T7460A,B,C,D,E,F

WALL MODULES

INSTALLATION INSTRUCTIONS

BEFORE INSTALLATION

All wiring must comply with local electrical codes and

ordinances or as specified on installation wiring diagrams.

Wall module wiring can be sized from 16 to 22 AWG (1.5

to 0.34 mm

2

), depending on the application. The maximum

length of wire from a device to a wall module is 1000 ft

(305 m). Twisted-pair wire is recommended for wire runs

longer than 100 ft (30.5 m).

COVER DISASSEMBLY

The cover of the wall module is fixed in place using a tab

located on the underside of the unit; to disassemble the

cover and the subbase, see Fig. 1.

Fig. 1. Cover disassembly.

Table 1. Features of T7460 Versions

Sensor

Setpoint Bypass/ LED Fan speed

T7460A

-

-

-

T7460B

-

-

T7460C

-

T7460D

-

5-position

T7460E

3-position

T7460F

5-position

INSTALLATION

The T7460B,C,D,E,F packages include two setpoint dials.

By default, the “Celsius Relative” type is mounted. This can

be easily replaced with the “Celsius Absolute” type by

pulling the one dial off and inserting the other one.

Mount the T7460A,B,C,D,E,F Wall Modules on an inside

wall approximately 54 in. (1.3 m) from the floor (or in the

specified location) to allow exposure to the average zone

temperature.

NOTE:

Maintain a mounting clearance of approx. 4 in.

(10 cm) to the left-hand side of the module in

order to allow a free airflow for the temperature

sensor and accessibility of the setpoint dial.

Do not mount the wall modules on an outside

wall, on a wall containing water pipes, or near air

ducts. Avoid locations that are exposed to

discharge air from registers or radiation from

lights, appliances, or the sun.

The T7460D,E,F should not be connected to

controllers that do not support fan operation

(e.g. W7751, W7762, W7763).

Keep wiring at least one ft (305 mm) away from

large inductive loads such as motors, line starters,

lighting ballasts, and large power distribution

panels.

Run wall module wiring separately from 50 Vac or

greater power wiring.

The wall modules can be mounted on a 60-mm wall outlet

box using No. 6 (3.5-mm) screws or on a wall (see Fig. 2

and 5). When mounting directly on a wall, use the type of

screws appropriate for the wall material.

Fig. 2. Bore-holes for T7460 wall modules in in. (mm).

See Fig. 3 for T7460A,B,C,D,E,F mounting dimensions.

Проектирование

Монтаж

Продажа

. - http://vskd.ru

Содержание EXCEL 5000 OPEN T7460A

Страница 1: ... the other one Mount the T7460A B C D E F Wall Modules on an inside wall approximately 54 in 1 3 m from the floor or in the specified location to allow exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the...

Страница 2: ...T7460A B C D E F WALL MODULES 95 7610 2 2 NOTE Graphics show E F model Dimensions are the same for all six models Fig 3 T7460A B C D E F dimensions in in mm Проектирование Монтаж Продажа http vskd ru ...

Страница 3: ...he T7460 wall modules are compatible with W7751A C E G VAV1 and W7752D1 FCU1 Controllers IMPORTANT Screw type terminal blocks are designed to accept no more than one 16 AWG 1 5 mm2 conductor Wire the terminal blocks as follows 1 Strip 3 16 in 5 mm of insulation from the conductor 2 Insert the wire in the required terminal location and tighten the screw to complete the termination 3 Verify jumper s...

Страница 4: ...B C D E F WALL MODULES 95 7610 2 4 Fig 7 Wiring diagram for T7460A B Wall Modules Fig 8 Wiring diagram for T7460C D E F Wall Modules for the jumper settings see Fig 6 Проектирование Монтаж Продажа http vskd ru ...

Страница 5: ...odule LONWORKS will be connected to the two LON terminals A PC connection can be established using the 3 5 mm jack plug Order quantity set with 5 pieces Fig 9 T7460 LONJACK Mounting Remove the setpoint dial and put in the T7460 LONJACK as shown in the following Fig 10 Mounting T7460 LONJACK Проектирование Монтаж Продажа http vskd ru ...

Страница 6: ...eywell com http www honeywell ca http europe hbc honeywell com 95 7610 2 Rev 04 02 7157325 Printed in Germany Subject to change without notice T7460 LIMITER The T7460 LIMITER can be used to adjust the setpoint dial to particular setpoints Put the limiters approximately opposite the setpoints you want to adjust In the following example the setpoints are at about 18 and 27 C Order quantity set of 10...

Отзывы: