background image

Important Additional Notes

1.

Only suitably qualified personnel should install this equipment.

2.

All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box 
for looping cables. 

3.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

4.

This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 
some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in 
order to achieve a predicted lamp life.   Please check with the manufacturer of the luminaires to ensure that they are 
compatible with automatic controls in this respect. 

Programmable Parameters

Power Up: ON/OFF

Set to ON the detector will automatically switch both outputs on when Mains is applied. If set to OFF, the 
detector will power up without turning its outputs on, wait 30 seconds and then look for occupancy. Only if the 
area is occupied will the outputs switch on at this time. The detector must be set to Power Up ON to allow 
manual switch as opposed to infrared operation, in Semi-Automatic mode. (See below).

Response: AUTO/SEMI AUTO

Where absence detection is required, (i.e. the user manually turns the lights On, if required, but the lights still 
turn off automatically once the area is vacated), SEMI AUTO-matic operation should be selected. If the manual 
operation is to be effected using ONLY an infrared hand-held controller then Power Up OFF may be used in 
SEMI AUTO mode, but if it is desired to use a manual wall switch, Power Up ON coupled with a means of 
interrupting the mains power to the MS2021PHB is required, e.g. using a push-to-break momentary switch 
capable of switching the load on the Switched Live output, plus the load on the Volt-free output, if this is not 
supplied separately.

R1 Off Delay 

In all modes this determines the time from the last detection of occupancy to primary Lights Off. It 

can be set between 1 minute and 96 hours, or DISABLED so that the lights never turn off for lack of detected 
movement.

R2 Off Delay 

In Lighting mode this defines the period from last detected occupancy to secondary Lights Off. In 

other modes setting this to longer than R1 Off Delay allows for an extended filling time for flush cistern or for 
extractor fan or air conditioning run-on. In Emergency Test mode it is not used, so that its configured value is a 
"don't care", the duration of the Maintained Live disconnection being set by the HC8 or HP2000 command. 

R2 Mode 

This sets the mode of operation of the R2 load circuit to one of those discussed opposite

PCELL (Photocell) Mode: PASSIVE / ACTIVE / DISABLED (affects the R1 Load only)

Passive Mode 

The photocell will inhibit the turn on of the controlled lights if sufficient natural light is available but it will not 
turn the lights off whilst the area is occupied. 

Active Mode  

The photocell will both inhibit turn on of the controlled lights and turn them off during occupancy if sufficient 
natural light becomes available. Turn off occurs when there has been sufficient natural light continuously for 
a period of the R1 Off Delay or 20 minutes, whichever is the shorter. There is no delay in switching the 
lights back on when natural light reduces.

Disabled

The photocell has no effect and the lights are on for the full period of occupancy plus the Off Delay.

Commissioning

The units are supplied with factory default settings (Power-Up On, fully Automatic operation, Lighting mode,  
20 minute Off Delays,  Photocell Disabled).  Programme using the HP2000 MLS Digital Programmer with 
LCD display.

Walk-test Mode

Walk-test mode is used to check that the detector is operating as required. The short off-delay enables the 
installer to check that lights are switching on when movements are made at the edge of the detection zone.  It is 
easier to carry out a walk-test when the photocell is not holding the lights off.

1.   Change the Off Delay to 10 seconds using  ‘Utilities/Walk Test/OK’  on the HP2000.

2.   Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before moving 

and triggering the lights back on.   Note: When the HP2000 is used to engage ‘soft’ walk test mode as described 
above, the programmed Off Delay will be automatically restored after 5 minutes. 

Содержание Ex-Or MS2021PHBF

Страница 1: ...021PHBF MS2021PHBSM Hi Bay Multi Function Dual Output LightSpot with photocell MS2021PHBSM MS2021PHBF Note HP2000 required for commissioning User override available via the HC7 and HC8 dedicated and HC5 general purpose Hand held Infrared Controllers ...

Страница 2: ...programmable run on timer The HC7 is a dedicated hand held Infrared controller for this mode but the HC5 will also switch the two outputs as outlined in 1 above 4 Lighting Control Emergency Test Controller This operating mode allows the testing of an area of Emergency Lighting to be conveniently implemented without the expense of a special single function controller The Switched Live output remain...

Страница 3: ... lights never turn off for lack of detected movement R2 Off Delay In Lighting mode this defines the period from last detected occupancy to secondary Lights Off In other modes setting this to longer than R1 Off Delay allows for an extended filling time for flush cistern or for extractor fan or air conditioning run on In Emergency Test mode it is not used so that its configured value is a don t care...

Страница 4: ...tor must have already been programmed to Passive Mode 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing Utilities Set Light Level OK on the HP2000 The detector takes a measurement adds a small amount and stores the...

Отзывы: