
p
or
r
from the clinching standoffs.
Replacement
a.
Fit the
Replacement PSU PCB assembly
r
on to the two
self clinching standoffs.
&
Ensure that the Replacement PSU PCB assembly is
secured using screws and washers at the two fixing points
o
.
b.
Reconnect the ribbon cable
n
between Replacement PSU
PCB assembly and MCB assembly.
c.
Align the
Replacement cover
q
with the two fixings on the
panel side. Slide the cover down and secure it using the
nuts and washers
l
.
d.
Reconnect the mains cable to mains terminals
j
on the
Replacement PSU PCB assembly.
e.
Reconnect the battery circuit to connector
k
on
Replacement PSU PCB assembly .
f.
Close the inner and outer doors of the panel.
4188-905 issue 2_07/08_Replacement PSU
1
Installation
Replacement PSU PCB & Cover
(VCS-PSU-N)
by Honeywell
Inner door
REMOVAL OF COVER
EXPOSES HIGH VOLTAGE
WARNING
REMOVE ONLY
DURING COMMISSIONING
Back box
Vigilon Compact panel
Existing PSU
New PSU
MCB
assembly
MCB
assembly