The kit (S4-INTERFACE-PROG)
can be used to program the

S4-Interface units

to simulate

legacy 344XX range of interface
units. This allows the
S4 interface units to be used in
place of old interfaces without the
need to upgrade or re-commission
the system.

Setting the rotary switches

The Programmer has four rotary
switches to set interface channels.

Set the rotary switches on the Programmer to the required number or letter for
each interface Input/Output channel(s).

To convert a S4-Interface to a
344XX interface:

Rotary switch settings on the Programmer

S4-34401

S4-34410

S4-34440-02

S4-34450

S4-34404

to a

Rotary
Switch
position Function

Applied
delay

3
4
4
1
5

3
4
4
1
0

3
4
4
4
0

3
4
4
5
0

Link
setting
applicable
to

S4-34450
only

3

4

4
5

0 ~

0

Unused

#

#

P P

1

Relay Output (N/O) or
Sector Output
(Normally Off)

P P

2

Relay Output (N/C) or
Sector Output
(Normally On)

P

3

N/C Fire Input

No delay

P

P

P

4

N/O Fire Input

No delay

P

P

P

5

N/C Fault Input

No delay

P

P

P

6

N/O Fault Input

No delay

P

P

P

7

N/C Supervisory Input No delay

P

P

P

8

N/O Supervisory Input No delay

P

P

P

9

N/C Fire Input

10s delay

!

P

!

A

N/O Fire Input

10s delay

!

P

!

B

N/C Fault Input

10s delay

!

P

!

C

N/O Fault Input

10s delay

!

P

!

D

N/C Supervisory Input 10s delay

!

P

!

E

N/O Supervisory Input 10s delay

!

P

!

F

Zone Input -
S4-34450 and
S4-34410 (channel 1
only)

P P P

N/C - Normally Closed N/O - Normally Open

!

- check if delay of 10s can be applied, the old product has a fixed delay of 30s.

P

- applicable option

# - only channel 1 is configurable, channels not used set to - UNUSED
~ - 34450 with 19245-06 PSU used for mains switching

A converted interface unit can be installed in an analogue addressable panel
based system:
BS panel having - MCC

³

V3.70 and LPC

³

V3.81

EN panel having - MCC

³

V4.10 and LPC

³

V4.11

4188-982 issue 5-3_10-13_S4 Interface progkit

1

User guide

S4 Interface Programmer

Kit

(S4-INTERFACE-PROG) V1.04

by Honeywell

AC-DC Adaptor
Model MCPLG6V10WUK
Input: 230Vac 47-63Hz 0.3A
Output: 6V

1.33A

Programmer

Cable assembly

Channel 4

Channel 3

Channel 2

Channel 1

Rotary switches

01

2

3

4

5

6

7 8 9 A B

C

D

E

F

Содержание GENT S4-INTERFACE-PROG

Страница 1: ... 5 N C Fault Input No delay P P P 6 N O Fault Input No delay P P P 7 N C Supervisory Input No delay P P P 8 N O Supervisory Input No delay P P P 9 N C Fire Input 10s delay P A N O Fire Input 10s delay P B N C Fault Input 10s delay P C N O Fault Input 10s delay P D N C Supervisory Input 10s delay P E N O Supervisory Input 10s delay P F Zone Input S4 34450 and S4 34410 channel 1 only P P P N C Norma...

Страница 2: ...er S4 34450 S4 34410 Interface unit then repeat the process from a e When all the programming is finished switch off the mains supply and unplug the AC DC Adaptor lead from the Programmer and mains socket The programmed S4 34450 S4 34410 Interface unit is now ready and can replace an existing 34450 or 34410 loop interface unit on a loop circuit of an Analogue Addressable fire detection and alarm s...

Страница 3: ...connect the battery lead from connector P7 on the PCB and remove the batteries and leads from the unit If mains supply was used to power up the S4 34440 02 Mains powered interface unit then power down and disconnect the Mains cable Close the door on the unit g If programming a number of S4 34440 02 Mains powered interface units then follow procedures a to f h When programming is finished switch of...

Страница 4: ...S4 34404 Mains switching interface unit can be used in place of a legacy interface 34450 having a 19245 06 Power supply unit A programmed S4 34401 Mains switching interface unit can be used in place of a legacy 34415 Single channel loop powered interface unit Where the interface unit is installed on a loop circuit of an Analogue Addressable fire detection and alarm system Connect the system cables...

Отзывы: