7.13 Configuring a Generic Device Support Block
The Generic DSBs (GENDSB, GENIODSB, GENPADSB, GENPAGWDSB) is configured for the PROFIBUS
devices that do not have device-specific DSBs. Although Generic DSBs can be used for configuring devices
with device-specific DSBs, Honeywell does not recommend this.
Attention
If the PROFIBUS PA devices are connected to a transparent PROFIBUS PA Coupler, you must use the GENPADSB.
If the PROFIBUS PA devices are connected to a DP/PA Link, Siemens DP/PA link IM-157, you must use the
GENPAGWDSB.
Prerequisites
• The PGM block and the Protocol Blockmust be defined.
• The PROFIBUS slave devices must be defined in the Field Network Configuration tab of the Protocol
Blocks.
Perform the following steps to configure a GENDSB
1
Drag-and-drop the Generic DSB (GENDSBDP/GENIODSBDP) block from the DSB library to one of the
Protocol Blocks.
The
Load Dialog
box appears.
Attention
For DSB blocks, the
State to Load
and
Post Load State
conditions are not applicable. For more information on
loading control strategy components, refer to the
Control Building User's Guide
.
2
Click
OK
.
The DSB block icon appears under the Protocol Block to which it is assigned.
3
Double-click the Generic DSB in the Project view.
4
In the
Tag Name,
box, typethe name of the DSB (a maximum of 16 characters) or accept the default.
5
In the
Item Name
box, type the item name.
6
In the
Description
box, type a brief description (a maximum of 132 characters) of the block.
7
In the
Byte Order
list, select the byte order.
You can define the byte order in the little-endian or big-endian format.
Attention
If you do not select the byte order, an error message "DSBByteOrderNotSelected" appears when you load the DSB
block.
8
In the
Associated Asset
box, click the button.
The
Point Selection
dialog box appears.
9
Select an asset from those configured in the Enterprise Model Database to set the Scope of Responsibility
(SOR) for the point.
No validation is done at the configuration time. If you enter an asset that does not exist in the points
database, the associated asset for the point reverts to the server point. If the asset does exist but is not an
area-enabled asset, then the first area-enabled asset up the tree is used for the SOR of that device. A
subsequent upload of that device point to Control Builder returns the area-enabled asset and not the original
non-assignable asset entered.
10
In the
Slave Address
box, type the address number of the slave device.
• The slave device address range is 2 through 125.
• This address must be identical to the address of the slave device defined during the field network
configuration.
7 DEVICE SUPPORT BLOCK (DSB)
148
www.honeywell.com
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...