EXCEL 500/600 INSTALLATION INSTRUCTIONS
Excel 500-XCL5010
Plug in the communication module until it snaps into the con
1.
Attach the DIN rail mounting clips to the housing.
troller housing
2.
Mount the controller on the DIN rail.
NOTE:
If the communication module has been replaced or
pulled out and plugged in again, push the reset
1
00
00
07
9a
button after power on.
1
2
3
Fig. 16. Mounting Excel 500-XCL5010 on DIN rail
Excel 500-XCL5010 Communication Module
CAUTION
Always plug in the communication module
before
connecting the power supply.
Always disconnect the power supply
before
unplugging the communication module.
Installation through a Control Panel Door
(not XCL5010)
IMPORTANT
Observer the minimum spacing of 1.5 in. (35 mm)
when installing more than one housing. Do not ex-
ceed the maximum spacing; otherwise, the tailor-
made internal bus cables will be too short.
1,
Prepare the door in accordance with the following.
dimensions.
Fig. 18. Panel door mounting dimensions
2.
Insert the housing.
00
00
04
3a
Fig. 17. Inserting the communication module
EN1R-1047GE51 R0902
10
Fig. 19. Inserting the housing in the panel door
3.