ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
Appendix J: Canadian Application
•
The ES-50XC is supplied standard with the DP-ES-R Dress Panel for Canadian applications.
•
When installing and programming the FACP, the Canadian Option must be set to
ON
prior to any other panel programming (refer to
“Canadian Option” on page 77 of the Programming Section of this manual).
•
At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary operator interface. Wiring to the ANN-
LED must be in metal conduit and must be connected to the FACP’s Primary ANN-BUS.
•
If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit.
•
The installer must write in the
Date of Final Assembly
on the Master Marking and Warranty Label located on the FACP backbox
door.
•
Positive Alarm Sequence (PAS) and the Pre-Signal option are not available for Canadian applications.
•
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
•
The F2 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation. This
prevents the NAC from advancing to the second-stage alarm.
•
The F3 function key is automatically configured to force active two-stage NACs into the second (alarm) stage. It advances NAC
coding directly to the second stage alarm.
•
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
•
AlarmNet supervision settings for panels communicating by Cellular-only and Ethernet-only communications are fixed at 3
minutes and cannot be changed regardless of programming selection.
Figure J.1 FACP Minimum Configuration - Single ANN-LED
FACP
ANN-LED
ANN-LED
ANN-I/O
ANN-S/PG
ANN-RLY
Optional Secondary ANN-BUS (data on
connector TB10, power on TB11 Terminals 5&6
with power programmed as non-resettable)
Primary ANN-BUS (data on
connector TB9, non-
resettable power on TB11
Terminals 1&2) in metal
conduit (adjacent to FACP)