40
FS20X Fire and Flame Detectors
Additional Performance Specifications
Flame Response Sensitivity
This table provides typical response times for various fuels:
MultiBand IR plus UV Detector
Location
Fuel
Fire Size
Distance
(ft/m)
Typical
Response
Time
(seconds)
Indoors
Acetylene 12 in (0.30 m) plume - medium flame
35/10.7
2
Acetylene 10 - 12 in (0.25 - 0.30 m) plume - lazy flame
40/12.2
< 2
Diesel
6 in X 6 in (15.2 cm X 15.2 cm)
87/26.5
< 3
Ethanol
12 in X 12 in (0.3 m X 0.3 m)
50/15.2
< 3
Hydrogen 3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
85/25.9
< 3
IPA
6 in X 6 in (15.2 cm X 15.2 cm)
87/26.5
< 3
JP4
6 in X 6 in (15.2 cm X 15.2 cm)
75/22.9
< 3
JP8
6 in X 6 in (15.2 cm X 15.2 cm)
87/26.5
3
Methane
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
70/21.3
< 3
Methanol 12 in X 12 in (0.3 m X 0.3 m)
40/12.2
< 3
n-Heptane 6 in X 6 in (15.2 cm X 15.2 cm)
87/26.5
< 3
Silane
1/32 dia (0.8 mm) orifice, 12 in (0.3 m) plume
30/9.1
< 2
Out-
doors
Acetylene 12 - 16 in (0.30 - 0.41 m) plume - large flame
100/30.5
< 3
Acetylene 12 in (0.30 m) plume - medium flame
100/30.5
< 4
Acetylene 10 - 12 in (0.25 - 0.30 m) plume - lazy flame
90/27.4
< 3
Diesel
12 in X 12 in (0.3 m X 0.3 m)
150/45.7
4
Ethanol
12 in X 12 in (0.3 m X 0.3 m)
60/18.3
< 3
Hydrogen 3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
75/22.9
< 3
IPA
12 in X 12 in (0.3 m X 0.3 m)
150/45.7
< 3
JP4
12 in X 12 in (0.3 m X 0.3 m)
150/45.7
< 4
JP8
12 in X 12 in (0.3 m X 0.3 m)
150/45.7
< 4
Methane
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
60/18.3
2
Methanol 12 in X 12 in (0.3 m X 0.3 m)
40/12.2
< 2
n-Heptane 12 in X 12 in (0.3 m X 0.3 m)
200/61.0
< 4
Silane
1/32 dia (0.8 mm) orifice, 12 in (0.3 m) plume
50/15.2
< 3