PRODUCT DATA

68-0258ES-04

W8835 EnviraZone Panel

APPLICATION

The W8835 EnviraZone Panel controls single-stage, multi-

stage, conventional or heat pump heat/cool equipment. It 

controls three zones, and is expandable up to nine zones with 

two additional W8703A Damper Interface Modules (DIM). 

For Internet access: http://yourhome.honeywell.com.

For technical support, call: 1-800-828-8367.

IMPORTANT

Please read these instructions and keep them

in your records.

FEATURES

• Controls up to three stages heat and two stages 

cooling of single-stage, multi-stage, conventional, or 

heat pump.

• Controls up to three zones and can be expanded up to 

nine zones with two W8703A DIM.

• Uses VisionPRO® IAQ or FocusPRO communicating 

thermostats for manual or automatic changeover by 

zone.

• Supports dehumidification, humidification and 

ventilator controls.

• Purge timer protects equipment between calls for heat 

or cool with choice of panel or HVAC equipment- 

controlled fan.

• System and zone damper LEDs indicate system and 

damper status.

• Individual zone fan control.
• Supports C7835 Discharge Air Temperature Sensor for 

capacity control with adjustable high and low limits 

and equipment failure indication.

• Controls duel fuel equipment when used with an 

external fossil fuel kit.

Contents

Application.........................................................................1

Features ............................................................................2

Specifications ....................................................................2

Ordering Information .........................................................2

Installation .........................................................................4

Startup and Checkout........................................................8

Operation...........................................................................8

Troubleshooting.................................................................11

Содержание ENVIRAZONE PANEL W8835

Страница 1: ...zones and can be expanded up to nine zones with two W8703A DIM Uses VisionPRO IAQ or FocusPRO communicating thermostats for manual or automatic changeover by zone Supports dehumidification humidification and ventilator controls Purge timer protects equipment between calls for heat or cool with choice of panel or HVAC equipment controlled fan System and zone damper LEDs indicate system and damper s...

Страница 2: ...ED SYSTEM mode LEDs 5 used to communicate equipment status Red Heat Heat mode Green Cool Cool mode Yellow Purge Purge mode Green Fan Fan mode Red Em Heat Emergency Heat mode ZONE LEDs 3 used to communicate damper status Green Dampers are open or opening No Color Dampers are closed or closing COM LED 1 used to indicate communication status Flashing Green Panel is transmitting or has received data N...

Страница 3: ... two 40 VA transformers Use SDCR for additional dampers required If using RRD dampers refer to RRD installation instructions for maximum number of dampers Fig 1 W8835 dimensions in in mm Table 1 Recommended Dampers Motor Terminal Damper Action Common M1 Common Open M4 Power Open Closed M6 Power Close Honeywell Damper Type Round Rectangular For systems 2000 cfm MARD or RRD For recommended dampers c...

Страница 4: ...it on a wall or on the cold air return See Fig 2 4 Level the W8835 for appearance only Fig 2 W8835 mounting location Wiring CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before continuing installation Wiring must comply with applicable codes ordinances and regulations Accessory Description Bypass Rating cfm 40 VA transformers AT140A1042a High and low limit ...

Страница 5: ...age heat pump equipment Fig 3 Conventional equipment wiring diagram 1 2 3 1 2 3 1 2 3 L C RH RC W1 E W2 W3 AUX Y1 Y2 G O B HUM HUM DEHUM DEHUM VENT VENT R C T1 T2 ZONE1 M6 M4 M1 ZONE2 M6 M4 M1 ZONE3 M6 M4 M1 1 2 3 1 2 3 1 2 3 1 2 3 DAMPERS ENVIRACOM BUS DAMPER XFRM ENVIRACOM XFRM REMOVE JUMPERS IF T1 AND T2 ARE USED HEAT COOL ZONE 1 COM EM HEAT FAN PURGE ZONE 3 ZONE 2 W8835A DIP SWITCH SETTINGS 1 ...

Страница 6: ... RH RC W1 E W2 W3 AUX SINGLE TRANSFORMER HEATING COOLING SYSTEMS REQUIRE A JUMPER TO BE INSTALLED CONNECTING RH AND RC FACTORY INSTALLED Y1 Y2 G O B HEATING TRANSFORMER 24 VAC EQUIPMENT COOLING TRANSFORMER COMPRESSOR REVERSING VALVE COOLING HEATING FAN RELAY C L AUXILIARY HEAT 1 1 FIELD INSTALLED JUMPER M31123 HVAC EQUIPMENT RH RC C L W1 E W2 W3 AUX SINGLE TRANSFORMER HEATING COOLING SYSTEMS REQUI...

Страница 7: ...sition indication mount end switch 201052B onto the ML6161 Fig 11 Wiring MARD Damper or ML6161 Actuator to panel Transformer Wire the transformers to the panel see Fig 12 One 40 VA 24 Vac transformer is required to operate the panel and up to five ARD or ZD dampers The transformer is connected to terminals R and C The auxiliary transformer is required if up to ten dampers are connected to the pane...

Страница 8: ...stat schedule if the default settings are not desired 8 Run Discovery by pressing the Discovery button on the panel 9 Set Zone one thermostat to heat and raise the setpoint to call for heat a Verify that the heat LED is red NOTE The furnace heat may not come on immedi ately Allow at least 5 minutes for heat to begin after the thermostat calls for heat b Verify that Zone one LED remains green c Ver...

Страница 9: ...n operation for that zone When the fan setting is On the fan is energized the fan LED illuminates and the dampers close to zones where the fan setting is Auto If there is a call for heat or cool during this time the fan mode ceases and the heat or cool call is honored When the zone calling is satisfied and Purge mode has ended the fan call resumes Single and Multi Stage Conventional Heat Operation...

Страница 10: ...ooting Microprocessor To reset the microprocessor press and release the Boot button The system reboots and enters the Purge mode EnviraCom Furnace For furnaces with EnviraCom communications built in configure the panel as shown below In this case no conventional equipment wiring is necessary because the W8835 uses the 3 wire EnviraCom bus to control the HVAC equipment In these installations the pa...

Страница 11: ... air or electric heat systems Set the blower function using DIP switch 8 When configured for heat pump this DIP switch is not used Table 10 Fan in heat Configuration Adding Additional Zones Connect one W8703 to the EnviraCom bus to expand the system up to six zones or connect two W8703 to control up to nine zones Wire the first three zone dampers and thermostats to the W8835 Envirazone Panel Wire ...

Страница 12: ...ional non communicating EnviraCom Communicating 4 Purge time Two minutes 3 5 minutes 5 Fan control during purge HVAC controlled Panel controlled 6 Damper control during purge Last zone s calling open during purge Open all dampers during purge 7 Heat pump compressor stages One stage Two stages 8 Fan control in heat Fan controlled by panel in cool and HVAC equipment in heat Fan controlled by panel i...

Страница 13: ...R THE AQUASTAT AND CIRCULATOR WIRING SEE THE INSTALLATION INSTRUCTIONS FOR THE HYDRONIC RELAY PANEL 1 3 1 3 1 3 ZONE 1 ZONE 2 ZONE 3 1 2 3 1 HUM HUM DHUM DHUM VENT VENT W2 W3 AUX Y1 Y2 G O B L C Rh Rc W1 E 1 3 G Y C W8835A R T W T R T W T R T W T Jumper in place O N 1 2 3 4 5 6 7 8 9 10 DAMPERS EN IF IT IS A HEAT ONLY APPLICATION THE R AND C WILL COME FROM A TRANSFORMER RATHER THAN A FAN RELAY CEN...

Страница 14: ...835A THIS DIAGRAM SHOWS HOW THE W8835 GETS WIRED TO ZONE VALVES AND AN AIR CONDITIONER FOR HOT WATER HEATING AND FORCED AIR COOLING APPLICATIONS FOR COMPLETE AQUASTAT WIRING SEE THE AQUASTAT INSTRUCTIONS ZONE 1 M6 M4 M1 ZONE 2 M6 M4 M1 ZONE 3 M6 M4 M1 TH TR TH TR TH TR Honeywell V8043 zone valves End switch End switch End switch R T W T L8124 or L8148 aquastat Remove Rh Rc jumper R Y G M31128 ...

Страница 15: ...W8835 ENVIRAZONE PANEL 15 68 0258 04 ...

Страница 16: ...ternational Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 68 0258 04 E K Rev 08 09 ...

Страница 17: ... 8367 Para obtener más información sobre los productos de Honeywell para mejorar la calidad del aire interior visite http yourhome honeywell com o comuníquese con el siguiente número 1 800 345 6770 x531 Agencia de Protección Ambiental de los Estados Unidos EPA Estados y tendencias de la calidad de aire nacional de 1999 Indoor Air Pollution An Introduction for Health Professionals EPA Imprenta del ...

Страница 18: ...combustible fósil externo ESPECIFICACIONES Calificacione de entrada Voltaje 20 30 V CA 50 60 Hz Electricidad 11 VA nominal Clase II Calificaciones de salida reguladores y equipos de cale facción ventilación y aire acondicionado 1 5 A por ciclo 200 000 ciclos 30 V CA 3 5 A de corriente de entrada 1 5 A por ciclo 100 000 ciclos 30 V CA 7 5 A de corriente de entrada Rangos de humedad 90 HR a 95 F sin...

Страница 19: ...uladores ARD o ZD cuando se utilizan dos transformadores de 40 VA Utilice un SDCR relé plano de control de regulador para los reguladores adicionales necesarios Si utiliza reguladores RRD consulte las instrucciones de instalación de un RRD para ver el número máximo de reguladores Fig 1 Dimensiones del W8835 en pulgadas mm Terminal del motor Acción del reguladores M1 común Común M4 abierto Suminist...

Страница 20: ...ig 2 Ubicación de montaje del W8835 Cableado PRECAUCIÓN Peligro de alta tensión Puede ocasionar descargas eléctricas o dañar el equipo Desconéctelo de la fuente de energía antes de continuar la instalación El cableado debe cumplir con los códigos las ordenanzas y las reglamentaciones correspondientes Tabla 2 Accesorios necesarios no incluidos con el panel Accesorio Descripción Rango de desviación ...

Страница 21: ...para un equipo de bomba de calor de dos etapas Fig 3 Diagrama de cableado del equipo convencional 1 2 3 1 2 3 1 2 3 L C RH RC W1 E W2 W3 AUX Y1 Y2 G O B HUM HUM DEHUM DEHUM VENT VENT R C T1 T2 ZONE1 M6 M4 M1 ZONE2 M6 M4 M1 ZONE3 M6 M4 M1 1 2 3 1 2 3 1 2 3 1 2 3 DAMPERS DAMPER XFRM ENVIRACOM XFRM QUITE LOS PUENTES SI UTILIZA T1 Y T2 HEAT W8835A DIP SWITCH SETTINGS 1 SEE TABLE OFF 2 SEE TABLE 1 0 3 ...

Страница 22: ...ompresor Válvula de inversión enfr calef Relé del ventilador C L Calefacción auxiliar 1 1 PUENTE INSTALADO EN EL CAMPO MS31124 Equipo HVAC RH RC W1 E W2 W3 AUX Los sistemas de calefacción enfriamiento de un solo transformador requieren que se instale un puente que conecte a RH y RC instalado en fábrica Y1 Y2 G O B Transformador calefacción Equipo de 24 V CA Transformador enfriamiento Compresor Vál...

Страница 23: ...aliméntelo con dos transformadores de 40 VA Fig 9 Conexión del humidificador RRD al panel Fig 10 Conexión de dos humidificadores RRD en paralelo Reguladores MARD o reguladores que utilizan el actuador de motor ML6161 Conecte el regulador MARD u otro regulador que utilice el actuador ML6161 al panel tal como se muestra en la Fig 11 Estos actuadores de control flotante son controlados como dispositi...

Страница 24: ... del humidificador están en verde para indicar que los humidificadores están abiertos El LED COM comienza a titilar 3 Presione el botón Purge Override anulación del pur gado para desactivar el modo Purge purgado 4 En el panel W8835 configure los interruptores DIP a Configure los interruptores DIP 1 2 y 7 para que asignen el número apropiado de etapas de calefac ción y refrigeración Vea las Tablas ...

Страница 25: ...rgado Después de cada orden de calefacción o refrigeración el panel ingresa al modo de purgado El DIP 4 configura el panel para que purgue durante dos predeterminado o tres minutos y medio El interruptor DIP 5 configura el panel o el equipo de calefacción ventilación y aire acondicionado HVAC para que el ventilador funcione durante el purgado El LED de purgado se enciende para indicar que el siste...

Страница 26: ...ia es la utilización de una fuente de calefacción auxiliar sin utilizar la bomba de calor El W8835 activa el terminal E cuando se emite una orden de calefacción de emergencia El interruptor del sistema del termostato está configurado en Em Heat calefacción de emergencia para activar esta función Cuando está activa cualquier zona que emita una orden de calefacción utilizará la calefacción de emerge...

Страница 27: ...tremo del serpentín El sensor se conecta al bus EnviraCom por medio de tres cables Cuando se alcanza un límite máximo o mínimo el panel apaga el equipo y mantiene en funcionamiento el ventilador durante por lo menos dos minutos y medio Después de este tiempo y de cualquier tiempo mínimo de apagado impuesto por el equipo de HVAC se vuelve a activar el equipo cuando se ha recuperado el aire de desca...

Страница 28: ...entes XFRM estén configurados correctamente Mensaje Com 3 en los termostatos Configuración incorrecta Controle que DIP 3 esté configurado correctamente Tabla 12 Interruptores DIP 1 y 2 Tipo de equipo DIP 1 DIP2 Etapa 1 convencional Encendido hacia arriba Encendido hacia arriba Etapa 2 convencional Encendido hacia arriba Apagado hacia abajo abajo Etapa 3 convencional Apagado hacia abajo Encendido h...

Страница 29: ...AQUASTAT Y EL CABLEADO DEL CIRCULADOR VEA LAS INSTRUCCIONES DE INSTALACIÓN PARA EL PANEL DE RELÉS HIDRÓNICOS 1 3 1 3 1 3 ZONA 1 ZONA 2 ZONA 3 1 2 3 1 HUM HUM DHUM DHUM VENT VENT W2 W3 AUX Y1 Y2 G O B L C Rh Rc W1 E 1 3 G Y C W8835A R T W T R T W T R T W T PUENTE INSTALADO O N 1 2 3 4 5 6 7 8 9 10 HUMIDIFICADORES EN SI ES UNA APLICACIÓN EXCLUSIVA PARA CALEFACCIÓN EL R Y C VENDRÁN DE UN TRANSFORMADO...

Страница 30: ... CONECTAR EL W8835 A LAS VÁLVULAS DE ZONA Y UN AIRE ACONDICIONADO PARA APLICACIONES DE CALEFACCIÓN DE AGUA CALIENTE Y DE ENFRIAMIENTO DE AIRE FORZADO PARA VER EL CABLEADO COMPLETO DEL AQUASTAT CONSULTE LAS INSTRUCCIONES PARA EL AQUASTAT ZONA 1 M6 M4 M1 ZONA 2 M6 M4 M1 ZONA 3 M6 M4 M1 TH TR TH TR TH TR Válvulas de zona V8043 Honeywell Interruptor terminal Interruptor terminal Interruptor terminal R...

Страница 31: ...PANEL ENVIRAZONE W8835 15 68 0258ES 04 ...

Страница 32: ...onal Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com Marca Registrada en los E U A C 2009 Honeywell International Inc todos Los Derechos Reservados 68 0258ES 04 E K Rev 09 09 ...

Отзывы: