ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
133
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings.
Program Option
Factory Default
Program Option
Factory Default
Detector Programming
Not Installed
Waterflow Silenceable
No
Detector Type
Smoke-Photo
Relay 1
Alarm
Detector Verification
Off
Relay 2
Trouble (fixed)
Detector Walktest
Yes
Relay 3
Supervisory
Detector PAS
No
Communicator Installed
Yes
Detector Presignal
No
POTS, Ethernet, Cellular Enabled
No
Detector Zone Assign.
000 only
Ethernet, Cellular Location ID
0000
Detector Adj/Noun
none
Ethernet, Cellular CS ID
0000
Module Programming
Not Installed
POTS, Ethernet, Cellular Account Code
000000
Module Type
Monitor
POTS Enabled
No
Module Walktest
Yes
POTS Type
Touchtone
Module Presignal
No
POTS Supervised
No
Module Zone Assign.
000 only
Gains Dialing
Normal
Module Adj/Noun
none
Gains Reporting
Normal
Module Control Module Delay
No
IP Settings- DHCP
Enabled
Zone Type
Alarm Zone
Trouble Report Limit
0
Zone 000 Enable
Enabled
Report Style
Point
Zone 001 Enable
Enabled
AC Loss Delay
2
Zone 002 Enable
Enabled
Primary Account Code
000000
Zone 003 Enable
Enabled
Secondary Account Code
000000
.........................through..........
.....................
Test Time
0100
Zone 045 Enable
Enabled
Primary Phone Number
Special Purpose Zones 046-049
Off
Secondary Phone Number
Loop Class
Class B
Primary Comm Format
Ademco Contact ID
Loop Protocol
LITESPEED
Secondary Comm Format
Ademco Contact ID
Trouble Reminder
24 Hr
ANN-Primary Enabled
No
Banner
ANN-Primary Modules Addr. 1 - 8
None
Time Format
12 Hr
ANN-Secondary Enabled
No
Hours Setting
12
ANN-Secondary Modules Addr. 1 - 8
None
Minutes Setting
00
ANN-S/PG Port
Serial
Second Settings
00
ANN-S/PG Baud
9600
AM-PM Setting
AM
ANN-S/PG Data Bits
7
Month Setting
01
ANN-S/PG Parity
Even
Day Setting
01
ANN-S/PG Stop Bits
1
Year Setting
00
ANN-S/PG Offline Timer
60
Daylight Savings
Enabled
ANN-S/PG Printer Supervision
No
Month Start Daylight Savings
April
ANN-80/100 Piezo Enabled
Yes
Week Start Daylight Savings
Week 2
ANN-80/100 Lock Enabled
Yes
Month End Daylight Savings
November
ANN-80/100 Acknowledge Button Enabled
Yes
Week End Daylight Savings
Week 1
ANN-80/100 Silence Button Enabled
Yes
Alarm Verification
Off
ANN-80/100 Reset Button Enabled
Yes
PAS Timer
0
ANN-80/100 Drill Button Enabled
Yes
Presignal Timer
0
ANN-I/O Point/Zone
Zone
Waterflow Retard Timer
0
ANN-I/O Range
00-29
Control Module Delay Timer
0
ANN-I/O Active LEDs Only
NAC 1 & 2 Enable
Enabled
ANN-RLY Relay 1
Zone 1
NAC 1 & 2 Silenceable
Yes
................through.......................
............
NAC 1 & 2 Type
Strobe Sync
ANN-RLY Relay 10
Zone 10
NAC 1 & 2 Sync Type
System Sensor
ANN-LED Point/Zone
Zone
NAC 1 & 2 Autosilence
0
ANN-LED Alarms/ATS (Alarm, Trbl, Supv)
ATS
NAC 1 & 2 Coding
Steady
ANN-LED Range
0 - 9
NAC 1 & 2 Zones
Zone 000 only
F1 - F4 function keys
Disabled
NAC 1 & 2 Silence Inhibit
No
Master Password
00000000
Charger Enabled
Yes
Maintenance Password
11111111
4XTM Supervision
No
Upload/Download Password
22222222
Remote Sync Enabled
Yes
Aux Power Class A
No
Aux Power Resettable
No
Canadian Option Enabled
No