Installation Guide and Operating 
Manual 

FSX™ Fire and Flame Detectors 

Model FS24X™ 

 

FS24X QuadBand Triple IR™ 

Multi-Spectrum Infrared Electro-Optical Multi-Spectral Digital WideBand IR Sensor 

Radiant Energy Fire and Flame Detector 

Содержание FS24X

Страница 1: ... Guide and Operating Manual FSX Fire and Flame Detectors Model FS24X FS24X QuadBand Triple IR Multi Spectrum Infrared Electro Optical Multi Spectral Digital WideBand IR Sensor Radiant Energy Fire and Flame Detector ...

Страница 2: ...tical Path Integrity CM1 CM1 A DartLogic FireLogic Fire Signature Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Fire Sentry Corporation Fire Sentry Corp FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5X FS6 FS6X FS7 FS7X FS8 FS8X FS9 FS9X FS10X FS10X FS11 FS11X FS12 FS12X FS14 FS14X FS15 FS15X FS16 FS16X FS17 FS17X FS18 FS18X FS19 FS...

Страница 3: ...nstallation Practices 13 U2 5 Start Up and Commissioning 14 SECTION 3 OPERATION 16U U3 1 Principle of Operation 16 U3 2 Configuring the Detector 16 U3 3 LED Status Indicators 18 3 4 Normal Operation 18 U3 5 Alarm Condition 18 U3 6 Fault Conditions 19 U U3 7 Maintenance 19 SECTION 4 APPENDIX 19U U4 1 Warranty Information 20 U4 2 Product Variations 21 U4 3 Digital Communication Options 21 U4 4 Test ...

Страница 4: ...luminum puck that provides superior ruggedness handling ease of installation and protection against EMI RFI Figure 1 1 FS24X Detector 110 Field of View Shown with 316 Stainless Steel Housing FS24X Detector Field Connectors The field connections feature two 2 connector choices for the installer 1 A removable ten 10 pin screw terminal connector J2 for hard wired relay applications 2 A removable six ...

Страница 5: ...ironmental Specifications Operating Temperature Standard 40 F to 185 F 40 C to 85 C Extended TempP 2 P 76 F to 230 F 60 C to 110 C Optional Operating Humidity Range 0 to 95 RH 100 RH condensing for short periods of time Storage Temperature 67 F to 221 F 55 C to 105 C 1 2 4 Performance SpecificationsP 2 P Field of View FS24X detectors have a cone of view of 90 horizontal and 80 vertical with the hi...

Страница 6: ... 6 1 2 6 Flame Performance Certification See Sections 4 7 3 and 4 7 4 on page 28 and 29 Agency Standard Certificate Notes LPCB EN 54 10 2002 A1 2005 1175a 02 Sensitivity settings Very High High EN 54 10 Class 1 CPR EN 54 10 2002 A1 2005 0832 CPR F0516 ...

Страница 7: ...Electronics Module Anodized Field Removable Detector Aluminum Module Puck Rugged superior protection against EMI RFI and handling plus easier field installation and replacement Three Separate Bright LED s Red Yellow Green Field status indicators with individual LED s for Alarm Fault and Normal conditions Provides superior Detector status viewing in bright outdoor environments see Section 3 6 FSC W...

Страница 8: ...lear unobstructed view of the threat area Physical obstructions between a fire and the Detector may cause the fire to be undetected 5 The Model SM4 is a 316 Stainless Steel Swivel Mount designed for the Honeywell Analytics Detector housing The adapter plate with the two 2 screw holes facing away is attached to the base of the Detector see Figure 2 1 The mounting plate with the four 4 screw holes f...

Страница 9: ...should be cleaned following the instructions listed below see Figure 2 5 2 When cleaning the Detector s sensor windows on the puck it is best to use Alcohol or IPA sparingly and a cotton swab 3 There are no serviceable parts inside the Detector puck If the puck is opened up or tampered with all warranties are voided FSX Detector Module puck Figure 2 5 CAUTION Follow static protection procedures wh...

Страница 10: ...nclosure to access the field connections 1 Loosen the set screw on the enclosure lid see Figure 2 6 Figure 2 6 2 Turn counterclockwise CCW to unscrew the enclosure lid see Figure 2 7 Figure 2 7 3 Loosen the three captive screws on the Detector Module puck see Figure 2 8 Figure 2 8 CAUTION Disconnect power before unscrewing the Housing Lid ...

Страница 11: ...see Figure 2 10 For relay configurations use the ten 10 pin plug J2 and its connector For digital and analog configurations use the six 6 pin plug J1 and its connector J2 Connector Figure 2 10 Detector Puck rear view J1 Connector Pin Connection Pin Connection 1 Auxiliary NC 1 DC Return 2 Auxiliary NO 2 RS 485 A 3 Auxiliary COM 3 RS 485 B 4 Alarm NC 4 24 VDC 5 Alarm NO 5 4 20mA Source 6 Alarm COM 6...

Страница 12: ...Installation Guide and Operating Manual Honeywell 12 Figure 2 11 Recommended Wiring Configurations ...

Страница 13: ...intenance 3 For applications requiring analog digital communications please refer to Section 3 2 of this Instruction Manual 2 4 Installation Practices UFor installations in a Hazardous Classified Area consult the National Electric Code Handbook Articles 500 through 517 for the proper installation practices For locations outside of the United States observe local and or regional regulations Model F...

Страница 14: ...rol panel or device Note Honeywell Analytics FSX Detectors feature an automatic built in through the lens test that verifies the cleanliness of its viewing window lens and test its internal electronics and software As with a n y any optical fire and flame detector this does not constitute a fully functional end to end test as these types of internal self tests only Upartially Ucheck and test the o...

Страница 15: ... feet Activate the Test Lamp by pressing and holding its pushbutton While watching the red ALARM LED on the face of the Detector slowly move the Test Lamp s boresight to ensure the Detector receives its full intensity UNOTE Practicing this technique may help to optimize testing of the FSX DetectorsU Sections 3 6 and 4 4 The Detector s red ALARM LED will illuminate usually within three 3 to ten 10 ...

Страница 16: ...false alarm source s Honeywell Analytics has developed and refined these complex proprietary and patented WideBand IR algorithms over the last 30 years These patented algorithms perform real time DSP and precisely analyze the signals in high resolution frequency and time domains This decision making process involves thousands of real time calculations every second Honeywell Analytics FS24X Detecto...

Страница 17: ...to set to De Energizied the Detector will not report any faults due to loss of input power to the Detector Energized ON De Energized OFF Analog and digital outputs are available in addition to relay outputs Select from two 2 analog outputs or two 2 digital outputs using a ten 10 position Rotary Switch SW3 FireBusII is the factory default setting Use Table on the right and Figure 3 3 to configure S...

Страница 18: ...ation of the Green LED Normal Operation is defined as the Detector with 24 VDC applied and no Alarm or Fault conditions are present If one of the 4 20 mA options are selected Table 3 1 the current sink or source will be 4 0 mA 0 6 mA Only the current source mode has been certified to the EN54 10 standard Figure 3 4 Green LED Location 3 5 Alarm Condition When an Alarm condition occurs the Red LED w...

Страница 19: ... for the Standard Version One or more Microprocessor Failures One or more Relay Coil Failures Communication Fault Electronic Self Test Failure Dirty Window Lens Yellow LED flashes the Yellow LED is ON solid for all other Faults 3 7 Maintenance After the FS24X Detector is installed and commissioned there is little maintenance required However a complete end to end test of the entire fire detection ...

Страница 20: ...oss of time inconvenience commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such product to the full extent such may be disclaimed by law THIS WARRANTY DOES NOT COVER 1 Defects or damage resulting from use of the Product s in other than its normal and customary manner 2 Defects or damage fro...

Страница 21: ...led of View General Applications with Relays 4 20mA Output FireBusII 316 Stainless Steel Enclosure with inch NPT Conduit Entries FM cFM ATEX IECEx Class I Division 1 Groups A B C D Class II Division 1 Groups E F G Class III Class I Zone 1 AEx d Ex d IIC Hazardous Locations ATEX IECEx Class I Zone 1 Ex db IIC T4 T6 and Ex tb IIIC T4 T6 Model Numbers FS24X Outputs 1 Relays 4 20mA FireBus II Modbus 2...

Страница 22: ... Internal Detector testing and window lens cleanliness testing cannot insure the Detector is aimed properly that its view of the fire scene has not been blocked by something such as a newly installed pipe or duct storage box parked vehicle etc and its alarm outputs are functioning properly For calibrated testing in compliance with NFPA 72 Codes for flame detectors as manufacturers of the FSX produ...

Страница 23: ...15m 90 feet 27 meters 5 seconds Ethanol 12 in X 12 in 0 3m X 0 3m 60 feet 18 meters 5 seconds IPA 6 in X 6 in 0 15m X 0 15m 90 feet 27 meters 8 seconds JP 4 6 in X 6 in 0 15m X 0 15m 90 feet 27 meters 5 seconds JP 8 6 in X 6 in 0 15m X 0 15m 90 feet 27 meters 5 seconds Methane 48 in X 3 8 in 1 2 meter Plume 90 feet 27 meters 5 seconds Methanol 12 in X 12 in 0 3m X 0 3m 60 feet 18 meters 5 seconds ...

Страница 24: ...feet 9 inches 1 14 meters Source at 15 feet 4 57 meters Fire at 30 feet 9 14 meters Continuous Arcwelding 3 feet 9 inches 1 14 meters Source at 15 feet 4 57 meters Fire at 30 feet 9 14 meters Resistive Electric Heater 1 foot 30 48 centimeters Source at 3 feet 91 44 centimeters Fire at 200 feet 60 96 meters Flourescent Lamp 1 foot 30 48 centimeters Source at 3 feet 91 44 centimeters Fire at 200 fee...

Страница 25: ...Installation Guide and Operating Manual Honeywell 25 4 7 Drawings 4 7 1 Outline and Dimensions Figure 4 3 Outline Dimesional Drawing for FS24X Figure 4 4 Outline Dimesional Drawing for SM4 ...

Страница 26: ...20mA Sourcing Analog Output Figure 4 6 Typical Wiring for 4 20mA Sinking Analog Output NOTES 1 Cable shield must be grounded at one end only at the Control Panel Coil and tape cable shield at the Detector end 2 Set SW3 rotary switch to position one 1 for Source current wiring 3 Set SW3 rotary switch to position zero 0 for Sink current wiring ...

Страница 27: ...y Contacts N O Note 3 Note 2 Note 4 EOL Note 1 Figure 4 8 Typical Relay Output Wiring for Monitoring Alarm and Fault Contacts on a single two wire input NOTES 1 Cable shield must be grounded to Earth Ground at the Control Panel end only Coil and tape the cable shield at the Detector end 2 Alarm relay contacts shown with no power applied Alarm relay is normally De Energized during normal operation ...

Страница 28: ... 003 FS24X 9 Label FS24X 9 ss with FM Canada US ATEX IECEX approval 0 020 316 Stainless Steel QuadBand Triple IRTM 1175a 02 0832 CPR F0516 Matte Black 150 60ºC to 110ºC 60ºC to 75ºC 60ºC to 60ºC Part Number Model Number Material Background Color Text Color mA T4 T5 T6 LB 6093 041 FS19X 0 020 Al 1100 Hl4 Black White 150 40C to 110C 40C to 75C 40C to 60C LB 6093 042 FS19X 0 020 316 Stainless Steel P...

Страница 29: ...17 19 27 Features and Benefits 7 FireBus II 13 16 17 19 20 21 22 H Hazardous Locations 4 5 8 14 I Installation Practices 13 L LEDs green 7 18 red 7 18 yellow 7 16 18 19 M Maintenance 19 Modbus 7 21 22 Module 9 10 11 19 21 Mounting Instructions 5 8 9 Multi spectrum 4 16 O Opening the Detector 10 11 P Principle of Operation 16 Product Overview 4 Product Variations 21 R radiant energy 4 8 Relay Coil ...

Страница 30: ...on Science Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Email analytics ap honeywell com Internet These Honeywell websites may be of interest to Industry Solution customers Honeywell Organization URL Corporate www honeywell com Honeywell Analytics www honeywellanalytics com Telephone Contact us by telephone at these numbers Organization Phone Number Americas Honeywell Analytics Inc 1 ...

Страница 31: ...Installation Guide and Operating Manual 1998M0901 Revision C September 2015 2015 Honeywell International Inc ...