ExiLED
Surface mounted
Important notice when installing
luminaires within the same area!!!
To avoid that luminaires perform their
battery test at the same day, connect
the battery packs with more than 1,5
minutes inbetween.
Installation:
The product contains bracket for wall mounting and spacers for ceiling mounting.
Step 1:
Dismantle the luminaire by sliding the mounting part as shown in picture.
Fasten the mounting part (with screws from within) to either wall bracket
(supplied), ceiling (with or without supplied spacers), pendulum, wire or
flag bracket.
Step 2:
Pass the mains cables through one of the cable glands. Connect the mains
cables to terminal blocks:
L
for live wire,
N
for neutral and
PE
for ground.
The
C1
and
C2
terminals are used for elBus communication (optional) or
voltage free contact (optional). Tighten the cable tie around the cables.
Step 3:
Connect the battery pack. Next to the battery connector is a jumper where
maintained/non-maintained operation can be selected. Bridge pin 1-2 for
non-maintained or pin 2-3 for maintained (default).
Step 4:
Carefully slide the sign in place.
Step 5:
Slide the two aluminium parts carefully together.
Step 6:
Fasten the two screws (included) as shown in picture.
Step 7:
Fasten the two screws (included) as shown in picture.
Note: In case of mains power disconnection for a period of more than
two months, the battery must be disconnected.
1
4
3
2
6
5
7
Dimensional drawings:
ExiLED22 ExiLED34 ExiLED44
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway