FL-PS Series Instruction Manual —
P/N LS10227-001FL-E:B 3/29/2021
25
Output Circuit Control DIP Switch Settings
Programming Options
3.2 Output Circuit Control DIP Switch Settings
Each output circuit has its own programming DIP switch. DIP switches S2-S8 are labeled on the PCB to indicate which output circuit it
is controlling. Output circuits are labeled at the top of the PCB, TB8-TB14.The following table applies to DIP Switches S2-S8.
Important!
If an output circuit is overloaded, the output will shut off and generate a trouble signal. If this happens, the FL-PS will need
to be reset manually. Either reset circuit configurations by toggling switch S1 position 10 to the OFF position for a minimum of five sec-
onds or turn off primary and secondary power and reapply to the FL-PS.
3.2.1 Output Circuit Programmable Features Description
Command Inputs/NAC Circuits
The FL-PS allows for individual NAC circuit programming. Each NAC can be configured to activate based on the settings selected for
up to 3 command inputs.
OFF
ON
Display Trouble History
ON
ON
Normal
Table 3.6 Operating Mode
DIP Switch Position
Output Control Setting/Operation
1
2
OFF
OFF
NAC output will activate when Command Input #1 is activated.
ON
OFF
NAC output will activate when Command Input #2 is activated.
(
Exception
: this Input controls Horn silencing during Selective Silence operation.)
OFF
ON
NAC output will activate when Command Input #3 is activated, if available.
(If accidentally
programmed on a FL-PS6, the system will default to Input #2.)
ON
ON
NAC output will activate when ANY Command Input is activated.
3
4
5
6
Output Control Setting/Operation
OFF
OFF
OFF
OFF
Unused/Unsupervised. Outputs will not activate.
Factory default setting.
ON
OFF
OFF
OFF
Reserved- Outputs will not activate
OFF
ON
OFF
OFF
Non-resettable auxiliary power
OFF
OFF
ON
OFF
Resettable aux power
ON
ON
OFF
OFF
Door holder auxiliary power
ON
OFF
ON
OFF
Slave mode (NAC follower)
OFF
ON
ON
OFF
Master mode - ANSI Temporal (Temporal 3)
ON
ON
ON
OFF
Master mode - CO Temporal (Temporal 4)
OFF
OFF
OFF
ON
Master mode - Amseco/Potter
OFF
ON
OFF
ON
Master mode - Gentex
OFF
OFF
ON
ON
Master mode - System Sensor
OFF
ON
ON
ON
Master mode - Wheelock
ON
OFF
OFF
ON
Master mode, Selective Silence - Amseco/Potter
ON
ON
OFF
ON
Master mode, Selective Silence - Gentex
ON
OFF
ON
ON
Master mode, Selective Silence - System Sensor
ON
ON
ON
ON
Master mode, Selective Silence - Wheelock
7
Output Control Setting/Operation (Only applies when ZNAC-PS is installed)
OFF
Class B
ON
Class A
8
Output Control Setting/Operation (Unused)
OFF
Unused/Unassigned
ON
Unused/Unassigned
Table 3.7 S2-S8 Output Circuit DIP Switch Settings
Position 1
Position 2
Output to Command Input Assignment
OFF
OFF
NAC will activate when Input #1 activates.
ON
OFF
NAC will activate when input #2 activates.
(
Exception
: this Input controls Horn silencing during Selective Silence operation.)
Table 3.8 NAC Activation Settings