Excel 50 

MMI 

 

 
 

 

 

USER GUIDE 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 
 

 

 

 

 

Содержание Excel 50

Страница 1: ...Copyright 2016 Honeywell Inc All Rights Reserved EN2B 0222GE51 R0216 Excel 50 MMI USER GUIDE ...

Страница 2: ...nBuilder NodeBuilder LonManager LonTalk LonUsers LonPoint Neuron 3120 3150 the Echelon logo the LONMARK logo and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries LonLink LonResponse LonSupport and LonMaker are trademarks of Echelon Corporation ...

Страница 3: ... Point Attributes 10 The Time Programs Fast Access Key 11 Time Programs 11 Time Schedules 12 The Today Time Schedule 13 The Daily Time Schedule 15 Deleting and Copying Creating Daycycles 17 Deleting a Switch Point 18 Creating a Switch Point 19 The Weekly Time Schedule 19 The Annual Time Schedule 21 Creating Additional Annual Time Schedules 23 Navigating through Annual Time Schedules 23 Deleting An...

Страница 4: ...r 42 Point in Alarm 43 Critical Non Critical Alarms 43 Alarm Attributes 43 System Alarms Description 43 Min Max Limit Monitoring 43 Powering Up Resetting the Controller 47 Hardware Interface Configuration 48 Choosing an Application Manually 49 Downloading an Application 51 Setting Up the Test Mode with Default Data Point Names 52 Appendix 1 Data Point Attributes 56 Analog Input Data Point Attribut...

Страница 5: ...I USER GUIDE v EN2B 0222GE51 R0216 Individual Data Point Attributes 61 Data Point Name 61 Appending the Controller s Number to the Data Points Names 61 The Operating Mode Attribute 61 Optimizing a Switch Point 62 ...

Страница 6: ......

Страница 7: ...nt software improvements facilitating operation of the MMI These improvements are essentially as follows The number of keystrokes necessary to access important information and or to reconfigure applications has been considerably reduced Moving from screen to screen has been simplified The utilization of space in the display screen has been optimized Additionally one important hardware improvement ...

Страница 8: ...EXCEL 50 MMI USER GUIDE EN2B 0222GE51 R0216 viii ...

Страница 9: ...TOR S TERMINAL Fig 1 Excel 50 Man Machine Interface The Excel 50 controller s MMI Man Machine Interface see Fig 1 consists of a keyboard and a display described below Keyboard The keyboard has 8 basic function keys and 4 fast access keys described below ...

Страница 10: ...ious field or to the last field of a previous screen equivalent to page up PLUS Increases the displayed numerical value by 1 In the case of a digital state it changes the state to the opposite state Increments scroll bar values i e destination screens Creates new Daily or Annual schedules MINUS Decreases the displayed numerical value by 1 In the case of a digital state it changes the state to the ...

Страница 11: ...r stays in same screen goes to next digit within field pages down escapes to root screen rejects change escapes to root screen no effect shifts from display to edit mode confirms value shifts from edit to display mode confirms selection Also Plant Components lists Point Attributes lists and System Topics submenus Resetting NOTE A reset has a more severe impact than simply switching off the device ...

Страница 12: ...critical alarms and non critical alarms LCD Display The LCD display can present four lines of alphanumeric text with 16 characters per line and has been provided with back lighting to improve legibility Screen usually contain one or more edit fields and display fields interspersed among its four lines The current edit field is indicated by the presence of a cursor arrowhead to the left of it In th...

Страница 13: ...e correct the initialization sequence should be immediately followed by the entry sequence see section Entry Sequence on page 5 Entry Sequence After the application has been downloaded the entry sequence will begin The first screen is the start screen see Fig 4 Fig 4 The start screen The start screen includes the name of the application in this case HE01 as well as the current date and time If BW ...

Страница 14: ...cess level 1 no password is necessary and only those screens accessible at that level will be displayed see also Table 2 In order to enter access levels 2 and 3 a corresponding password must be entered Table 2 Access Levels and Corresponding Authorizations access level PLANTS key TIME PROGRAMS key SYSTEM TOPICS key ALARMS key 1 read only read only no effect read only 2 read only time schedules no ...

Страница 15: ...on completion of password entry confirm using the ENTER key You can then leave this screen and return to the start screen using the CANCEL key If you wish to modify a password select the Change field This will take you to the Modify password screen see also section Modifying the Password on page 7 Modifying the Password In order to modify a password you must already be in access level 3 After havi...

Страница 16: ...ill cause a listbox headed Plant Components to appear see Fig 8 Fig 8 Listbox of plant components data point groups Depending upon your given application see Table 3 on page 9 and configuration data this listbox will contain a varying number of items i e data point groups meaning that you may have to scroll downwards through several screens in order to display all of the items ...

Страница 17: ... Circ 3 Boiler Dom Hot Water LON meter Zone1 Heat meter Alarms Zone2 Alarms Time Programs Zone3 Time Programs LON Zone4 LON Htg Strategy Alarms Time Programs LON Data Points Selecting an individual group of data points e g Sensors will cause a listbox including a scrollbar at the right hand margin with a corresponding heading to appear see Fig 9 Fig 9 Listbox of data points belonging to a plant co...

Страница 18: ...with a corresponding heading to appear see Fig 10 Fig 10 Data point attributes first screen of a series Depending upon the type and sub type of the given data point see section Types of Data Points on page 25 this series will consist of a varying number of screens containing edit fields in which you can specify the data point s various different attributes You will thus have to scroll sideways thr...

Страница 19: ...ures and states e g ON or OFF to data points belonging to a specific time schedule These values states will then become active inactive at the switch points i e starting and stopping times you specify Various different time schedules are grouped together to form a so called time program NOTE You will have to be in access level 2 or 3 in order to edit a data point s value state and or switch points...

Страница 20: ... AHU_Strategy Heating Circ 1 Heating Circ 1 2 Heating Circuit Heating Circ 2 Heating Circ 2 3 Time Programs Heating Circ 3 Dom Hot Water1 4 Zone Htg_Strategy Dom Hot Water2 5 LON Dom Hot Water Time Program 1 6 Time Program 1 Time Program 2 7 Time Program 2 Time Program 3 8 Time Program 3 Alarm NonCrit En 9 Time Prog Lon 1 Time Prog Lon 1 10 Time Prog Lon 2 Time Prog Lon 2 11 Time Prog Lon 3 Time P...

Страница 21: ... change to the data point s switch points value and state without affecting the original time program NOTE In order to use the Today time schedule the data point must have a value state and switch point already assigned to it NOTE Changes to the Today time schedule affect the time program only for the current day If you change a starting switch point the new starting switch point will take effect ...

Страница 22: ...e considered here however the Today time schedule which belongs to the Heating time program contains only two data points HG1_occ and HG1_tsp NOTE In the case of listboxes spread out over three or more screens use of the scrollbar the value of which is incremented or decremented with the PLUS and MINUS keys see also Table 1 on page 3 can greatly simplify navigation by allowing the user to skip ahe...

Страница 23: ...point s it will be marked with an asterisk as shown in Fig 14 in which HG1_occ is so marked The Daily Time Schedule Selecting the Daily time schedule will cause a listbox with a corresponding heading containing the given time program and next to it the word Daily to appear see Fig 17 Fig 17 Daycycles belonging to all four time schedules Regardless of your application and the specific time program ...

Страница 24: ... data as well as upon the specific time program you have chosen this listbox will contain a number of items i e data points meaning that you may have to scroll downwards through several screens in order to display all of the items Regardless of the given daycycle however the same data points will always appear In the example considered here there are only two data points HG1_occ and HG1_tsp NOTE T...

Страница 25: ...e also section Optimizing a Switch Point on page 62 Daycycles of this kind will be needed in order to configure the individual days of the week see also Assigning Daycycles to Individual Days of the Week on page 20 of which the Weekly time schedule see section The Weekly Time Schedule on page 19 is comprised Deleting and Copying Creating Daycycles Existent daycycles can be deleted It is also possi...

Страница 26: ...ued the name DP to which the lowest number which has not already been assigned to an existent daycycle will be appended Thus the first new daycycle to be created would be named DP_1 NOTE If the COPY function is used to create a new daycycle the next free daycycle will be assigned This means that the default daycycle can be overridden by a new daycycle Deleting a Switch Point Existent switch points...

Страница 27: ...LUS key In the resultant screen see Fig 24 you will be presented with a list of all possible data points valid for this daycycle Fig 24 Creating a switch point Move the cursor to the data point for which switch points are to be defined and confirm A screen resembling Fig 19 or Fig 20 as the case may be will then appear Edit the value state and switch point s as desired and confirm The Weekly Time ...

Страница 28: ...ning that you will have to scroll downwards through several screens in order to display all of the items Assigning Daycycles to Individual Days of the Week Selecting a particular day of the week will cause a listbox with a corresponding heading containing the given time program and next to it the abbreviated name of the day of the week to appear see Fig 26 Fig 26 Daycycles assignable to days of th...

Страница 29: ... day of the week Example 1 The same daycycle namely Workday could be assigned to Monday through Friday while a different daycycle i e Weekend could be assigned to Saturday and Sunday Example 2 Let s assume that for some reason Thursday requires a different daycycle A specially created daycycle DP_2 could therefore be assigned it while the Workday daycycle is assigned to Monday Tuesday Wednesday an...

Страница 30: ...desired daycycle move the cursor to the bottom line in which the asterisks are located and confirm The following screen will then appear see Fig 29 Fig 29 Assigning a daycycle to a time period Depending upon the number of daycycles you have deleted and or created this listbox will contain a varying number of daycycles from which to choose meaning that you may have to scroll downwards through sever...

Страница 31: ...individual periods will be truncated to correspond to the starting times of subsequent time periods Time periods wholly included within other time periods will be deleted Creating Additional Annual Time Schedules It is possible to repeat the process described in section The Annual Time Schedule for other time programs This is done using the PLUS key Navigating through Annual Time Schedules It is p...

Страница 32: ...EXCEL 50 MMI USER GUIDE EN2B 0222GE51 R0216 24 THE SYSTEM TOPICS FAST ACCESS KEY Fig 31 The SYSTEM TOPICS fast access key ...

Страница 33: ...nts Physical data points are inputs and outputs directly connected to a hardware device such as a sensor or an actuator The Excel 50 MMI is equipped to handle a maximum of 22 physical data points Physical data points include the following analog inputs i e measured values received from field devices analog outputs i e modulating or floating control signals generated by the controller itself digita...

Страница 34: ...ng heading to appear see Fig 33 on page 26 Fig 33 Maintenance tasks Regardless of your application or configuration this listbox will always contain the same five items i e maintenance tasks from which to choose It will thus be necessary to scroll downwards in order to display all of the items Manual Operation Selecting Manual Operat will cause a listbox with a corresponding heading to appear see ...

Страница 35: ...ly switch to Manual To reset the mode to Auto select Manual and change to Auto NOTE Using the procedure described here the state of data points can be changed only from Manual to Auto If you wish to change the state of data points from Auto to Manual this must be done as described in Appendix 1 Data Point Attributes on page 56 If the operating mode is changed an alarm screen will appear immediatel...

Страница 36: ...firming this alarm by pressing the CANCEL key will return you to the previous screen See also section The Operating Mode Attribute on page 61 Points in Trend Selecting Points in Trend will cause a listbox with a corresponding heading to appear see Fig 37 in which it is assumed that the trend log has been set Fig 37 Points in trend Fig 38 Points in trend alternative screen Using the basic function ...

Страница 37: ...HT ARROW key go to the second screen in the sequence see Appendix 1 Data Point Attributes 5 Set the trend log to ON Trend Buffer Selecting Trend Buffer will cause a listbox with a corresponding heading to appear see Fig 39 Fig 39 Trend buffer A maximum of 20 data points with a total of 200 values can be entered into the trend buffer Move the cursor to the appropriate data point and confirm In this...

Страница 38: ...yed in the Hours Run attribute The corresponding values have a resolution of 1 minute Move the cursor to the desired data point and confirm The resultant screen see Fig 41 will then display the total running hours logged together with the number of times the device has been switched on Fig 41 Total running hours and no of times switched on DDC Parameters Selecting DDC Parameters will cause a listb...

Страница 39: ...ed to it this unit will be displayed in the upper right hand corner System Configuration Selecting System Configuration will cause a listbox consisting of two screens with a corresponding heading to appear see Fig 43 Fig 43 System configuration Regardless of your application or configuration this listbox will always contain the same six items from which to choose It will thus be necessary to scrol...

Страница 40: ...en as shown here NOTE If you wish to change the codes you must first perform a RESET see section Resetting on page 3 You will then be able to change the codes during the resultant start up sequence You may now proceed to the next screen The next screen displays the burn date and time of the current project and application You may now proceed to the next screen The final screen displays the revisio...

Страница 41: ...as been pressed The value previously displayed will be restored Daylight Saving The actual dates on which daylight savings time starts and ends in a given year must be changed on an annual basis Move the cursor to the Daylight Saving field and confirm The following screen appears Fig 46 Entering the dates for daylight savings time Using the PLUS or MINUS keys you can now enter the dates on which d...

Страница 42: ...ts of this listbox will depend upon the specific hardware interfaces which your controller features It may be necessary to scroll downwards in order to display all of the items Table 5 Contents of listbox dependent upon hardware interfaces XD50C F XD50C FC XD50C FL XD50C FCL C Bus YES YES Lon Bus YES YES B Port YES YES YES YES Modem YES YES YES YES C Bus Configuration Selecting C Bus will cause a ...

Страница 43: ... a C Bus connection NOTE If no controller number is set or if the number shown is not reconfirmed the controller will not go online on the C Bus after start up LON Bus Configuration Selecting Lon Bus will cause a screen with a corresponding heading to appear see Fig 50 and which displays the unique ID number of the Excel 50 MMI s Neuron processor Fig 50 LON bus configuration B Port Selecting B Por...

Страница 44: ...guration NOTE Changing the baud rate or the GSM PIN or executing the modem reset requires a level 3 password Baud Rate If you wish to set the baud rate for the modem ISDN terminal adapter select Baudrate GSM Personal Identification Number PIN If you wish to set the GSM Personal Identification Number PIN select GSM PIN NOTE The modem baud rate must be set to 9600 for GSM communication to work NOTE ...

Страница 45: ... Selecting Flash EPROM will cause a listbox with a corresponding heading to appear see Fig 53 Fig 53 Hardware interface configuration screens Regardless of your application or configuration this listbox will always contain the same three items from which to choose By selecting Save Applic you can burn all data of the current application into the Flash EPROM By selecting Erase Flash you can erase a...

Страница 46: ...onding message and also displaying the date and clock time will appear see Fig 55 Fig 55 Flash memory full Erasing the Flash Memory If Erase Flash is selected the following screen will appear see Fig 56 Fig 56 Erasing the flash memory Showing the Application If Show Applic is selected the following screen will appear see Fig 57 ...

Страница 47: ...lication or configuration this screen will always contain the same four entries Move the cursor to Login in order to log in to another controller on the same C bus Logoff in order to log off from the remote controller to which you are logged in at the moment appears only when accessing a slave controller from a remote controller On to enable the logging of alarms coming from other controllers on t...

Страница 48: ...ur own controller Use the LOGOFF function or select your own controller in the controller list of the LOGIN function If you do not press a key for 10 min you will also be logged off You will return to the controller list screen of the LOGIN function on your own controller Logging in to a controller that uses an XI581AH 582AH operator interface results in only part of the information from that cont...

Страница 49: ... DDC times This screen displays the execution time and RACL cycle time in seconds The cycle time can be changed to optimize the system performance NOTE Changing the cycle time requires a level 3 password Move the cursor to the Cycl Time field and confirm ...

Страница 50: ...cal alarms non critical alarms Alarm Buffer The last 99 alarms are stored in the alarm buffer Typical alarm information includes Date and time the alarm occurred Name of the data point in alarm Value state of the data point in alarm Alarm text e g MIN1 alarm When the alarm memory capacity is exceeded the first alarm is overwritten Alarms are organized on a first in first out basis The contents of ...

Страница 51: ...he Min Limit Max Limit Totalizer and Alarm State attributes you can classify alarms as either critical or non critical NOTE The Operating Mode attribute always generates a critical alarm System Alarms Description Operating malfunctions arising within a controller e g power failure or during communication with another Excel 5000 device are displayed on the Excel 50 MMI NOTE System alarms are always...

Страница 52: ...lues are available minimum limit 2 minimum limit 1 maximum limit 1 maximum limit 2 Press the ALARMS fast access key to display alarm information on alarm history points currently in an alarm condition critical alarms non critical alarms and bus wide alarms Fig 63 Sequence of screens in the alarms procedure ...

Страница 53: ... one shown to the right in Fig 64 Alarm information comprising the date time alarm name value state and alarm reason is displayed Press CANCEL to return to the previous screen NOTE The same operating method as described for Point in Alarm applies to the All Alarms Critical Alarms and Non Crit Alarms If the item Bus wide alarms has been chosen from the alarm menu a screen resembling Fig 65 will app...

Страница 54: ...EXCEL 50 MMI USER GUIDE EN2B 0222GE51 R0216 46 ...

Страница 55: ...nly non editable information the company name the model name and the firmware version You may proceed to the next screen by pressing the ENTER key The second screen presents the date format DD MM YYYY clock time format HH MM and controller number fields You can edit any or all of these fields using the basic function keys NOTE If no controller number is set or if the number shown is not reconfirme...

Страница 56: ...erator and service software or from the XBS Central A Requ Download and setting up the test mode with default data point names DP Wiring Check Move your cursor to the desired entry and confirm by pressing the ENTER key Depending upon your selection you will proceed to one of the series of screens described in the respective section below Hardware Interface Configuration Selecting and confirming Co...

Страница 57: ...guration To view configure the fourth entry Modem you will have to scroll downwards See also section Hardware Interface Configuration on page 34 Choosing an Application Manually Selecting and confirming Select Applic will cause a listbox headed Choose Applic to appear see Fig 68 ...

Страница 58: ...o the data point s name see also section Appending the Controller s Number to the Data Points Names in order to identify the controller to which it belongs In the following sequence of screens see Fig 69 the codes of the configurable application can be changed The application codes can be generated with the LIZARD Excel 50 Application Selector Fig 69 Sequence of configuration screen NOTE If the LI...

Страница 59: ...you can request a download Requ Download after which the following screen will appear see Fig 70 Fig 70 Downloading an application You may then proceed as follows 1 Establish the physical connection e g a null modem cable between the XL50 B Port and your PC 2 Launch lizard exe on your PC 3 Open one of the applications e g HE01V2 00 XD50C F FC FL FCL present in the corresponding sub folder A list o...

Страница 60: ...t s names are generated according to the following pattern AI0101 Analog input board 1 input 1 AO0201 Analog output board 2 output 1 DI0301 Digital input board 3 input 1 DO0401 Digital output board 4 output 1 NOTE The board numbers shown above are internal references and are not relevant to the User In Excel 50 Controllers the numbers are fixed for the I O type i e analog inputs are always AI01 di...

Страница 61: ...ted a listbox similar to Fig 73 will be displayed showing all default data point names and their current values Fig 73 Default data point names To manually set the state value of output data points use the ARROW keys to move the cursor to the appropriate output data point from the list box and confirm In the case of e g analog output data points a screen similar to Fig 74 will be displayed Fig 74 ...

Страница 62: ...ig 76 will be displayed showing all points in alarm as well as any system alarms max 100 entries Fig 76 Alarm history NOTE Alarms are generated for changes of state value on inputs which allows shorting and opening the inputs at the switches and or sensors and then checking the alarm buffer to verify the wiring To display an alarm use the ARROW keys to move the cursor to the default data point s n...

Страница 63: ...MMI USER GUIDE 55 EN2B 0222GE51 R0216 If by manipulating the hardware you change the state to 1 return to normal will be displayed NOTE Reset the controller after using the test options to clear the alarm buffer ...

Страница 64: ...ig 78 Analog input data point attributes as exemplified by OATemp In the first screen the data point s name which is non editable is displayed You can edit the switch point value state the engineering unit is non editable and or change the operating mode field from AUTO to MANUAL and vice versa See also section The Operating Mode Attribute NOTE If the operating mode is changed an alarm screen with...

Страница 65: ...n Max Limit Monitoring on page 43 The fifth screen displays the data point s technical address which is non editable The technical address is a six digit number The first two digits stand for the controller number The next two digits stand for the board number The last two digits stand for the physical point address Analog Output Data Point Attributes See also section Types of Physical Data Points...

Страница 66: ...f the digital input data point to be checked for a change in the event of a change an alarm is generated The AlmDelay alarm delay attribute Using this attribute the delay in seconds until an alarm is generated can be set hours run enable disables measuring of the runtime of the connected actuator e g a pump hours run not editable See also the previous sections for information on previously describ...

Страница 67: ...nt attributes as exemplified by CPU_Calc_Htg_Sp Pseudo Digital Data Point Attributes See also section Types of Pseudo Data Points on page 25 for a description of pseudo digital data points Their editable and non editable attributes are displayed in the following series of screens Fig 83 Pseudo digital data point attributes as exemplified by EXECUTING_STOP See also the previous sections for informa...

Страница 68: ... the given hysteresis absolute value is exceeded See also the previous sections for information on previously described attributes Remote Digital Data Point Attributes See also section Types of Remote Data Points on page 26 for a description of remote digital data points Their editable and non editable attributes are displayed in the following series of screens Fig 85 Remote digital data point att...

Страница 69: ...cation program exists on the C bus the controller s number must be appended to the data point s name This must be done in order to make it unique likewise the controller s number must also be appended to the controller s name in order to make it unique Bus numbers are appended automatically except in the case of remote points In the case of remote points the remote controller number must be entere...

Страница 70: ... of the control system is interrupted When the controller is in the manual operation mode the data specified manually is written into the manual value attribute processed in the controller and passed on to an output The user can of course recall the measured value coming from the value attribute but this has no effect on the application Optimizing a Switch Point The optimization function is used t...

Страница 71: ...EXCEL 50 MMI USER GUIDE 63 EN2B 0222GE51 R0216 ...

Страница 72: ...neywell Technologies Sàrl Rolle Z A La Pièce 16 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 http ecc emea honeywell com EN2B 0222GE51 R0216 Subject to change without notice ...