Installation and Commissioning

Instructions

              Note: HP2000 required for commissioning

 

 MR2500D / MR2500DF

MR2500DALI / MR2500DALIF

Mid Range Regulating LightSpot

  

 MR2500D

MR2500DALI

   

MR2500DF

MR2500DALIF

Содержание Ex-Or MR2500D

Страница 1: ...Installation and Commissioning Instructions Note HP2000 required for commissioning MR2500D MR2500DF MR2500DALI MR2500DALIF Mid Range Regulating LightSpot MR2500D MR2500DALI MR2500DF MR2500DALIF ...

Страница 2: ...ations where there are large areas of metal e g metal ceiling or panelling as unpredictable sensitivity may result Also microwave presence detection is not completely attenuated by materials such as plasterboard wood and glass so the possibility of unwanted presence detection through office partitions should be considered when determining detector positioning and sensitivity settings within the in...

Страница 3: ...led completely by its digital input and therefore would normally have a permanent power supply Turning the power off to some lights within a control circuit will not affect the operation of those lights that remain powered and under the control of the MR2500D When switching via the relay output multiple MR2500Ds relay outputs may be connected in parallel provided the controlled load does not excee...

Страница 4: ...ON Sensitivity This is an approximation and should be tested on site during commissioning Like all programmable parameters the sensitivity settings will be retained in the event of a power failure and can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power Up Response Off Delay On...

Страница 5: ...below SET POINT LOW iii Photocell DISABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the...

Страница 6: ...asurement and stores the value in SET POINT LOW The lights now switch on again to acknowledge a successful programming operation The two switching thresholds have now been set and the difference between them is equal to slightly more than the contribution made by the electric lighting This is the perfect amount of hysteresis to ensure that the lights will not oscillate OneSwitch OneSwitch Dimming ...

Страница 7: ...a location for this equipment since this type of device is capable of detecting large moving metal objects well beyond the normal range at which it is sensitive to human targets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of room location where there will be excessive influence by daylight reflected from th...

Страница 8: ...5B Technical Data OPERATING VOLTAGE 230V 50Hz UK Europe SWITCH CAPACITY 10 Amps max any lighting load except incandescent lamps 1500W max at 230V MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant P...